Plan Review Details - Permit 12070268
Plan Review Stops For Permit 12070268
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-07-24 Cont ID  
Sent By shill Date 2012-07-24 Time 10:35 Rev Time 0.00
Received By shill Date 2012-07-24 Time 10:35 Sent To  
Notes
2012-07-24 10:37:59****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. PROVIDE A STRUCTURAL PLAN FOR ALL OF THE PROPOSED
 WORK. PHOTOGRAPHS CANNOT BE USED IN LIEU OF AN
 ARCHITECTURAL QUALITY PLAN, DRAWN TO SCALE, WHICH SHOWS
 ALL MATERIALS, CONNECTIONS, ETC. IN ORDER TO SHOW
 COMPLIANCE WITH FBC RESIDENTIAL 301.1, RESISTANCE TO
 WIND LOADS. PLAN SHOULD INCLUDE WIND DESIGN CRITERIA.
  
 2. A COPY OF AN OLD PERMIT WAS INCLUDED, PLEASE PROVIDE
 A NEW PLAN WHICH SHOWS SCOPE OF WORK.
  
 3. CURRENT FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED FOR WINDOWS, FAC9N-3. THE PRODUCT APPROVAL
 PROVIDED IS EXPIRED.
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-07-10 Cont ID  
Sent By rlecky Date 2012-07-10 Time 10:45 Rev Time 0.00
Received By rlecky Date 2012-07-10 Time 10:45 Sent To  
Notes
2012-07-10 10:46:15TO MISC 2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-07-24 Cont ID  
Sent By shill Date 2012-07-24 Time 10:38 Rev Time 0.00
Received By shill Date 2012-07-10 Time 10:11 Sent To  
Notes
2012-07-10 10:12:07SENT TO ELECTRIC BOX