Plan Review Details - Permit 12070151
Plan Review Stops For Permit 12070151
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-07-06 Cont ID  
Sent By rlecky Date 2012-07-06 Time 16:11 Rev Time 0.00
Received By rlecky Date 2012-07-06 Time 15:57 Sent To  
Notes
2012-07-06 16:11:27PROVIDE LISTING FROM A NATIONALLY RECOGNIZED TESTING
 LAB FOR THE NEW ELECTRIC CONTROL CABINET. NEC 110.3
 PROVIDE ENGINEERED DRAWINGS FOR THE MODIFICATIONS TO
 THE LIFT STATION. NEC 110.3
 CLASSIFY THE LOCATION AS TO THE LEVEL OF HAZARD DUE TO
 FLAMMABLE GASES OR VAPORS OR LIQUIDS. NEC 501.1
 PROVIDE CONDUIT SEALS. NEC 501.15
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  