Plan Review Details - Permit 12060858
Plan Review Stops For Permit 12060858
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2013-03-07 Cont ID  
Sent By jgomez Date 2013-03-07 Time 15:05 Rev Time 0.00
Received By jgomez Date 2013-03-07 Time 15:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2013-01-24 Cont ID  
Sent By jgomez Date 2013-01-24 Time 08:38 Rev Time 0.00
Received By jgomez Date 2013-01-24 Time 08:38 Sent To  
Notes
2013-01-24 08:39:02RESIDENTIAL (R3) CHANGE OF USE SIXTH BUILDING REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 ***ORIGINAL COMMENTS:
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 SEC. 107.2 CITY AMENDMENTS TO FBC AND RULE 9N-3 FOR:
 A) CASEMENT WINDOW AS SHOWN ON PLANS. CLARIFY IF
 DRAWINGS SUBMITTED ARE ALREADY APPROVED BY DCA OR BY
 MIAMI-DADE. PROVIDE PRODUCT APPROVAL NUMBER OR NOA
 NUMBER. OTHERWISE COMPLETE PRODUCT APPROVAL INFORMATION
 CAN BE SUBMITTED BY THE ENGINEER TO OBTAIN A ONE TIME
 LOCAL PRODUCT APPROVAL.
  
 B) SINGLE HUNG WINDOW AS SHOWN ON PLANS. SAME COMMENT
 AS FOR CASEMENT WINDOW ABOVE.
  
 2- ARCHITECT TO REVIEW AND APPROVE IN WRITING ABOVE
 PRODUCT APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS.
  
  
 ***RESPONSE TO INFORMATION SUBMITTED:
 A) DRAWINGS SUBMITTED ARE ONLY FOR SINGLE HUNG WINDOWS.
 NEED ALSO PRODUCT APPROVAL FOR CASEMENT WINDOW AS SHOWN
 ON PLANS.
  
 B) DRAWINGS SUBMITTED DON'T SHOW IF THEY WERE APPROVED
 EITHER BY THE FLORIDA BUILDING COMMISSION OR BY
 MIAMI-DADE.
 ***NOTE: IF THEY ARE NOT APPROVED BY EITHER ONE, THEN
 MANUFACTURER MAY APPLY FOR LOCAL PRODUCT APPROVAL BY
 SUBMITTING COMPLETE ORIGINAL ENGINEERING ANALYSIS FOR
 REVIEW.
  
 C) IN ADDITION, NEED THE ARCHITECT'S OF RECORD REVIEW
 AND APPROVAL IN WRITING.
  
 ***NOTE:
 SUBMIT SEPARATE PERMIT APPLICATION FOR MECHANICAL WORK
 (A/C WORK).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2013-01-07 Cont ID  
Sent By jgomez Date 2013-01-07 Time 09:06 Rev Time 0.00
Received By jgomez Date 2013-01-07 Time 09:06 Sent To  
Notes
2013-01-07 09:10:13RESIDENTIAL (R3) CHANGE OF USE FIFTH BUILDING REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 1- E-MAIL SUBMITTED SHOWS NOA 11-0107.10. THIS NOA IS
 FOR WINDOW MULLIONS. THERE ARE NOT WINDOW MULLIONS ON
 THIS PROJECT. NEED TO PROVIDE PRODUCT APPROVALS FOR
 CASEMENT WINDOWS AND FOR SINGLE HUNG WINDOWS AS SHOWN
 ON PLANS. SEE COPY OF PREVIOUS CHECKLIST BELOW:
  
  
  
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 SEC. 107.2 CITY AMENDMENTS TO FBC AND RULE 9N-3 FOR:
 A) CASEMENT WINDOW AS SHOWN ON PLANS. CLARIFY IF
 DRAWINGS SUBMITTED ARE ALREADY APPROVED BY DCA OR BY
 MIAMI-DADE. PROVIDE PRODUCT APPROVAL NUMBER OR NOA
 NUMBER. OTHERWISE COMPLETE PRODUCT APPROVAL INFORMATION
 CAN BE SUBMITTED BY THE ENGINEER TO OBTAIN A ONE TIME
 LOCAL PRODUCT APPROVAL.
  
 B) SINGLE HUNG WINDOW AS SHOWN ON PLANS. SAME COMMENT
 AS FOR CASEMENT WINDOW ABOVE.
  
 2- ARCHITECT TO REVIEW AND APPROVE IN WRITING ABOVE
 PRODUCT APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS.
  
