Plan Review Details - Permit 12070303
Plan Review Stops For Permit 12070303
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2012-10-10 Cont ID  
Sent By shill Date 2012-10-10 Time 10:02 Rev Time 0.00
Received By shill Date 2012-10-10 Time 10:02 Sent To  
Notes
2012-10-10 10:04:15PROVISO - SURVEYOR TO INCLUDE SOURCE OF
 LATITUDE/LONGITUDE INFORMATION IN COMMENTS PER ELEVATIN
 CERTIFICATE INSTRUCTIONS, ITEM A5. REVISE ELEVATION
 CERTIFICATE AND PROVIDE AT FORM BOARD INSPECTION
 ("BUILDING UNDER CONSTRUCTION") ELEVATION CERTIFICATE.
  
 IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY REQUIRED
 PRIOR TO PERMIT ISSUANCE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2012-09-26 Cont ID  
Sent By RMCDOUGA Date 2012-09-26 Time 10:15 Rev Time 0.00
Received By rmcdouga Date 2012-09-26 Time 08:58 Sent To  
Notes
2012-09-26 10:17:15DENIED BY BUILDING
  
 1) SUBMIT 2 SETS OF CORRECTED ELEVATION CERTIFICATES
 ARE REQUESTED IN PREVIOUS REVIEW.
  
 FROM SECOND REVIEW: 1) THE ELEVATION CERTIFICATE
 CONTAINS SEVERAL MISTAKES. THE BUILDING'S OWNER IS
 INCORRECT ON THE FORM. THE PLAT NUMBER SHOULD BE 2,
 INSTEAD OF 3. THE LATITUDE AND LONGITUDE ARE INCORRECT.
 THE FLOOD ZONE IS A5. SUBMIT TWO COPIES OF THE
 CORRECTED ELEVATION CERTIFICATES WITH THE SURVEYOR'S
 ORIGINAL SIGNATURE ON THEM AS REQUIRED BY FS 472.025.
  
 FROM FIRST REVIEW: 1) THE STRUCTURE IS LOCATED IN AN A5
 FLOOD ZONE AND THE VALUE OF THE PROPOSED WORK IS MORE
 THAN 50 PERCENT OF THE APPRAISED VALUE OF THE STRUCTURE
 ( PBC PROPERTY APPRAISER ). THE CITY'S FLOOD PLAIN
 ORDINANCE REQUIRES THE STRUCTURE TO HAVE A MINIMUM
 FINISH FLOOR ELEVATION OF 7.5 FEET B.F.E. SECTION
 94-546 OF THE CITY OF WPB MUNICIPAL CODE. SPECIFY THE
 FINISH FLOOR ELEVATION ON THE PLANS AND PROVIDE AN
 ELEVATION CERTIFICATE.
  
 2) NOTE: THE PLANS ARE REQUIRED TO BE REVIEWED BY PALM
 BEACH COUNTY FOR IMPACT FEES BEFORE THE PERMIT IS
 ISSUED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-08-17 Cont ID  
Sent By rmcdouga Date 2012-08-17 Time 16:09 Rev Time 0.00
Received By rmcdouga Date 2012-08-17 Time 13:23 Sent To Z
Notes
2012-08-17 15:52:002010 FBC
  
 DENIED BY BUILDING
  
 1) THE ELEVATION CERTIFICATE CONTAINS SEVERAL MISTAKES.
 THE BUILDING'S OWNER IS INCORRECT ON THE FORM. THE PLAT
 NUMBER SHOULD BE 2, INSTEAD OF 3. THE LATITUDE AND
 LONGITUDE ARE INCORRECT. THE FLOOD ZONE IS A5. SUBMIT
 TWO COPIES OF THE CORRECTED ELEVATION CERTIFICATES WITH
 THE SURVEYOR'S ORIGINAL SIGNATURE ON THEM AS REQUIRED
 BY FS 472.025.
  
