Plan Review Details - Permit 12070357
Plan Review Stops For Permit 12070357
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-12-05 Cont ID  
Sent By rmcdouga Date 2012-12-05 Time 16:40 Rev Time 0.00
Received By rmcdouga Date 2012-12-04 Time 10:38 Sent To  
Notes
2012-12-05 16:44:22ROOFING PRODUCT APPROVALS SUBMITTED: HANSON ROOF TILE-
 NOA NO.10-0706.06 AND TAMKO-NOA NO.12-0227.18

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-08-29 Cont ID  
Sent By rmcdouga Date 2012-08-29 Time 16:25 Rev Time 0.00
Received By rmcdouga Date 2012-08-28 Time 16:54 Sent To  
Notes
2012-08-29 06:53:222010 FBC
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO SETS OF ENERGY CALCULATIONS FOR THE NEW
 DWELLING IN ACCORDANCE WITH FBC ENERGY CONSERVATION
 SECTION 401.2.
  
 2) SHOW COMPLIANCE WITH FBCR G2407.5 FOR INDOOR
 COMBUSTION AIR FOR THE CLOTHES DRYER IN THE UTILITY
 ROOM.
  
 3) PROVIDE STRUCTURAL DETAILS OF THE ARCH OPENINGS.
 CITY AMENDMENTS 107.2.1.3
  
 4) SUBMIT TWO SETS OF A SURFACE WATER DRAINAGE PLAN
 SHOWING COMPLIANCE WITH FBC R401.3.
  
 5) SPECIFY THE UPLIFT LOADS AND ROOF TO WALL CONNECTORS
 ON THE ROOF FRAMING PLAN. FBC R802.1.6.5
  
 6) SUBMIT A FOUNDATION PLAN SHOWING FOOTING SIZES,
 REINFORCEMENT, LOCATIONS, SLAB REINFORCING AND LOCATION
 OF VERTICAL REINFORCEMENT. CITY AMENDMENTS 107.2.1.3
 AND R401.2
  
 7) PROVIDE A STRUCTURAL DETAIL OF THE VERTICAL
 REINFORCEMENT AND HORIZONTAL CAP REINFORCEMENT OF THE
 PARAPET WALL ON THE GARAGE. FBC R606.2.4
  
 8) PROVIDE SCUPPER SIZING CALCULATIONS FOR THE GARAGE
 ROOF. SPECIFY THE SIZES AND LOCATIONS OF THE GARAGE
 ROOF SCUPPERS AND OVERFLOW SCUPPERS. FBCR 903.4 AND FBC
 PLUMBING SECTIONS 1106 AND 1107.
  
 9) THE BEDROOM AND LIBRARY WINDOWS ARE REQUIRED TO
 COMPLY WITH FBCR 310.1 FOR EMERGENCY ESCAPE AND RESCUE
 OPENINGS.
  
 10) SHOW COMPLIANCE WITH FBC R302.5.1 FOR THE DOOR
 BETWEEN THE GARAGE AND THE RESIDENCE.
  
 11) PROVIDE A DETAIL OF HOW THE LOWER ROOF WILL BE
 ATTACHED TO THE WALL OF THE TWO STORY PORTION OF THE
 STRUCTURE. CITY AMENDMENTS 107.2.1.3
  
 12) PROVIDE A DETAIL OF THE STAIRS, INCLUDING THE
 GUARDS AND HANDRAILS. FBCR 311.7 AND 312
  
 13) SPECIFY THE SPACING OF THE ANCHOR BOLTS AT THE TOP
 OF THE MASONRY WALLS SHOWN ON DETAIL 4 ON SHEET A104.
 CITY AMENDMENTS 107.2.1.3
  
 14) ON DETAIL 4 SHEET A104 THE ANCHOR BOLTS ARE SHOWN
 AT THE BASE OF THE MASONRY WALL WHERE THE DOWEL BARS
 FOR THE MASONRY BARS ARE NORMALLY LOCATED. PLEASE
 CLARIFY. CITY AMENDMENTS 107.2.1
  
 15) ON DETAIL 4 SHEET A104 THE CONNECTION OF THE STUDS
 TO THE TOP PLATE AT THE TOP OF THE SECOND FLOOR FRAME
 WALL IS NOT SHOWN. ALSO THE CONNECTOR IDS THAT ARE
 SPECIFIED IN THE DETAIL WHEN LOOKED UP IN THE 2011/2012
 SIMPSON CATALOG DON'T LOOK LIKE THE ONES SHOWN ON THE
 DRAWING. PLEASE CLARIFY. CITY AMENDMENTS 107.2.1.3
  
 16) SUBMIT TWO COPIES OF THE EVALUATION REPORT FOR THE
 SPRAY FOAM INSULATION. FBCR 316
  
 17) PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD FOR THE PROJECT.
 CITY AMENDMENTS 107.3.4.1
  
 18) SUBMIT TWO COPIES OF PRODUCT APPROVALS AS REQUIRED
 BY DCA RULE 9N-3 FOR THE ROOFING MATERIALS FOR THE
 GARAGE FLAT ROOF AND THE BALCONY WATER PROOFING SYSTEM.
  
