Plan Review Details - Permit 12060899
Plan Review Stops For Permit 12060899
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-07-27 Cont ID  
Sent By jwitmer Date 2012-07-31 Time 11:46 Rev Time 0.00
Received By jwitmer Date 2012-07-27 Time 11:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-07-19 Cont ID  
Sent By jwitmer Date 2012-07-19 Time 08:43 Rev Time 0.00
Received By jwitmer Date 2012-07-18 Time 16:40 Sent To  
Notes
2012-07-19 09:10:45BUILDING PLAN REVIEW
 PERMIT: 12060899
 ADD: 1500 BELVEDERE RD
 CONT: GARLAND BROWN
 TEL: (561)719-8015
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION INDICATES THE CONTRACT VALUE
 OF $42,500.00, PLEASE SEE THE CODE SECTION LISTED BELOW
 THAT DEALS WITH ACCESSIBILITY TO EXISTING BUILDINGS AND
 THE
 ADDITIONAL COST INVOLVED TO START TO BRING THIS
 STRUCTURE UP TO THE CURRENT ACCESSIBILITY STANDARDS.
 THE 2010 FBC-ACCESSIBILITY CODE SECTION 202.4.1
 REQUIRES UP TO 20% OF THE CONTRACT VALUE ($8,500) TO
 BRING THE BUILDING UP TO CODE FOR ACCESSIBILITY.
 SECTION 202.4.2 PROVIDES THE PRIORITY IN WHICH ELEMENTS
 SHOULD BE MADE ACCESSIBLE WITHOUT INCURRING OVER THE
 20% DISPROPORTIONATE COST.
 202.4.1 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
 WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH
 OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 1A) INTERIOR DOORS ARE LABELED AS 2'8" WIDE DOORWAYS,
 2010 ACCESSIBILITY CODE 404.2.3 REQUIRES A CLEAR WIDTH
 OF 32" WHICH REQUIRES AT A MINIMUM OF 34".
 404.2.3 CLEAR WIDTH.
 DOOR OPENINGS SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES
 (815 MM) MINIMUM. CLEAR OPENINGS OF DOORWAYS WITH
 SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF
 THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 DEGREES.
 OPENINGS MORE THAN 24 INCHES (610 MM) DEEP SHALL
 PROVIDE A CLEAR OPENING OF 36 INCHES (915 MM) MINIMUM.
 THERE SHALL BE NO PROJECTIONS INTO THE REQUIRED CLEAR
 OPENING WIDTH LOWER THAN 34 INCHES (865 MM) ABOVE THE
 FINISH FLOOR OR GROUND. PROJECTIONS INTO THE CLEAR
 OPENING WIDTH BETWEEN 34 INCHES (865 MM) AND 80 INCHES
 (2030 MM) ABOVE THE FINISH FLOOR OR GROUND SHALL NOT
 EXCEED 4 INCHES (100 MM).
  
 1B) PLEASE PROVIDE A LIST OF ALTERATIONS PROVIDING
 WHERE THE MONIES WILL BE SPENT BRINGING THIS BUILDING
 UP TO THE 2010 ACCESSIBILITY CODE.
  
 2) PLEASE PROVIDE LOCATTION FOR PORTABLE FIRE
 EXTINGUISHERS PER 2010 FBC-B:
 906.5 CONSPICUOUS LOCATION. [F]
  
 PORTABLE FIRE EXTINGUISHERS SHALL BE LOCATED IN
 CONSPICUOUS LOCATIONS WHERE THEY WILL BE READILY
 ACCESSIBLE AND IMMEDIATELY AVAILABLE FOR USE. THESE
 LOCATIONS SHALL BE ALONG NORMAL PATHS OF TRAVEL, UNLESS
 THE FIRE CODE OFFICIAL DETERMINES THAT THE HAZARD POSED
 INDICATES THE NEED FOR PLACEMENT AWAY FROM NORMAL PATHS
 OF TRAVEL.
  
 906.6 UNOBSTRUCTED AND UNOBSCURED. [F]
  
 PORTABLE FIRE EXTINGUISHERS SHALL NOT BE OBSTRUCTED OR
 OBSCURED FROM VIEW. IN ROOMS OR AREAS IN WHICH VISUAL
 OBSTRUCTION CANNOT BE COMPLETELY AVOIDED, MEANS SHALL
 BE PROVIDED TO INDICATE THE LOCATIONS OF EXTINGUISHERS.
  
 3A)EXIT SIGNS 2010 FBC-B 1006.3.1: EXITS SHALL BE
 MARKED BY AN APPROVED SIGN READILY VISIBLE FROM ANY
 DIRECTION OF EXIT ACCESS. EVERY EXIT SIGN SHALL BE
 SUITABLY ILLUMINATED BY A RELIABLE LIGHT SOURCE.
 EXTERNALLY AND INTERNALLY ILLUMINATED SIGNS SHALL BE
 VISIBLE IN BOTH NORMAL AND EMERGENCY LIGHTING.
  