 2) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 ARCH SERIES 2500 ALUMINUM SINGLE HUNG WINDOWS HAS BEEN
 SUPERSEDED. THE CURRENT PRODUCT APPROVAL FOR THIS
 WINDOW IS NOA NO. 12-0118.18. PLEASE SUBMIT TWO COPIES
 OF THE CURRENT NOA THAT HAVE BEEN REVIEWED AND APPROVED
 BY THE DESIGNER OF RECORD. DCA RULE 9N-3 AND CITY
 AMENDMENTS 107.3.4.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-07-24 Cont ID  
Sent By rmcdouga Date 2012-07-24 Time 08:51 Rev Time 0.00
Received By rmcdouga Date 2012-07-18 Time 11:17 Sent To  
Notes
2012-07-23 10:58:242010 FBC
  
 DENIED BY BUILDING
  
 1) THE STRUCTURE IS LOCATED IN AN A5 FLOOD ZONE AND THE
 VALUE OF THE PROPOSED WORK IS MORE THAN 50 PERCENT OF
 THE APPRAISED VALUE OF THE STRUCTURE ( PBC PROPERTY
 APPRAISER ). THE CITY'S FLOOD PLAIN ORDINANCE REQUIRES
 THE STRUCTURE TO HAVE A MINIMUM FINISH FLOOR ELEVATION
 OF 7.5 FEET B.F.E. SECTION 94-546 OF THE CITY OF WPB
 MUNICIPAL CODE. SPECIFY THE FINISH FLOOR ELEVATION ON
 THE PLANS AND PROVIDE AN ELEVATION CERTIFICATE.
  
 2) THE SURVEY THAT WAS SUBMITTED INDICATES THE PROPERTY
 LOCATED IN FLOOD ZONE B. HOWEVER, THE A5 FLOOD ZONE
 ALSO EXTENDS THROUGH THE PROPERTY. PLEASE CORRECT THE
 SURVEY. CITY AMENDMENTS 107.2.1 AND FBC R322.1.
  
 3) THE ENERGY CALCULATIONS THAT WERE SUBMITTED ARE ON
 THE FORMS (1100A-08) THAT ARE USED WITH THE 2007 FBC.
 SUBMIT TWO SETS OF ENERGY CALCULATIONS ON FORM 405,
 WHICH IS THE FORM USED WITH THE 2010 FBC. 2010 FBC
 ENERGY CONSERVATION 401.2.
  
 4) SPECIFY THE SEER FOR THE COOLING EQUIPMENT ON THE
 MANUAL J CALCULATIONS. THE SEER ON THE CALCULATIONS IS
 REQUIRED TO MATCH THE ONES ON THE MECHANICAL PLANS. FBC
 2010 FBC ENERGY CONSERVATION 503.2.3
  
 5) THE PRODUCT APPROVALS FOR THE ARCH WINDOWS SERIES
 2500 ALUMINUM SINGLE HUNG WINDOWS HAS BEEN SUPERSEDED.
 SUBMIT TWO COPIES OF THE CURRENT PRODUCT APPROVALS AS
 REQUIRED BY DCA RULE 9N-3.
  
 6) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 AMARR GARAGE DOOR ( FL 5302.5 ) IS FOR THE 2007 FBC AND
 ASCE 7-98. SUBMIT TWO COPIES OF GARAGE DOOR PRODUCT
 APPROVALS FOR THE 2010 FBC AND ASCE 7-10. DCA RULE 9N-3
  
 7) THE TRUSS DRAWINGS AND LAYOUT PLAN THAT WERE
 SUBMITTED ARE DESIGNED USING ASCE 7-05 WITH 140 MPH
 WIND SPEED. THE PROJECT IS UNDER THE 2010 FBC WHICH
 REFERENCES ASCE 7-10 AND THE WIND SPEED IS 170 MPH,
 EXPOSURE C FOR THIS PROJECT. PLEASE REVISE. THE TRUSS
 DRAWINGS AND LAYOUT FOR SINGLE FAMILY HOMES CAN BE
 GIVEN TO THE FIELD INSPECTOR TO BRING IN AT THE TIME OF
 THE ROOF FRAMING INSPECTION RATHER THAN BEING SUBMITTED
 AT PLAN REVIEW FOR PERMIT. THE PLANS ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE TRUSS ENGINEER AND REVIEWED
 AND APPROVED BY THE DESIGNER OF RECORD FOR THE PROJECT.
 CITY AMENDMENTS 107.3.4.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-07-20 Cont ID  
Sent By rmcdouga Date 2012-07-20 Time 15:55 Rev Time 0.00
Received By rmcdouga Date 2012-07-20 Time 15:55 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2012-10-04 Cont ID  
Sent By MGONZALE Date 2012-10-04 Time   Rev Time 1.00
Received By mgonzale Date 2012-10-04 Time   Sent To Z
Notes
2012-10-04 16:19:32PASSED.
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2012-08-28 Cont ID  
Sent By mgonzale Date 2012-08-28 Time   Rev Time 0.25
Received By mgonzale Date 2012-08-21 Time 17:33 Sent To  
Notes
2012-08-28 12:02:41NEED TO RESPOND TO PLANNING'S COMMENTS
2012-08-21 17:23:55NEW DRIVEWAY AND APRON, ENGINEERING NEEDS TO REVIEW.
 LMF