 19) SUBMIT PRODUCT APPROVALS ( FLORIDA OR MIAMI-DADE )
 AS REQUIRED BY DCA RULE 9N-3 FOR THE EXTERIOR DOORS (
 #S 101, 104, 105 ) , THE SIDELIGHTS AND THE DOUBLE HUNG
 WINDOWS.
  
 20) SUBMIT TWO COPIES OF THE COMPLETE PRODUCT APPROVAL
 WITH THE FL# OR NOA # FOR THE STORM PANELS AS REQUIRED
 BY DCA RULE 9N-3.
  
 21) SUBMIT TWO COPIES OF AN INSTALLATION SCHEDULE AND A
 KEY PLAN FOR THE OPENINGS THAT WILL HAVE THE STORM
 PANELS. SPECIFY THE ANCHOR TYPE AND SPACING AND OTHER
 REQUIRED CRITERIA LISTED IN THE STORM PANEL PRODUCT
 APPROVAL THAT WILL BE REQUIRED FOR INSTALLATION. CITY
 AMENDMENTS 107.2.1.3
  
 22) SPECIFY THE METHOD OF ATTACHMENT LISTED IN THE ROOF
 TILE PRODUCT APPROVAL THAT WILL BE USED. IF AN ADHESIVE
 IS USED SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR
 IT. DCA RULE 9N-3 AND FBC R905.3.7
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-11-19 Cont ID  
Sent By rlecky Date 2012-11-19 Time 16:50 Rev Time 0.00
Received By rlecky Date 2012-11-19 Time 16:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-07-24 Cont ID  
Sent By rlecky Date 2012-07-24 Time 14:04 Rev Time 0.00
Received By rlecky Date 2012-07-24 Time 11:43 Sent To  
Notes
2012-07-24 14:04:1112070357
 231 PLYMOUTH ROAD
 NEW SFD
  
 PLEASE CLARIFY THE FOLLOWING ITEMS:
 PROVIDE INTERCONNECTED SMOKE ALARMS AND A CARBON
 MONOXIDE DETECTOR WITHIN TEN FEET OF EACH ROOM USED FOR
 SLEEPING. SMOKE ALARMS ARE REQUIRED WITHIN AND OUTSIDE
 EACH SLEEPING AREA. 2010 FBC R314, 315
 RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
 PROVIDE LOCATION OF PANEL BOARD. NEC 215.5, 110.26
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. 2008 NEC 250.94
 PROVIDE A NOTE THAT THE LETTER ?G? REPRESENTS A GROUND
 FAULT PROTECTED OUTLET. NEC 210.8
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2012-12-04 Cont ID  
Sent By rmcdouga Date 2012-12-04 Time 10:38 Rev Time 0.00
Received By rmcdouga Date 2012-12-04 Time 10:38 Sent To  
Notes
2012-12-04 10:39:45SEPARATE SUB-PERMIT AND APPLICATION IS REQUIRED FOR
 GAS. GAS IS SHOWN ON SHEET A101 OF MASTER PLANS.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2012-08-22 Cont ID  
Sent By rmcdouga Date 2012-08-22 Time 13:02 Rev Time 0.00
Received By rmcdouga Date 2012-08-22 Time 13:02 Sent To  
Notes
2012-08-22 13:20:562010 FBC
  
 DENIED BY GAS
  
 1) SUBMIT TWO COPIES OF A GAS RISER DIAGRAM. SPECIFY
 THE TYPES OF PIPE, THE PIPE SIZES, THE PIPE LENGTHS,
 THE BTUS OF THE EQUIPMENT AND THE GAS PIPE SIZING
 TABLES OR SIZING EQUATIONS USED. FBCR G2413.1
  
 2) SHOW COMPLIANCE WITH FBCR G2415.4 (404.4) REQUIRES
 GAS PIPING TO ENTER AND EXIT A BUILDING AT A POINT
 ABOVE GRADE.
  
