| 2012-07-11 09:46:30 | ****PROVISO**** |
| | ****ISSUED AT CONTRACTOR'S RISK**** |
| | ****PROVIDE REVISED INSTALLATION SCHEDULE AND FLOOR |
| | PLAN AT INSPECTION**** |
| | ****SUBJECT TO FIELD INSPECTOR'S DISCRETION, A REVISION |
| | MAY BE REQUIRED**** |
| | |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2010 |
| | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL |
| | |
| | 1. FBC 301.1, FAC9N-3, PLEASE REVISE THE INSTALLATION |
| | SCHEDULE (FOR THE ACCORDION SHUTTERS) TO ADDRESS THE |
| | FOLLOWING ISSUES: |
| | |
| | SUBSTRATE IS NOTED AS "CONCRETE BLOCK" BUT ANCHORING |
| | FROM "CONCRETE" SUBSTRATE WAS USED, SEE SHEET 11. FOR |
| | FILLED CELLS (GROUT FILLED BLOCK) OR HOLLOW BLOCK, USE |
| | THE "HOLLOW BLOCK" CHART ON THE SAME PAGE. |
| | |
| | 2.5" EDGE DISTANCE REQUIRED, 2" PROPOSED. SEE SHEET 11, |
| | ANCHOR CHART. |
| | |
| | 1 3/4" EMBEDMENT FOR TAPCON REQUIRED, 1 3/4" PROPOSED. |
| | DUE TO STUCCO, PRODUCT THICKNESS, A LONGER FASTENER IS |
| | REQUIRED. |
| | |
| | 2. PROVIDE A FLOOR PLAN SHOWING LOCATION OF WINDOW, |
| | SHUTTER, DOOR INSTALLATION. |
| | |
| | INSTRUCTIONS TO CONTRACTOR - REVISE INSTALLATION |
| | SCHEDULE AS INDICATED |
| | PROVIDE INSTALLATION SCHEDULE AND FLOOR PLAN TO FIELD |
| | INSPECTOR - SUBJECT TO INSPECTOR'S DISCRETION, REVISED |
| | INSTALLATION SCHEDULE MAY BE ACCEPTED IN THE FIELD OR A |
| | REVISION MAY BE REQUIRED |
| | |
| | DISCUSSED WITH AND AGREED TO BY CONTRACTOR |
| | |
| | |
| | |
| | |