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2012-07-20 Cont ID  
Sent By rmcdouga Date 2012-07-20 Time 15:43 Rev Time 0.00
Received By rmcdouga Date 2012-07-20 Time 15:43 Sent To  
Notes
2012-07-20 15:44:52SEPARATE APPLICATION, DRAWINGS AND REVIEW IS REQUIRED
 FOR THE GAS PERMIT.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2012-10-15 Cont ID  
Sent By mdekle Date 2012-10-15 Time   Rev Time 0.00
Received By mdekle Date 2012-10-15 Time 09:04 Sent To  
Notes
2012-10-15 11:24:19COUNTY #MU-2012-18873.
2012-10-15 09:04:51INCOMING FROM IMPACT FEES TO MD, DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2012-10-10 Cont ID  
Sent By mdekle Date 2012-10-10 Time   Rev Time 0.00
Received By mdekle Date 2012-10-04 Time 15:39 Sent To  
Notes
2012-10-04 15:40:02SUBMITTED, ENGINEERING, ZONING AND LANDSCAPE

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2012-10-10 Cont ID  
Sent By mdekle Date 2012-09-26 Time   Rev Time 0.00
Received By mdekle Date 2012-09-05 Time 10:03 Sent To  
Notes
2012-09-06 10:03:36R22

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-09-04 Cont ID  
Sent By rmcdouga Date 2012-08-28 Time 16:30 Rev Time 0.00
Received By lmartine Date 2012-08-14 Time 14:11 Sent To  
Notes
2012-08-14 14:12:14INCOMING SENT TO R MCDOUGALS'S DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-07-30 Cont ID  
Sent By rmcdouga Date 2012-08-17 Time 16:10 Rev Time 0.00
Received By rmcdouga Date 2012-08-08 Time 11:48 Sent To  
Notes
2012-08-08 11:51:15TO RM DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2012-08-03 Time   Rev Time 0.00
Received By rlecky Date 2012-07-11 Time 10:16 Sent To  
Notes
2012-07-12 10:16:54R15

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2012-10-15 Cont ID  
Sent By mdekle Date 2012-10-15 Time 11:21 Rev Time 0.00
Received By mdekle Date 2012-10-15 Time 11:21 Sent To  
Notes
2012-10-15 11:21:28PER LUIS MARTINEZ

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2012-09-26 Cont ID  
Sent By rmcdouga Date 2012-09-26 Time 09:11 Rev Time 0.00
Received By rmcdouga Date 2012-09-26 Time 09:11 Sent To  
Notes
2012-09-26 09:11:36IMPACT FEE REVIEW BY PALM BEACH COUNTY IS REQUIRED.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2012-08-17 Cont ID  
Sent By rmcdouga Date 2012-08-17 Time 16:09 Rev Time 0.00
Received By rmcdouga Date 2012-08-17 Time 16:11 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2012-07-20 Cont ID  
Sent By rmcdouga Date 2012-07-20 Time 15:45 Rev Time 0.00
Received By rmcdouga Date 2012-07-20 Time 15:45 Sent To  
Notes
2012-07-20 15:46:12AN IMPACT FEE PLAN REVIEW IS REQUIRED BY PALM PEACH
 COUNTY.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2012-09-26 Cont ID  
Sent By RMCDOUGA Date 2012-09-26 Time 08:58 Rev Time 0.00
Received By rmcdouga Date 2012-09-26 Time 08:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2012-08-17 Cont ID  
Sent By rmcdouga Date 2012-08-17 Time 11:00 Rev Time 0.00
Received By rmcdouga Date 2012-08-16 Time 15:45 Sent To  
Notes
2012-08-17 13:23:492010 FBC
  
