Plan Review Details - Permit 12070099
Plan Review Stops For Permit 12070099
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-10-15 Cont ID  
Sent By rmcdouga Date 2012-10-15 Time 14:38 Rev Time 0.00
Received By rmcdouga Date 2012-10-15 Time 14:38 Sent To  
Notes
2012-10-15 14:48:07REVISION REQUIRED
  
 SUBMIT RAS 117 CALCULATIONS FOR THE TAMKO MODIFIED ROOF
 SYSTEM NOA NO.12-0227.18. THE ONES THAT WERE SUBMITTED
 ARE NOT CORRECT FOR A STRUCTURE LOCATED IN A 170 MPH
 VULT / 132 VASD EXPOSURE D WITH A 22' MEAN ROOF HEIGHT.
 SUBMIT TWO CORRECTED SETS OF RAS 117 CALCULATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-09-20 Cont ID  
Sent By rmcdouga Date 2012-09-20 Time 11:01 Rev Time 0.00
Received By rmcdouga Date 2012-09-19 Time 10:24 Sent To  
Notes
2012-09-20 10:53:16DENIED BY BUILDING
  
 1) RAS 117 CALCULATIONS ARE INCORRECT. THE SPECIFIED C
 & C PRESSURES ARE NOT FOR EXPOSURE D. THE ASSEMBLY
 SPECIFIED ON PAGE 6 OF THE NOA NO. 12-0227.18 IS FOR AN
 INSULATED WOOD DECK. THE UPLIFT OF 60 PSF THAT IS
 SPECIFIED IN THE RAS CALCS. DOES NOT MATCH THE SPACING
 IN THE CALCS. AND IS FOR DEKFAST FASTENERS WITH HEX
 PLATES. THE CALCS. REFERENCE A SECTION FROM THE 2004
 FBC. DCA RULE 9N-3
  
 2) ENERGY CALCULATIONS ARE NOT SIGNED BY THE
 OWNER/AGENT AS REQUIRED BY 2010 FBC ENERGY CONSERVATION
 405.4.
  
 3) THE NOC WILL NEED TO BE RE-RECORDED PRIOR TO FIRST
 INSPECTION. FS 713
  
 4) THE PLANS ARE REQUIRED TO BE REVIEWED BY PALM BEACH
 COUNTY FOR IMPACT FEES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-08-07 Cont ID  
Sent By rmcdouga Date 2012-08-07 Time 14:13 Rev Time 0.00
Received By rmcdouga Date 2012-07-27 Time 16:56 Sent To  
Notes
2012-08-07 10:57:292010 FBC
  
 DENIED BY BUILDING
  
 1) THE STRUCTURE IS LOCATED WITHIN 600 FT OF THE
 INTERCOASTAL WATERWAY. ACCORDING TO FBC R301.2.1.4.3,
 THIS STRUCTURE IS LOCATED IN EXPOSURE CATEGORY D.
 PLEASE REVISE THE PRESSURES, UPLIFTS AND OTHER WIND
 LOADS ON THE PLANS.
  
 2) THE ENERGY CALCULATIONS THAT WERE SUBMITTED ARE ON
 THE OLD 2007 FBC FORM. THE 2010 FBC ENERGY CONSERVATION
 REQUIRES FORM 405. PLEASE SUBMIT 2 SETS OF ENERGY
 CALCULATIONS ON THE PROPER FORMS AS REQUIRED BY FBC
 ENERGY CONSERVATION SECTION 405.4.2.
  
 3) THERE WERE SEVERAL ERRORS ON THE ENERGY CALCULATIONS
 THAT WERE SUBMITTED AS FOLLOWS: 1) THE ADDITION IS ON A
 SLAB FOUNDATION, NOT A CRAWL SPACE. (2) THE CEILING FAN
 CREDIT IS NO LONGER ALLOWED. (3) THE CALCS. SHOW A
 VENTED ATTIC AND SHEET S-2 OF THE PLANS SHOWS AN
 UN-VENTED ATTIC WITH R-30 ICYNENE SPRAY FOAM
 INSULATION. (3) THE RESIDENCE IS LOCATED IN WEST PALM
 BEACH AND THE CALCS. HAVE FORT LAUDERDALE. PLEASE
 REVIEW THE ENERGY CALCULATIONS TO INSURE THAT THE
 INFORMATION GIVEN IS CORRECT. 2010 FBC ENERGY
 CONSERVATION CHAPTER 4.
  
 4) SUBMIT A SIGNED AND SEALED COPY OF THE SOIL REPORT
 AS REQUIRED BY FS 471.025.
  
 5) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 SECTIONAL GARAGE DOORS IS EXPIRED. SUBMIT CURRENT
 PRODUCT APPROVALS FOR THE GARAGE DOORS. DCA RULE 9N-3.
  