 3- FOUR TIMES FOR THE PORTION OF PLAN REVIEW FEE WAS
 CHARGED TO THE ARCHITECT AS REQUIRED BY FLORIDA STATUTE
 553.80(2)(B) AND AS MENTIONED ON THE PREVIOUS THIRD
 REVIEW CHECKLIST. TOTAL FEE IS $332.52 (83.13 X 4 =
 332.52).
  
 ***NOTE:
 SUBMIT SEPARATE PERMIT APPLICATIONS FOR ELECTRICAL AND
 FOR MECHANICAL WORK. ONLY PERMIT APPLICATIONS FOR THE
 BUILDING AND PLUMBING WORK WERE SUBMITTED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2012-12-17 Cont ID  
Sent By jgomez Date 2012-12-17 Time 10:59 Rev Time 0.00
Received By jgomez Date 2012-12-17 Time 10:58 Sent To  
Notes
2012-12-17 13:12:16RESIDENTIAL (R3) CHANGE OF USE FOURTH BUILDING REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 SEC. 107.2 CITY AMENDMENTS TO FBC AND RULE 9N-3 FOR:
 A) CASEMENT WINDOW AS SHOWN ON PLANS. CLARIFY IF
 DRAWINGS SUBMITTED ARE ALREADY APPROVED BY DCA OR BY
 MIAMI-DADE. PROVIDE PRODUCT APPROVAL NUMBER OR NOA
 NUMBER. OTHERWISE COMPLETE PRODUCT APPROVAL INFORMATION
 CAN BE SUBMITTED BY THE ENGINEER TO OBTAIN A ONE TIME
 LOCAL PRODUCT APPROVAL.
  
 B) SINGLE HUNG WINDOW AS SHOWN ON PLANS. SAME COMMENT
 AS FOR CASEMENT WINDOW ABOVE.
  
 2- ARCHITECT TO REVIEW AND APPROVE IN WRITING ABOVE
 PRODUCT APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS.
  
 3- FOUR TIMES FOR THE PORTION OF PLAN REVIEW FEE WAS
 CHARGED TO THE ARCHITECT AS REQUIRED BY FLORIDA STATUTE
 553.80(2)(B) AND AS MENTIONED ON THE PREVIOUS THIRD
 REVIEW CHECKLIST. TOTAL FEE IS $332.52 (83.13 X 4 =
 332.52).
  
 ***NOTE:
 SUBMIT SEPARATE PERMIT APPLICATIONS FOR ELECTRICAL AND
 FOR MECHANICAL WORK. ONLY PERMIT APPLICATIONS FOR THE
 BUILDING AND PLUMBING WORK WERE SUBMITTED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2012-11-05 Cont ID  
Sent By jgomez Date 2012-11-05 Time 11:13 Rev Time 0.00
Received By jgomez Date 2012-11-05 Time 11:13 Sent To  
Notes
2012-11-05 11:16:23BUILDING REVIEW THIRD CHECKLIST:
  
 1- PLANS NEED TO BE SIGNED AND SEALED BY THE ARCHITECT.
 SEC. 107.1 CITY AMENDMENTS TO FBC. PLANS SUBMITTED THIS
 TIME ARE NOT SIGNED AND SEALED.
  
 2- (A) EGRESS WINDOW W2 SPECIFIED ON PLANS DON'T COMPLY
 WITH THE MINIMUM OPENING SIZE REQUIRED BY SEC. R310 OF
 2010 FBC-RESIDENTIAL. REVISE AS REQUIRED. ALSO, CLARIFY
 IF ORDERING CUSTOM SIZE WINDOW. (REPEAT COMMENT. THREE
 TIMES).
  
 ***REVIEW RESPONSE: 37" X 54" SINGLE HUNG WINDOW
 DOESN'T MEET THE EGRESS REQUIREMENTS. I ENTERED WINDOW
 SIZE ON JELD WEN WEBSITE AND THE RESULT IS THAT IT
 DOESN'T MEET THE EGRESS REQUIREMENTS. SEE BELOW.
  
 SINGLE-HUNG
 NET FRAME WIDTH: 37"
 NET FRAME HEIGHT: 54"
 DOES NOT MEET EGRESS REQUIREMENTS.
 CLEAR OPENING WIDTH 34.75 (COMPLIES).
 CLEAR OPENING HEIGHT 20.562 (DOESN'T COMPLY).
 CLEAR OPENING SQ. FT. 4.962 (DOESN'T COMPLY).
  