 DENIED BY MECHANICAL
  
 1) THE ENERGY CALCULATIONS THAT WERE SUBMITTED ARE
 CLAIMING THE CEILING FAN AND WHOLE HOUSE FAN CREDIT
 OPTIONS. THE PLANS DO NOT SHOW THE REQUIREMENTS NEEDED
 TO CLAIM THESE CREDITS. PLEASE SHOW HOW THE
 REQUIREMENTS WILL BE MET OR REVISE THE ENERGY CALCS.
 FBC ENERGY CONSERVATION SECTION 405.6
  
 2) ON SHEET M.1, THE DUCT SUPPLYING AIR TO THE 10 X 10
 GRILL IN THE GREAT ROOM IS NOT SHOWN. SPECIFY THE SIZE
 AND LOCATION OF THE DUCT THAT IS SUPPLYING AIR TO THIS
 GRILL. CITY AMENDMENTS 107.2.1 AND FBCR M1601.1
 (PREVIOUS COMMENT THAT WAS NOT ADDRESSED)
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-07-20 Cont ID  
Sent By rmcdouga Date 2012-07-20 Time 14:04 Rev Time 0.00
Received By rmcdouga Date 2012-07-20 Time 14:04 Sent To  
Notes
2012-07-20 14:38:372010 FBC
  
 DENIED BY MECHANICAL
  
 1) SUBMIT TWO COPIES OF 2010 ENERGY CALCULATIONS ON
 FORM 405. THE ONES THAT WERE SUBMITTED ARE ON THE 2007
 FBC FORM 1100A-08. FBC ENERGY CONSERVATION SECTION
 405.4.2
  
 2) SPECIFY THE HEATING AND COOLING EQUIPMENT THAT WILL
 BE INSTALLED ON THE MANUAL J CALCULATIONS AND SPECIFY
 THE SEER OF THE COOLING EQUIPMENT. FBC ENERGY
 CONSERVATION SECTION 403.6
  
 3) ON SHEET M.1, THE DUCT SUPPLYING AIR TO THE 10 X 10
 GRILL IN THE GREAT ROOM IS NOT SHOWN. SPECIFY THE SIZE
 AND LOCATION OF THE DUCT THAT IS SUPPLYING AIR TO THIS
 GRILL. CITY AMENDMENTS 107.2.1 AND FBCR M1601.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-07-20 Cont ID  
Sent By rmcdouga Date 2012-07-20 Time 15:50 Rev Time 0.00
Received By rmcdouga Date 2012-07-20 Time 14:38 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2012-10-10 Cont ID  
Sent By lfranco Date 2012-10-10 Time   Rev Time 0.00
Received By mdekle Date 2012-10-05 Time   Sent To  
Notes
2012-10-05 15:27:49CONTACTING APPLICANT - REQUIRES SEPERATE LANDSCAPE
 PERMIT.

Review Stop Z ZONING
Rev No 3 Status F Date 2012-09-20 Cont ID  
Sent By L FRANCO Date 2012-09-20 Time   Rev Time 0.00
Received By mdekle Date 2012-09-20 Time   Sent To  
Notes
2012-09-20 10:02:57APPLICANT DID NOT ADDRESS PREVIOUS COMMENTS BY ZONING.
 PLEASE REFER TO LINDA MIA FRANCO'S ZONING COMMENTS MADE
 ON 8/23/12.

Review Stop Z ZONING
Rev No 2 Status F Date 2012-08-23 Cont ID  
Sent By lfranco Date 2012-08-23 Time 09:08 Rev Time 0.00
Received By lfranco Date 2012-08-23 Time 09:08 Sent To ENG
Notes
2012-08-23 09:13:12 
 PLANNING: ***** FAILED, STAFF SPOKE TO THE CONTRACTOR
 BLAS CONTRERAS, AND EXPLAINED THE COMMENTS BELOW THAT
 WERE NOT ADDRESSED IN THE 2ND SUBMITTAL, ALSO THE
 REDUCTION OF THE DRIVEWAY AND EXISTING APRON ON THE
 RIGHT-OF-WAY, REQUIRES A ENGINEERING REVIEW AND ROW
 PERMIT APPROVAL. ****
  
