Plan Review Details - Permit 12070380
Plan Review Stops For Permit 12070380
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-10-29 Cont ID  
Sent By lmartine Date 2012-10-29 Time 13:40 Rev Time 0.00
Received By lmartine Date 2012-10-29 Time 13:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-07-27 Cont ID  
Sent By jwitmer Date 2012-07-27 Time 10:28 Rev Time 0.00
Received By jwitmer Date 2012-07-27 Time 10:27 Sent To  
Notes
2012-07-27 10:39:06BUILDING PLAN REVIEW
 PERMIT: 12070380
 ADD: 2505 N DIXIE HWY
 CONT: STONESTYLES
 TEL: (561)809-5115
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLEASE PROVIDE A LIFE DAFETY SHEET WITH A BREAK DOWN
 OF AISLE WIDTHS WITH 2010 FBC-B 1017.4. ALSO PROVIDE AN
 AREA BREAK DOWN FOR OCCUPANCY LOADS USING 15 NET FOR
 UNCONCENTRATED TABLES AND CHAIRS, KITCHEN AREAS 200
 GROSS AND OFFICE SPACE 100 GROSS. IT APPEARS THE
 OCCUPANT LOAD WILL BE GREATER THAN 50 OCCUPANTS MAKING
 THIS A CHANGE OF OCCUPANCY TO A A-2 OCCUPANCY FOR
 RESTARAUNTS. 2010 FBC-B TABLE 1004.1.1.
  
 WITH THIS BEING A CHANGE OF OCCUPANCY THE 2010 EXISTING
 BUILDING CODE WILL APPLY, CHAPTER 9,
  
 2) PLEASE PROVIDE A SURVEY OF THIS PROPERTY TO
 DETERMINE IF THIS IS A SINGLE TENANT BUILDING UNDER
 THIS PROPERTY CONTROL NUMBER, THIS DETERMINES WHICH
 SECTION TO USE IN THE EXISTING BUILDING CODE:
 901.3 FOR WHERE THE WHOLE BUILDING IS UNDER GOING A
 CHANGE OF OCCUPANCY OR
 901.3. FOR A PARTIAL CHANGE OF OCCUPANCY.
 EACH HAS SEPERATE REQUIREMENTS. FOR THIS REVIEW WE WILL
 USE WHOLE BUILDING UNDERGOING A CHANGE OF OCCUPANCY.
  
 3) EXST BLDG CODE 904.1 FIRE PROTECTION REQUIREMENTS OF
 SECTION 912 SHALL APPLY WHERE A BUILDING OR PORTIONS
 THEREOF UNDERGO A CHANGE OF OCCUPANCY CLASSIFICATION.
 EXST BLDG CODE 912.2.1 FIRE SPRINKLER SYSTEM. WHERE A
 CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT REQUIRES
 AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE PROVIDED BASED
 ON THE NEW OCCUPANCY IN ACCORDANCE WITH CHAPTER 9 OF
 THE FLORIDA BUILDING CODE, BUILDING, SUCH SYSTEM SHALL
 BE PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF
 OCCUPANCY OCCURS.
  
 4) EXST BLDG CODE 905.1 MEANS OF EGRESS IN PORTIONS OF
 BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH SECTION 912.
 2010 FBC-B TABLE 1015.1 WILL REQUIRE TWO EXITS ISNCE
 THE OCCUPANCY LOAD IS OVER 49 OCCUPANTS, PLEASE PROVIDE
 THE 2ND EXIT. NOTE BUILDINGS THAT ARE SPRINKLERED SHALL
 HAVE THEIR EXITS A MINIMUM OF 1/3 THE DIAGONAL APART.
 FBC-B 1015.2.1.
  
