Plan Review Details - Permit 12070252
Plan Review Stops For Permit 12070252
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-07-25 Cont ID  
Sent By jgomez Date 2012-07-25 Time 10:38 Rev Time 0.00
Received By jgomez Date 2012-07-25 Time 09:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-07-10 Cont ID  
Sent By jgomez Date 2012-07-10 Time 11:45 Rev Time 0.00
Received By jgomez Date 2012-07-10 Time 10:41 Sent To  
Notes
2012-07-10 11:45:40RE-ROOF REVISION BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- ENGINEER RAS 117 CALCULATIONS SUBMITTED SPECIFY NOA
 #11-0510.03, SYSTEM TYPE A(1) ON PAGE 6-7 OF 14, WHILE,
 NOA 11-0510.03 SUBMITTED IS SHOWING SYSTEM TYPE E(1) ON
 PAGE 10 OF 14. INFORMATION NEEDS TO MATCH. SEC.
 107.2.1.2 CITY AMENDMENTS TO FBC.
  
 2- GENERAL LIMITATION #5 ON PAGE 14 OF NOA 11-0510.03
 SUBMITTED SPECIFIES THAT IF THE FASTENER VALUE, AS
 FIELD-TESTED IS BELOW 275 LBF, THEN INSULATION
 ATTACHMENT SHALL NOT BE ACCEPTABLE. TEST REPORT TAS 105
 SUBMITTED SHOWS THAT THE FASTENER VALUE TESTED IS LESS
 THAN 275 LBF. THEREFORE, IT'S NOT ACCEPTABLE. SEC.
 107.2.1.2 CITY AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
 [email protected].

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-07-25 Cont ID  
Sent By jgomez Date 2012-07-25 Time 09:54 Rev Time 0.00
Received By jgomez Date 2012-07-24 Time 13:06 Sent To  
Notes
2012-07-24 13:06:47SENT TO J GOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-07-10 Cont ID  
Sent By jgomez Date 2012-07-10 Time 10:41 Rev Time 0.00
Received By jgomez Date 2012-07-09 Time 07:36 Sent To  
Notes
2012-07-10 07:36:23SENT TO J GOMEZ