 1. RESPOND TO COMMENTS IN WRITING. WAS THE DRIVEWAY
 ALREADY DONE?
  
 2. SEC. 94-482. - PARKING REQUIREMENTS FOR LESS THAN
 THREE RESIDENTIAL DWELLING UNITS.
  
 (A) LOCATION AND SURFACE. REQUIRED OFF-STREET PARKING
 SPACES FOR LESS THAN THREE RESIDENTIAL DWELLING UNITS
 SHALL BE PROVIDED ON THE PROPERTY ON WHICH THE UNITS
 ARE LOCATED. REQUIRED PARKING MAY BE LOCATED IN A FRONT
 YARD; HOWEVER, THE LESSER OF 1,000 SQUARE FEET OR 75
 PERCENT OF THE FRONT YARD AREA SHALL BE LANDSCAPED WITH
 LIVING PLANT MATERIAL (SUCH AS GRASS, GROUND COVER,
 SHRUBS, HEDGES, VINES OR TREES).
 NOTWITHSTANDING THE PRECEDING PARAGRAPH, LOCATIONS
 WHERE OFF-STREET PARKING SPACES, DRIVEWAYS, PATIOS
 AND/OR WALKWAYS IN THE FRONT YARD EXCLUSIVELY CONSIST
 OF A PERMEABLE PAVER SYSTEM, 60 PERCENT OF THE FRONT
 YARD AREA SHALL BE LANDSCAPED WITH LIVING PLANT
 MATERIAL (SUCH AS GRASS, GROUND COVER, SHRUBS, HEDGES,
 VINES OR TREES).
  
 THE FRONT YARD CALCULATIONS ARE THE FIRST 25 FEET OF
 LOT DEPTH FROM THE FRONT PROPERTY X THE WIDTH OF THE
 PROPERTY (SURVEY SHOWS 65.27 FEET) X 75% = 1,223.81
 SQ.FT. THEREFORE, YOUR MINIMUM LANDSCAPE AREA IS 1,000
 SQ. FT. SHOW DATA ON PLAN.
  
 3. CIRCULAR DRIVEWAY, PURSUANT TO SECTION 94-482(D)(5),
  
 SETBACK FROM PROPERTY LINES; REPAIR AND REPLACEMENT.
  
 (1) NEW OFF-STREET PARKING SPACES AND DRIVEWAYS WITHIN
 A FRONT YARD OR A CORNER SIDE YARD SHALL BE SET BACK A
 MINIMUM OF FIVE FEET FROM A FRONT AND/OR CORNER SIDE
 PROPERTY LINE AND THREE FEET FROM A SIDE OR REAR
 PROPERTY LINE, EXCEPT FOR THAT PORTION OF THE DRIVEWAY
 ADJOINING THE APRON.
  
 (2) EXPANSIONS TO EXISTING OFF-STREET PARKING SPACES
 AND DRIVEWAYS WITHIN A FRONT YARD OR A CORNER SIDE YARD
 SHALL BE SET BACK A MINIMUM OF FIVE FEET FROM A FRONT
 AND/OR CORNER SIDE PROPERTY LINE AND THREE FEET FROM A
 SIDE OR REAR PROPERTY LINE, EXCEPT FOR THAT PORTION OF
 THE DRIVEWAY ADJOINING THE APRON.
  
 (3) EXISTING OFF-STREET PARKING SPACES AND DRIVEWAYS
 WHICH ARE NOT SET BACK A MINIMUM OF FIVE FEET FROM A
 FRONT OR CORNER SIDE PROPERTY LINE AND THREE FEET FROM
 A SIDE OR REAR PROPERTY LINE MAY BE REPAIRED AS PART OF
 NORMAL MAINTENANCE.
  
 (4) EXISTING OFF-STREET PARKING SPACES AND DRIVEWAYS
 WHICH ARE NOT SET BACK A MINIMUM OF FIVE FEET FROM A
 FRONT AND/OR CORNER SIDE PROPERTY LINE AND THREE FEET
 FROM A SIDE OR REAR PROPERTY LINE MAY BE REPLACED IN
 THE EXACT LOCATION OR WITH A GREATER SETBACK THAN
 CURRENTLY EXISTS.
  