 3B) 1006.3.4 EXIT STAIR DOOR OR TACTILE SIGNAGE.
 TACTILE SIGNAGE STATING "EXIT" AND COMPLYING WITH
 ICC/ANSI A117.1, AMERICAN NATIONAL STANDARD FOR
 ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES, SHALL
 BE INSTALLED ADJACENT TO THE LATCH SIDE OF THE DOOR 60
 INCHES (1524 MM) ABOVE THE FINISHED FLOOR TO THE CENTER
 LINE OF THE SIGN.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-07-09 Cont ID  
Sent By rlecky Date 2012-07-09 Time 11:35 Rev Time 0.00
Received By rlecky Date 2012-07-09 Time 09:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2012-08-02 Cont ID  
Sent By wjolin Date 2012-08-02 Time 10:26 Rev Time 0.00
Received By wjolin Date 2012-08-02 Time 10:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2012-07-31 Cont ID  
Sent By wjolin Date 2012-07-31 Time 11:35 Rev Time 0.00
Received By wjolin Date 2012-07-31 Time 11:12 Sent To B
Notes
2012-07-31 11:35:001500 BELVEDERE ROAD
 PERMIT #12060899
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 COMPLIED: PROVIDE PORTABLE FIRE EXTINGUISHERS.
 EXTINGUISHERS SHALL HAVE A MINIMUM RATING OF 2A:10BC
 AND SHALL BE TAGGED BY A LICENSED FIRE EXTINGUISHER
 COMPANY. TRAVEL DISTANCE TO EXTINGUISHERS SHALL NOT
 EXCEED 75 FEET.
  
 REPEAT COMMENT: PROVIDE BUILDING ADDRESS VISIBLE FROM
 THE STREET. NUMBERS SHALL BE ATTACHED TO THE BUILDING
 AND BE AT LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE
 AND SHALL CONTRAST THE BACKGROUND (REFERENCE: SECTION
 10.12.1.2 OF THE FLORIDA FIRE PREVENTION CODE - NFPA
 1).
  
 REPEAT COMMENT: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED
 EXIT DOORS WITH EXIT SIGNS.
  
 REPEAT COMMENT: PROVIDE A FLOOR PLAN SHOWING EXIT
 DOORS, LIGHTING, ETC. FOR THE EASTERN MOST PORTION OF
 THE BUILDING INDICATED AS "NO WORK THIS AREA." INDICATE
 THE USE OF THIS SPACE.
  
 REPEAT COMMENT: INDICATE IF ANY VEHICLE REFUELING OR
 VEHICLE MAINTENANCE/REPAIRS/BODYWORK/PAINTING IS
 INTENDED FOR THIS FACILITY.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-07-10 Cont ID  
Sent By wjolin Date 2012-07-10 Time 09:35 Rev Time 0.00
Received By wjolin Date 2012-07-10 Time 09:12 Sent To  
Notes
2012-07-10 09:34:531500 BELVEDERE ROAD
 PERMIT #12060899
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET.
 NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT
 LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND SHALL
 CONTRAST THE BACKGROUND (REFERENCE: SECTION 10.12.1.2
 OF THE FLORIDA FIRE PREVENTION CODE ? NFPA 1).
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 PROVIDE A FLOOR PLAN SHOWING EXIT DOORS, LIGHTING, ETC.
 FOR THE EASTERN MOST PORTION OF THE BUILDING INDICATED
 AS "NO WORK THIS AREA." INDICATE THE USE OF THIS SPACE.
  
 INDICATE IF ANY VEHICLE REFUELING OR VEHICLE
 MAINTENANCE/REPAIRS/BODYWORK IS INTENDED FOR THIS
 FACILITY.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-08-02 Cont ID  
Sent By wjolin Date 2012-08-02 Time 10:26 Rev Time 0.00
Received By wjolin Date 2012-08-02 Time 10:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-08-02 Cont ID  
Sent By wjolin Date 2012-08-02 Time 10:26 Rev Time 0.00
Received By wjolin Date 2012-07-23 Time 15:09 Sent To  
Notes
2012-07-24 15:10:29B01

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-07-19 Cont ID  
Sent By hmoser Date 2012-07-19 Time 14:53 Rev Time 0.00
Received By hmoser Date 2012-06-29 Time 08:53 Sent To  
Notes
2012-07-02 08:58:15B01

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-07-19 Cont ID  
Sent By hmoser Date 2012-07-19 Time 14:52 Rev Time 0.00
Received By hmoser Date 2012-07-19 Time 14:01 Sent To  
Notes
2012-07-19 14:52:50PASS PROVISO
 REFER TO SECTION 503.2.4.4 SHUT OFF DAMPER CONTROLS.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status N Date 2012-07-10 Cont ID  
Sent By lwagner Date 2012-07-10 Time 10:28 Rev Time 0.00
Received By lwagner Date 2012-07-10 Time 10:13 Sent To  
Notes
2012-07-10 10:29:18NO PLUMBING SHOWN AT THIS TIME.

Review Stop Z ZONING
Rev No 1 Status N Date 2012-07-17 Cont ID  
Sent By eschneid Date 2012-07-17 Time 16:34 Rev Time 0.50
Received By eschneid Date 2012-07-17 Time 16:17 Sent To  
Notes
2012-07-17 16:35:41NOT REQUIRED - VALUE OF PERMITS OVER PAST YEAR LESS
 THAN 50% OF STRUCTURE VALUE.
  
 SEPARATE PERMITS REQUIRED FOR SIGNS AND SITE LIGHTING.