 3) THIS INFORMATION CAN BE PROVIDED NOW OR UNDER A
 SEPARATE GAS PERMIT WITH SEPARATE APPLICATION AND
 REVIEW AT A LATER DATE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2012-11-08 Cont ID  
Sent By fmittner Date 2012-11-08 Time 16:54 Rev Time 0.00
Received By fmittner Date 2012-11-08 Time 16:54 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2012-07-20 Cont ID  
Sent By fmittner Date 2012-07-20 Time 12:57 Rev Time 0.00
Received By fmittner Date 2012-07-20 Time 12:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-12-06 Cont ID  
Sent By rmcdouga Date 2012-12-06 Time 07:15 Rev Time 0.00
Received By rmcdouga Date 2012-11-05 Time 16:18 Sent To  
Notes
2012-11-05 16:19:10R--4

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-08-29 Cont ID  
Sent By rmcdouga Date 2012-08-29 Time 16:26 Rev Time 0.00
Received By rmcdouga Date 2012-07-20 Time 17:10 Sent To  
Notes
2012-07-20 17:13:50R--4

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2015-07-31 Cont ID  
Sent By rmcdouga Date 2015-07-31 Time 08:53 Rev Time 0.00
Received By rmcdouga Date 2015-07-31 Time 08:53 Sent To  
Notes
2015-07-31 08:57:49MU2015-18389, PAID $236.59

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2012-12-06 Cont ID  
Sent By rmcdouga Date 2012-12-06 Time 07:44 Rev Time 0.00
Received By rmcdouga Date 2012-12-06 Time 07:44 Sent To  
Notes
2012-12-06 07:45:53PALM BEACH COUNTY IMPACT FEE REVIEW IS REQUIRED.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2012-08-27 Cont ID  
Sent By rmcdouga Date 2012-08-27 Time 15:57 Rev Time 0.00
Received By rmcdouga Date 2012-08-27 Time 15:57 Sent To  
Notes
2012-08-27 15:58:34AN IMPACT FEE REVIEW BY PALM BEACH COUNTY WILL BE
 REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-12-04 Cont ID  
Sent By rmcdouga Date 2012-12-04 Time 09:29 Rev Time 0.00
Received By rmcdouga Date 2012-11-30 Time 16:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-08-27 Cont ID  
Sent By rmcdouga Date 2012-08-27 Time 15:59 Rev Time 0.00
Received By rmcdouga Date 2012-08-27 Time 15:58 Sent To  
Notes
2012-08-27 16:24:262010 FBC
  
 DENIED BY MECHANICAL
  
 1) SUBMIT TWO SETS OF MECHANICAL PLANS. SHOW THE
 LOCATION OF THE MECHANICAL EQUIPMENT. SPECIFY THE
 SUPPLY AND RETURN DUCT SIZES, GRILL SIZES AND CFMS AT
 EACH OUTLET. PROVIDE AN EQUIPMENT SCHEDULE ON THE PLANS
 THAT MATCHES THE EQUIPMENT SIZING CALCULATIONS. CITY
 AMENDMENTS 107.3.5.3 AND FBCR M1401.3
  
 2) SHOW COMPLIANCE WITH FBCR G2407.5 FOR INDOOR
 COMBUSTION AIR FOR THE CLOTHES DRYER IN THE UTILITY
 ROOM.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-08-27 Cont ID  
Sent By rmcdouga Date 2012-08-27 Time 16:17 Rev Time 0.00
Received By rmcdouga Date 2012-08-21 Time 16:52 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2013-03-08 Cont ID  
Sent By fmittner Date 2013-03-08 Time 09:24 Rev Time 0.00
Received By fmittner Date 2013-03-08 Time 09:24 Sent To  
Notes
2013-03-08 09:25:19PROVISO: MUST OBTAIN LANDSCAPE PERMIT PRIOR TO CO

Review Stop Z ZONING
Rev No 2 Status F Date 2012-11-08 Cont ID  
Sent By fmittner Date 2012-11-08 Time 16:52 Rev Time 0.00
Received By fmittner Date 2012-11-08 Time 16:52 Sent To  
Notes
2012-11-08 16:53:33REQUIRES SUBMITTAL OF LANDSCAPE PERMIT.

Review Stop Z ZONING
Rev No 1 Status F Date 2012-07-20 Cont ID  
Sent By fmittner Date 2012-07-20 Time 12:57 Rev Time 0.00
Received By fmittner Date 2012-07-20 Time 12:57 Sent To  
Notes
2012-07-20 15:15:18REQUIRES 2 COPIES OF SURVEY.