 (5) FOR CIRCULAR DRIVEWAYS THE INTERIOR ARC MAY BE AN
 IRREGULAR SHAPE, BUT SHALL HAVE A MINIMUM RADIUS OF
 FIVE FEET, AS DEPICTED IN FIGURE XV-1. THE INTERIOR ARC
 SHALL BE LANDSCAPED WITH LIVING PLANT MATERIAL.
  
 THE PROPOSED CIRCULAR DRIVE CONFIGURATION DOES NOT MEET
 REGULATIONS. THE MAXIMUM DRIVE WIDTH IS 10 FEET ON EACH
 INGRESS/EGRESS AREA ON EACH SIDE AND THE SIDE SETBACK
 IS 3 FEET. REFER TO FIGURE XV-1.
  
 RE-SUBMITTAL: THE REDUCTION OF THE DRIVEWAY AND
 EXISTING APRON ON THE RIGHT-OF-WAY, REQUIRES A
 ENGINEERING REVIEW AND ROW PERMIT APPROVAL.
  
 4. PROVIDE DIMENSIONS OF NEW ADDITION ON SURVEY. THE
 DIMENSION ON SHEET S.P ON THE WEST PROPERTY LINE SHOW
 113.3 INCHES VS. SURVEY 112.37 FEET AND NO DIMENSION IS
 SHOWN ON THE SITE PLAN FOR THE WEST PROPERTY LINE.
 REVISE PLANS/SURVEY TO MATCH.
  
 5. PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR): AS THE VALUE OF
 THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE
 (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF
 THE ZLDR.
 INCLUDE INFORMATION SUCH AS THE FOLLOWING REQUIREMENT
 IN THE LANDSCAPE TABULATION, PURSUANT TO SECTION
 94-442(2)A: AT LEAST ONE SHADE, FLOWERING OR FRUIT TREE
 SHALL BE PLANTED FOR EACH 1,200 SQUARE FEET OF OPEN
 SPACE OR PORTION THEREOF.
  
 PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDR.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO, AICP
 SENIOR PLANNER
 PLANNING DIVISION
 TEL: (561) 822-1443
 EMAIL: [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2012-07-30 Cont ID  
Sent By lfranco Date 2012-07-30 Time 18:30 Rev Time 0.00
Received By lfranco Date 2012-07-27 Time 17:04 Sent To  
Notes
2012-07-27 17:04:44PLANNING: ***** FAILED ****
  
 1. RESPOND TO COMMENTS IN WRITING. WAS THE DRIVEWAY
 ALREADY DONE?
  
 2. SEC. 94-482. - PARKING REQUIREMENTS FOR LESS THAN
 THREE RESIDENTIAL DWELLING UNITS.
  
 (A) LOCATION AND SURFACE. REQUIRED OFF-STREET PARKING
 SPACES FOR LESS THAN THREE RESIDENTIAL DWELLING UNITS
 SHALL BE PROVIDED ON THE PROPERTY ON WHICH THE UNITS
 ARE LOCATED. REQUIRED PARKING MAY BE LOCATED IN A FRONT
 YARD; HOWEVER, THE LESSER OF 1,000 SQUARE FEET OR 75
 PERCENT OF THE FRONT YARD AREA SHALL BE LANDSCAPED WITH
 LIVING PLANT MATERIAL (SUCH AS GRASS, GROUND COVER,
 SHRUBS, HEDGES, VINES OR TREES).
 NOTWITHSTANDING THE PRECEDING PARAGRAPH, LOCATIONS
 WHERE OFF-STREET PARKING SPACES, DRIVEWAYS, PATIOS
 AND/OR WALKWAYS IN THE FRONT YARD EXCLUSIVELY CONSIST
 OF A PERMEABLE PAVER SYSTEM, 60 PERCENT OF THE FRONT
 YARD AREA SHALL BE LANDSCAPED WITH LIVING PLANT
 MATERIAL (SUCH AS GRASS, GROUND COVER, SHRUBS, HEDGES,
 VINES OR TREES).
  
 THE FRONT YARD CALCULATIONS ARE THE FIRST 25 FEET OF
 LOT DEPTH FROM THE FRONT PROPERTY X THE WIDTH OF THE
 PROPERTY (SURVEY SHOWS 65.27 FEET) X 75% = 1,223.81
 SQ.FT. THEREFORE, YOUR MINIMUM LANDSCAPE AREA IS 1,000
 SQ. FT. SHOW DATA ON PLAN.
  