 (B) THIRD DENIED REVIEW: ARCHITECT TO PAY A FEE OF FOUR
 TIMES THE ATTRIBUTED TO PLAN REVIEW AS REQUIRED BY SEC.
 553.80(2)(B) FLORIDA STATUTE. (SEC. 107.1 CITY
 AMENDMENTS TO FBC).
  
 IMPORTANT NOTICE DESIGN PROFESSIONALS FLORIDA STATUTE
 553.80(2)(B) DESIGN PROFESSIONAL DOCUMENTS:
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION A
 FEE OF FOUR TIMES THE AMOUNT OF THE PORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLAN REVIEW.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 SEC. 107.2 CITY AMENDMENTS TO FBC AND RULE 9N-3 FOR:
 A) ENTRY DOOR AS SHOWN ON PLANS. OWNER SAID NOT
 REPLACING DOOR. THEN, ARCHITECT TO REVISE PLANS
 ACCORDINGLY.
  
 B) CASEMENT WINDOW AS SHOWN ON PLANS. (REPEAT COMMENT.
 NO RESPONSE).
  
 C) SINGLE HUNG WINDOW THAT MEETS THE DESIGN PRESSURES
 CALCULATED BY THE ARCHITECT. NOA 09-0916.05 SUBMITTED
 DOESN'T MEET THE DESIGN PRESSURES CALCULATED BY THE
 ARCHITECT.
  
 4- ARCHITECT TO REVIEW AND APPROVE IN WRITING (NOT
 SIGNING AND SEALING) ALL PRODUCT APPROVALS. SEC.
 107.3.4.1 CITY AMENDMENTS. (REPEAT COMMENT. NOT
 ADDRESSED).
  
 ***NOTE:
 SUBMIT SEPARATE PERMIT APPLICATIONS FOR ELECTRICAL AND
 FOR MECHANICAL WORK. ONLY PERMIT APPLICATIONS FOR THE
 BUILDING AND PLUMBING WORK WERE SUBMITTED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-10-05 Cont ID  
Sent By jgomez Date 2012-10-05 Time 10:45 Rev Time 0.00
Received By jgomez Date 2012-10-05 Time 10:44 Sent To  
Notes
2012-10-05 10:45:59RESIDENTIAL (R3) CHANGE OF USE/ALTERATION SECOND
 BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC-RESIDENTIAL.
  
 1- (ORIGINAL COMMENT):
 EGRESS WINDOW W2 SPECIFIED ON PLANS DON'T COMPLY WITH
 THE MINIMUM OPENING SIZE REQUIRED BY SEC. R310 OF 2010
 FBC-RESIDENTIAL. REVISE AS REQUIRED. ALSO, CLARIFY IF
 ORDERING CUSTOM SIZE WINDOW. PGT SIZE CHART DOESN'T
 INCLUDE THIS SIZE OF WINDOW. SEE PRODUCT APPROVAL
 SUBMITTED.
  
 ***REVIEW RESPONSE: PROVIDE MANUFACTURER'S CUT SHEETS
 SHOWING COMPLIANCE WITH THE EGRESS OPENING OF 5.7S.F.
 AS SPECIFIED BY THE ARCHITECT. SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 2- (ORIGINAL COMMENT):
 PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY SEC.
 107.2 CITY AMENDMENTS TO FBC AND RULE 9N-3 FOR:
 A) ENTRY DOOR AS SHOWN ON PLANS.
 B) CASEMENT WINDOW AS SHOWN ON PLANS.
 C) SINGLE HUNG WINDOW. ONLY ONE NOA WAS SUBMITTED. NEED
 TWO COPIES.
 D) STORM SHUTTERS IF GLASS IN DOORS AND WINDOWS DON'T
 HAVE HURRICANE IMPACT GLASS.
 AND, PROVIDE COMPLETE INSTALLATION SCHEDULE SHOWING
 CONNECTION TYPE, ANCHOR TYPE AND SPACING.
  
 ***REVIEW RESPONSE: THERE WAS NOT RESPONSE TO THIS
 ITEM. ONLY THE FLORIDA PRODUCT APPROVALS FOR THE
 SIMPSON STRUCTURAL CONNECTORS WERE ADDRESSED. THERE WAS
 NOT RESPONSE FOR THE OTHER PRODUCT APRPOVALS.
  
 3- (ORIGINAL COMMENT):
 ARCHITECT TO REVIEW AND APPROVE IN WRITING (NOT SIGNING
 AND SEALING) ALL PRODUCT APPROVALS. SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 ***REVIEW RESPONSE: NOT RESPONSE TO THIS ITEM. NOT
 ADDRESSED.
  
