| 2012-08-07 16:16:31 | 2010 FBC |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THE SCOPE OF WORK ON THE APPLICATION IS FOR |
| | REPLACING THE WINDOWS WITH IMPACT WINDOWS. BASED ON THE |
| | PLANS SUBMITTED FOR THE PLUMBING PERMIT, IT APPEARS |
| | THAT THE EXISTING GARAGE IS BEING CONVERTED TO LIVING |
| | SPACE TO CREATE A TWO FAMILY DWELLING. THE PBC PROPERTY |
| | APPRAISER SHOWS A SINGLE FAMILY DWELLING AND A GARAGE |
| | APARTMENT. UNLESS YOU HAVE PROOF THAT THE GARAGE WAS |
| | CONVERTED TO LIVING SPACE CREATING A DUPLEX WITH THE |
| | PROPER PERMITS AND INSPECTIONS, THEN IT IS ASSUMED THAT |
| | YOU ARE PROPOSING TO CONVERT THE GARAGE APARTMENT INTO |
| | A TWO FAMILY DWELLING. AN IMPACT FEE REVIEW BY PALM |
| | BEACH COUNTY WILL BE REQUIRED. PLEASE SUBMIT TWO SETS |
| | OF PLANS SHOWING THE COMPLETE SCOPE OF THE PROPOSED |
| | WORK AND PROVIDE AREA TABULATIONS ON THE PLANS. CITY |
| | AMENDMENTS 107.2.1 IN ADDITION, A REVISION TO THIS |
| | PERMIT OR A NEW PERMIT APPLICATION MAY BE REQUIRED TO |
| | INCLUDE THE SCOPE OF WORK REQUIRED TO CONVERT THE |
| | GARAGE APARTMENT TO A TWO FAMILY DWELLING WITH THE |
| | APPROPRIATE VALUE FOR THE WORK INDICATED. |
| | |
| | 2) SUBMIT TWO SETS OF ENERGY CALCULATIONS FOR THE |
| | DUPLEX SHOWING COMPLIANCE WITH CHAPTER 4 OF THE 2010 |
| | FBC ENERGY CONSERVATION. |
| | |
| | 3) PROVIDE WALL AND ROOF SECTIONS SHOWING INSULATION, |
| | FRAMING, VENTING, FINISHES, ETC. CITY AMENDMENTS |
| | 107.2.1 |
| | |
| | 4) SHOW COMPLIANCE WITH FBC R302.3 FOR 1-HOUR FIRE |
| | RESISTANCE RATED SEPARATION BETWEEN TWO FAMILY |
| | DWELLINGS FROM THE FOUNDATION TO THE UNDERSIDE OF THE |
| | ROOF SHEATHING. |
| | |
| | 5) SHOW COMPLIANCE WITH FBC R311.2 AT THE CONVERTED |
| | GARAGE FOR THE REQUIRED EGRESS DOOR WITH A MINIMUM 32" |
| | CLEAR OPENING WIDTH MEASURED FROM THE FACE OF THE DOOR |
| | TO THE STOP WITH THE DOOR OPEN 90 DEGREES. |
| | |
| | 6) SHOW COMPLIANCE WITH FBC R310.1 FOR THE EMERGENCY |
| | ESCAPE AND RESCUE OPENING REQUIRED IN SLEEPING ROOMS. |
| | |
| | 7) SUBMIT TWO SETS OF DIMENSIONED FLOOR PLANS SHOWING |
| | COMPLIANCE WITH FBC R307.1 FOR MINIMUM BATHROOM FIXTURE |
| | CLEARANCES AND R304 MINIMUM ROOM AREAS. |
| | |
| | 8) SHOW COMPLIANCE WITH FBC R303.3 FOR BATHROOM |
| | VENTILATION. |
| | |
| | 9) SHOW COMPLIANCE WITH FBC R305.1 FOR MINIMUM REQUIRED |
| | CEILING HEIGHT. |
| | |
| | 10) SHOW COMPLIANCE WITH FBC R314 FOR REQUIRED SMOKE |
| | ALARMS. |
| | |
| | 11) IN ORDER TO REDUCE REVIEW TIME, PLEASE SUBMIT A |
| | RESPONSE LETTER STATING HOW EACH OF THE REVIEW COMMENTS |
| | WAS ADDRESSED. THANKS. |
| | |