 6) ROOF NOTE 1 ON SHEET S-6 THAT SPECIFIES THE WIND
 SPEED AS 140MPH 3 SECOND GUST AND EXPOSURE B IS
 INCORRECT. UNDER THE 2010 FBCR THE WINDSPEED FOR WEST
 PALM BEACH IS 170 MPH VULT AND THE EXPOSURE CATEGORY
 FOR THIS STRUCTURE IS D. PLEASE CORRECT. FBC R301.2.1 &
 R301.2.1.4
  
 7) THE COMPONENT AND CLADDING PRESSURES FROM THE FRENCH
 DOOR AND CASEMENT WINDOW PRODUCT APPROVALS ARE LESS
 THAN THE REQUIRED PRESSURES SPECIFIED IN THE TABLE ON
 A-2 FOR MARK C. PLEASE PROVIDE PRODUCT APPROVALS WITH
 ADEQUATE DESIGN PRESSURES AS REQUIRED BY FBC R301.2.1.
 ALSO PLEASE HAVE THE STRUCTURAL ENGINEER REVIEW THE
 COMPONENT AND CLADDING PRESSURES IN THE TABLES ON A-2,
 THEY APPEAR TO BE THE VULT VALUES RATHER THAN THE VASD
 VALUES.
  
 8) ON THE TAMKO PRODUCT APPROVALS FOR THE FLAT ROOF,
 PLEASE SPECIFY THE APPROVED ASSEMBLY AND FASTENING
 OPTION THAT WILL BE USED. ALSO, PROVIDE TWO COPIES OF
 THE ENHANCED FASTENING REQUIREMENTS FOR THE PERIMETER
 AND CORNER AREAS IN ACCORDANCE WITH LIMITATION NUMBER 7
 ON PAGE 15 OF THE PRODUCT APPROVAL.
  
 9) PLEASE SPECIFY THE ATTACHMENT METHOD LISTED IN THE
 PRODUCT APPROVAL THAT WILL BE USED TO INSTALL THE CLAY
 BARREL AND PROVIDE ADEQUATE RESISTANCE TO OVERTURNING
 MOMENT PER FBC R905.3. IF POLYFOAM WILL BE USED PLEASE
 SUBMIT TWO COPIES OF THE PRODUCT APPROVALS AS REQUIRED
 BY DCA RULE 9N-3.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-07-23 Cont ID  
Sent By rlecky Date 2012-07-23 Time 14:39 Rev Time 0.00
Received By rlecky Date 2012-07-23 Time 14:13 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2012-07-19 Cont ID  
Sent By fmittner Date 2012-07-19 Time 10:22 Rev Time 0.00
Received By fmittner Date 2012-07-19 Time 10:22 Sent To  
Notes
2012-07-19 10:23:25RETURNED TO INCOMING RESIDENTIAL FOR BOX ASSIGNMENT

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-10-15 Cont ID  
Sent By rmcdouga Date 2012-10-15 Time 14:56 Rev Time 0.00
Received By rmcdouga Date 2012-09-28 Time 16:32 Sent To  
Notes
2012-09-28 16:32:08RM

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-09-20 Cont ID  
Sent By rmcdouga Date 2012-09-20 Time 11:01 Rev Time 0.00
Received By rmcdouga Date 2012-08-29 Time 16:04 Sent To  
Notes
2012-08-30 16:05:35GAVE TO ROBBIE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-08-07 Cont ID  
Sent By rmcdouga Date 2012-08-07 Time 14:13 Rev Time 0.00
Received By rmcdouga Date 2012-07-03 Time 11:28 Sent To  
Notes
2012-07-23 11:29:51SENT TO R5 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2012-10-18 Cont ID  
Sent By rmcdouga Date 2012-10-18 Time 11:27 Rev Time 0.00
Received By rmcdouga Date 2012-10-18 Time 11:27 Sent To  
Notes
2012-10-18 11:35:34MU2012-19064

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2012-07-27 Cont ID  
Sent By rmcdouga Date 2012-07-27 Time 16:02 Rev Time 0.00
Received By rmcdouga Date 2012-07-27 Time 16:02 Sent To  
Notes
2012-07-27 16:02:51AN IMPACT FEE REVIEW BY PALM BEACH COUNTY WILL BE
 REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-09-19 Cont ID  
Sent By rmcdouga Date 2012-09-19 Time 10:24 Rev Time 0.00
Received By rmcdouga Date 2012-09-19 Time 10:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-07-27 Cont ID  
Sent By rmcdouga Date 2012-07-27 Time 16:01 Rev Time 0.00
Received By rmcdouga Date 2012-07-27 Time 15:00 Sent To  
Notes
2012-07-27 16:01:462010 FBC
  
 DENIED BY MECHANICAL
  
 1) SUBMIT TWO COPIES OF OF HEATING AND COOLING
 EQUIPMENT SIZING CALCULATIONS AS REQUIRED BY FBCR
 M1401.3. THE EQUIPMENT SPECIFIED ON THE MECHANICAL PLAN
 SHALL MATCH THE EQUIPMENT SIZING CALCULATIONS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-07-27 Cont ID  
Sent By rmcdouga Date 2012-07-27 Time 14:32 Rev Time 0.00
Received By rmcdouga Date 2012-07-27 Time 14:09 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2012-07-19 Cont ID  
Sent By fmittner Date 2012-07-19 Time 10:22 Rev Time 0.00
Received By fmittner Date 2012-07-19 Time 10:22 Sent To  
Notes
***NONE***