 4- (ORIGINAL COMMENT):
 BRING PLANS TO PALM BEACH COUNTY BUILDING (2300 N. JOG
 RD) TO VERIFY IF IMPACT FEES ARE DUE. THEN, BRING BACK
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
 THIS IS REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 ***REVIEW RESPONSE: THIS ITEM WAS NOT ADDRESSED.
  
  
 ***NOTE:
 SUBMIT SEPARATE PERMIT APPLICATIONS FOR A/C WORK,
 ELECTRICAL WORK. ONLY PERMIT APPLICATIONS FOR THE
 BUILDING AND PLUMBING WORK WERE SUBMITTED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-07-18 Cont ID  
Sent By jgomez Date 2012-07-18 Time 10:45 Rev Time 0.00
Received By jgomez Date 2012-07-17 Time 15:49 Sent To  
Notes
2012-07-18 10:45:46RESIDENTIAL (R3) CHANGE OF USE, BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 101.4.4 AND SEC. 103.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 2- EGRESS WINDOW W2 SPECIFIED ON PLANS DON'T COMPLY
 WITH THE MINIMUM OPENING SIZE REQUIRED BY SEC. R310 OF
 2010 FBC-RESIDENTIAL. REVISE AS REQUIRED. ALSO, CLARIFY
 IF ORDERING CUSTOM SIZE WINDOW. PGT SIZE CHART DOESN'T
 INCLUDE THIS SIZE OF WINDOW. SEE PRODUCT APPROVAL
 SUBMITTED.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 SEC. 107.2 CITY AMENDMENTS TO FBC AND RULE 9N-3 FOR:
 A) ENTRY DOOR AS SHOWN ON PLANS.
 B) CASEMENT WINDOW AS SHOWN ON PLANS.
 C) SINGLE HUNG WINDOW. ONLY ONE NOA WAS SUBMITTED. NEED
 TWO COPIES.
 D) STORM SHUTTERS IF GLASS IN DOORS AND WINDOWS DON'T
 HAVE HURRICANE IMPACT GLASS. AND, PROVIDE COMPLETE
 INSTALLATION SCHEDULE SHOWING CONNECTION TYPE, ANCHOR
 TYPE AND SPACING.
 E) SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS.
 PROVIDE ONLY THE COVER PAGE AND PAGE SHOWING THE
 SPECIFIED CONNECTOR.
  
 4- ARCHITECT TO REVIEW AND APPROVE IN WRITING (NOT
 SIGNING AND SEALING) ALL PRODUCT APPROVALS. SEC.
 107.3.4.1 CITY AMENDMENTS.
  
 5- ARCHITECT TO REVISE/CLARIFY SPECIFICATIONS SHOWN ON
 PLANS. SEC.107.2.1 CITY AMENDMENTS TO FBC:
 A) THIS IS NOT ALTERATION LEVEL 1. THIS IS A CHANGE OF
 OCCUPANCY FROM GARAGE TO LIVING AREA. SEC.
 406-FBC-EXISTING BUILDING. REVISE AS REQUIRED.
 B) ARCHITECT SPECIFIES ALUMINUM IMPACT GLASS PER FBC
 1026.2. THIS SECTION IS NOT RELATED TO IMPACT GLASS.
 CITE CORRECT SECTION. SEE 2010 FLORIDA RESIDENTIAL CODE
 AND REVISE AS REQUIRED.
 C) ARCHITECT SPECIFIES 5.0 SF MIN. OPENING FOR EGRESS
 WINDOW @ GRADE PER SEC. 1026.2.1. THIS SECTION IS NOT
 RELATED TO WINDOW EGRESS. SEE 2010 FLORIDA RESIDENTIAL
 CODE AND REVISE AS REQUIRED.
  
 6- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY BUILDING TO VERIFY IF IMPACT FEES ARE DUE. BRING
 BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE
 DUE. THIS IS REQUIRED BY THE COUNTY IMPACT FEE
 ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  
  