 5) ESXT BLDG CODE SECTION 906 ACCESSIBILITY ,906.1
 ACCESSIBILITY IN PORTIONS OF BUILDINGS UNDERGOING A
 CHANGE OF OCCUPANCY CLASSIFICATION SHALL COMPLY WITH
 THE PROVISIONS OF THE FLORIDA BUILDING CODE,
 ACCESSIBILITY.
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 PLEASE PROVIDE COMPLIANCE WITH :202.4.1
 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
 WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH
 OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 NOTE THE EXISTING RESTROOM AT THE REAR OF THE
 RESTARAUNT WILL NEED TO HAVE A RAMP TO BE ACCESSIBLE,
 PROVIDE LANDING TOP & BOTTOM OF RAMP WILL REQUIRE
 HANDRAILS IF RAMP IS OVER 6" IN HEIGHT. SEE 2010
 ACCESSIBILITY CODE 405 RAMP REQUIREMENTS 505 HANDRAILS.
  
 6) SHEET 1.0A INDICATES THE USE OF NEW IN-SWINGING
 BIFOLD DOORS, PLEASE PROVIDE PRODUCT TESTING REPORTS
 FOR THIS PRODUCT. RULE 9N-3 (31)(A) EXTERIOR DOORS /
 2010 FBC-B 1609.6
 COMPONENTS & CLADDING, 1609.1.2 PROTECTION OF OPENINGS
 & 1609.1.2.3 IMPACT RESISTANT COVERINGS.
  
 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-10-29 Cont ID  
Sent By rlecky Date 2012-10-29 Time 11:47 Rev Time 0.00
Received By rlecky Date 2012-10-29 Time 11:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-07-23 Cont ID  
Sent By rlecky Date 2012-07-23 Time 12:09 Rev Time 0.00
Received By rlecky Date 2012-07-23 Time 11:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-10-15 Cont ID  
Sent By wjolin Date 2012-10-15 Time 14:02 Rev Time 0.00
Received By wjolin Date 2012-10-15 Time 13:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-07-17 Cont ID  
Sent By wjolin Date 2012-07-17 Time 09:57 Rev Time 0.00
Received By wjolin Date 2012-07-17 Time 09:27 Sent To  
Notes
2012-07-17 09:57:032505 NORTH DIXIE HIGHWAY
 PERMIT #12070380
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THIS PERMIT SHOULD BE A PROPOSED CHANGE IN OCCUPANCY
 FROM MERCANTILE (MARKET ) TO ASSEMBLY (RESTAURANT).
  
 THE SEATING AREA IS APPROXIMATELY 1,050 SQUARE FEET
 WHICH EQUATES TO AN OCCUPANT LOAD OF 70 PERSONS BASED
 UPON AN OCCUPANT LOAD FACTOR OF 15 SQ.FT. PER PERSON
 USING TABLES/CHAIRS.
  
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 AN ASSEMBLY OCCUPANCY WILL REQUIRE TWO SEPARATE EXITS.
  
 THE PLANS INDICATE THIS BUILDING IS PROTECTED BY AN
 AUTOMATIC SPRINKLER SYSTEM. PLEASE CONFIRM AS OUR
 RECORDS DO NOT SHOW SPRINKLERS IN THIS BUILDING.
  
 A THUMB TURN LOCK IS NOT PERMITTED ON THE MAIN ENTRY
 DOOR; HOWEVER, THE MAIN ENTRY IS PERMITTED TO BE
 EQUIPPED PANIC HARDWARE OR WITH A KEYED LOCK WITH
 LOCK/UNLOCK INDICATOR WINDOW AND SIGNAGE STATING THE
 DOOR IS TO REMAIN UNLOCKED DURING BUSINESS HOURS. NO
 OTHER LOCKING OR LATCHING MECHANISMS ARE PERMITTED.
  
 SEPARATE PLANS AN PERMITS NEEDED FOR KITCHEN EXHAUST
 HOOD AND HOOD SUPPRESSION SYSTEM.
  
 DEEP FAT FRYERS SHALL BE EQUIPPED WITH A SEPARATE
 HIGH-LIMIT CONTROL IN ADDITION TO THE ADJUSTABLE
 THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN THE FAT
 TEMPERATURE REACHES 475F DEGREES AT 1-INCH BELOW THE
 SURFACE.
  