 3. CIRCULAR DRIVEWAY, PURSUANT TO SECTION 94-482(D)(5),
  
 SETBACK FROM PROPERTY LINES; REPAIR AND REPLACEMENT.
  
 (1) NEW OFF-STREET PARKING SPACES AND DRIVEWAYS WITHIN
 A FRONT YARD OR A CORNER SIDE YARD SHALL BE SET BACK A
 MINIMUM OF FIVE FEET FROM A FRONT AND/OR CORNER SIDE
 PROPERTY LINE AND THREE FEET FROM A SIDE OR REAR
 PROPERTY LINE, EXCEPT FOR THAT PORTION OF THE DRIVEWAY
 ADJOINING THE APRON.
  
 (2) EXPANSIONS TO EXISTING OFF-STREET PARKING SPACES
 AND DRIVEWAYS WITHIN A FRONT YARD OR A CORNER SIDE YARD
 SHALL BE SET BACK A MINIMUM OF FIVE FEET FROM A FRONT
 AND/OR CORNER SIDE PROPERTY LINE AND THREE FEET FROM A
 SIDE OR REAR PROPERTY LINE, EXCEPT FOR THAT PORTION OF
 THE DRIVEWAY ADJOINING THE APRON.
  
 (3) EXISTING OFF-STREET PARKING SPACES AND DRIVEWAYS
 WHICH ARE NOT SET BACK A MINIMUM OF FIVE FEET FROM A
 FRONT OR CORNER SIDE PROPERTY LINE AND THREE FEET FROM
 A SIDE OR REAR PROPERTY LINE MAY BE REPAIRED AS PART OF
 NORMAL MAINTENANCE.
  
 (4) EXISTING OFF-STREET PARKING SPACES AND DRIVEWAYS
 WHICH ARE NOT SET BACK A MINIMUM OF FIVE FEET FROM A
 FRONT AND/OR CORNER SIDE PROPERTY LINE AND THREE FEET
 FROM A SIDE OR REAR PROPERTY LINE MAY BE REPLACED IN
 THE EXACT LOCATION OR WITH A GREATER SETBACK THAN
 CURRENTLY EXISTS.
  
 (5) FOR CIRCULAR DRIVEWAYS THE INTERIOR ARC MAY BE AN
 IRREGULAR SHAPE, BUT SHALL HAVE A MINIMUM RADIUS OF
 FIVE FEET, AS DEPICTED IN FIGURE XV-1. THE INTERIOR ARC
 SHALL BE LANDSCAPED WITH LIVING PLANT MATERIAL.
  
 THE PROPOSED CIRCULAR DRIVE CONFIGURATION DOES NOT MEET
 REGULATIONS. THE MAXIMUM DRIVE WIDTH IS 10 FEET ON EACH
 INGRESS/EGRESS AREA ON EACH SIDE AND THE SIDE SETBACK
 IS 3 FEET. REFER TO FIGURE XV-1.
  
 4. PROVIDE DIMENSIONS OF NEW ADDITION ON SURVEY. THE
 DIMENSION ON SHEET S.P ON THE WEST PROPERTY LINE SHOW
 113.3 INCHES VS. SURVEY 112.37 FEET AND NO DIMENSION IS
 SHOWN ON THE SITE PLAN FOR THE WEST PROPERTY LINE.
 REVISE PLANS/SURVEY TO MATCH.
  
 5. PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR): AS THE VALUE OF
 THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE
 (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF
 THE ZLDR.
 INCLUDE INFORMATION SUCH AS THE FOLLOWING REQUIREMENT
 IN THE LANDSCAPE TABULATION, PURSUANT TO SECTION
 94-442(2)A: AT LEAST ONE SHADE, FLOWERING OR FRUIT TREE
 SHALL BE PLANTED FOR EACH 1,200 SQUARE FEET OF OPEN
 SPACE OR PORTION THEREOF.
  
 PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDR.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO, AICP
 SENIOR PLANNER
 PLANNING DIVISION
 TEL: (561) 822-1443
 EMAIL: [email protected]
  
  