| Plan Review Stops For Permit 12070151 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2012-07-06 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-07-06 |
Time |
16:11 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-07-06 |
Time |
15:57 |
Sent To |
|
|
| Notes |
| 2012-07-06 16:11:27 | PROVIDE LISTING FROM A NATIONALLY RECOGNIZED TESTING | | | LAB FOR THE NEW ELECTRIC CONTROL CABINET. NEC 110.3 | | | PROVIDE ENGINEERED DRAWINGS FOR THE MODIFICATIONS TO | | | THE LIFT STATION. NEC 110.3 | | | CLASSIFY THE LOCATION AS TO THE LEVEL OF HAZARD DUE TO | | | FLAMMABLE GASES OR VAPORS OR LIQUIDS. NEC 501.1 | | | PROVIDE CONDUIT SEALS. NEC 501.15 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2012-07-06 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-07-06 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-07-05 |
Time |
10:55 |
Sent To |
|
|
| Notes |
| 2012-07-06 11:09:10 | SENT TO ELECTRICAL UNDER $5000 SHELF FOR REVIEW. JG. |
|
|
|