 PROVIDE AN 8" TALL STEEL BAFFLE OR PROVIDE 16" OF SPACE
 BETWEEN THE DEEP FAT FRYER AND SURFACE FLAMES OF THE
 ADJACENT EQUIPMENT.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-10-29 Cont ID  
Sent By lmartine Date 2012-10-29 Time 13:55 Rev Time 0.00
Received By lmartine Date 2012-10-11 Time 12:22 Sent To  
Notes
2012-10-11 12:29:34C--10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-08-01 Cont ID  
Sent By hmoser Date 2012-08-01 Time 10:51 Rev Time 0.00
Received By hmoser Date 2012-07-12 Time 12:52 Sent To  
Notes
2012-07-13 12:57:03SENT TO B6 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2012-10-30 Cont ID  
Sent By lmartine Date 2012-10-30 Time 10:42 Rev Time 0.00
Received By lmartine Date 2012-10-30 Time 10:42 Sent To  
Notes
2012-10-30 10:43:07SEE COUNTY STAMP ON PLANS.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2012-07-27 Cont ID  
Sent By jwitmer Date 2012-07-27 Time 11:48 Rev Time 0.00
Received By jwitmer Date 2012-07-27 Time 11:48 Sent To  
Notes
2012-07-27 11:49:32BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-10-22 Cont ID  
Sent By hmoser Date 2012-10-22 Time 12:54 Rev Time 0.00
Received By hmoser Date 2012-10-22 Time 12:41 Sent To  
Notes
2012-10-22 12:57:12HOODS AND COOLERS REQUIRE SEPARATE APPLICATION, PLANS
 AND PERMIT
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-08-01 Cont ID  
Sent By hmoser Date 2012-08-01 Time 10:44 Rev Time 0.00
Received By hmoser Date 2012-08-01 Time 10:44 Sent To  
Notes
2012-08-01 10:50:56PLANS DENIED
 1) GRILL NECK SIZE AND DUCT DO NOT MATCH.
 PER SECTION 107.2.1.4 FBC 2010
 2) SEPARATE APPLICATION. PLANS AND PERMIT REQUIRED
 FOR HOOD AND COOLERS.SECTION 105 FBC 2010
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-10-19 Cont ID  
Sent By lwagner Date 2012-10-19 Time 11:16 Rev Time 0.00
Received By lwagner Date 2012-10-19 Time 11:15 Sent To  
Notes
2012-10-19 11:16:17FUEL GAS IS NOT INCLUDED IN THIS REVIEW. SEPARATE
 APPLICATION, PLAN, REVIEW, FEES, AND PERMIT REQUIRED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-07-25 Cont ID  
Sent By lwagner Date 2012-07-25 Time 08:54 Rev Time 0.00
Received By lwagner Date 2012-07-19 Time 15:13 Sent To  
Notes
2012-07-20 09:49:13FBC 2010 PLUMBING REVIEW #1
 PENDING:
  
 1. PLUMBING OK PENDING OUTCOME OF OCCUPANCY TYPE,
 OCCUPANT LOAD, AND CHANGE OF OCCUPANCY FOR RESTROOM
 COUNT.
  
 2. P 403.2 SEPARATE FACILITIES ARE REQUIRED FOE EACH
 SEX.
  
 3. ACCESSIBILITY FOR EACH RESTROOM
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2012-10-18 Cont ID  
Sent By lfranco Date 2012-10-18 Time 11:02 Rev Time 0.00
Received By lfranco Date 2012-10-16 Time 16:01 Sent To  
Notes
2012-10-18 11:03:27PLANNING: **** PASSED, ZONING REVIEW NOT REQUIRED:
 INTERIOR WORK ONLY AND THE VALUE OF PROPOSED WORK DOES
 NOT EXCEED 50% OF THE IMPROVEMENT VALUE. ****

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By lfranco Date 2012-07-27 Time   Rev Time  
Received By   Date 2012-07-27 Time   Sent To  
Notes
2012-07-27 16:15:01*ZONING REVIEW NOT REQUIRED: INTERIOR WORK ONLY AND THE
 VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE. PER L.M.F.