 ***NOTE:
 SUBMIT SEPARATE PERMIT APPLICATIONS FOR A/C WORK,
 ELECTRICAL WORK. ONLY PERMIT APPLICATIONS FOR THE
 BUILDING AND PLUMBING WORK WERE SUBMITTED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-12-05 Cont ID  
Sent By rlecky Date 2012-12-05 Time 13:25 Rev Time 0.00
Received By rlecky Date 2012-12-05 Time 13:19 Sent To  
Notes
2012-12-03 14:19:17NEW SHEETS SUBMITTED. JG.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-07-09 Cont ID  
Sent By rlecky Date 2012-07-09 Time 12:25 Rev Time 0.00
Received By rlecky Date 2012-07-09 Time 12:19 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2013-03-07 Cont ID  
Sent By fmittner Date 2013-03-07 Time 16:08 Rev Time 0.00
Received By fmittner Date 2013-03-07 Time 16:08 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2012-12-12 Cont ID  
Sent By fmittner Date 2012-12-12 Time 13:41 Rev Time 0.00
Received By fmittner Date 2012-12-12 Time 13:41 Sent To  
Notes
2012-12-03 14:18:35NEW SHEETS SUBMITTED. JG.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2012-06-28 Cont ID  
Sent By fmittner Date 2012-06-28 Time 14:14 Rev Time 0.00
Received By fmittner Date 2012-06-28 Time 14:14 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2013-03-07 Cont ID  
Sent By jgomez Date 2013-03-07 Time 15:42 Rev Time 0.00
Received By jgomez Date 2013-02-21 Time 08:50 Sent To  
Notes
2013-02-22 08:50:23SENT TO JULIO'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2013-01-24 Cont ID  
Sent By jgomez Date 2013-01-24 Time 08:37 Rev Time 0.00
Received By jgomez Date 2013-01-24 Time 08:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2013-01-07 Cont ID  
Sent By jgomez Date 2013-01-07 Time 09:05 Rev Time 0.00
Received By jgomez Date 2013-01-07 Time 09:05 Sent To  
Notes
2013-01-07 09:06:01OWNER SENT E-MAIL WITH PRODUCT APPROVALS. JG.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2012-12-17 Cont ID  
Sent By jgomez Date 2012-12-17 Time 16:50 Rev Time 0.00
Received By jgomez Date 2012-11-30 Time 14:17 Sent To  
Notes
2012-12-03 14:17:28NEW SHEETS SUBMITTED. SENT TO R1 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-11-05 Cont ID  
Sent By jgomez Date 2012-11-05 Time 14:42 Rev Time 0.00
Received By jgomez Date 2012-11-01 Time 15:44 Sent To  
Notes
2012-11-01 15:45:16SENT TO J GOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-10-05 Cont ID  
Sent By jgomez Date 2012-10-05 Time 13:32 Rev Time 0.00
Received By jgomez Date 2012-10-03 Time 12:13 Sent To  
Notes
2012-10-04 12:15:11GAVE TO JULIO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-07-18 Cont ID  
Sent By jgomez Date 2012-07-18 Time 10:46 Rev Time 0.00
Received By jgomez Date 2012-06-29 Time 08:32 Sent To  
Notes
2012-07-02 08:34:05R2

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2012-11-05 Cont ID  
Sent By jgomez Date 2012-11-05 Time 14:49 Rev Time 0.00
Received By jgomez Date 2012-11-05 Time 14:49 Sent To  
Notes
2012-11-05 14:50:55NO FEES DUE. PALM BEACH COUNTY STAMPED BY W. SWOOPE ON
 DATE 10/31/12 ON DRAWING SUBMITTED. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2012-10-05 Cont ID  
Sent By jgomez Date 2012-10-05 Time 13:30 Rev Time 0.00
Received By jgomez Date 2012-10-05 Time 13:30 Sent To  
Notes
2012-10-05 13:30:47SECOND REVIEW:
 AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY BUILDING TO VERIFY IF IMPACT FEES ARE DUE. BRING
 BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE
 DUE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2012-07-18 Cont ID  
Sent By jgomez Date 2012-07-18 Time 10:28 Rev Time 0.00
Received By jgomez Date 2012-07-18 Time 10:28 Sent To  
Notes
2012-07-18 10:29:50AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY BUILDING TO VERIFY IF IMPACT FEES ARE DUE. BRING
 BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE
 DUE.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-12-13 Cont ID  
Sent By lmartine Date 2012-12-13 Time 11:40 Rev Time 0.00
Received By lmartine Date 2012-12-13 Time 11:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-07-18 Cont ID  
Sent By jgomez Date 2012-07-18 Time 10:35 Rev Time 0.00
Received By jgomez Date 2012-07-18 Time 10:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2012-12-17 Cont ID  
Sent By jgomez Date 2012-12-17 Time 16:51 Rev Time 0.00
Received By jgomez Date 2012-12-17 Time 16:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-10-05 Cont ID  
Sent By jgomez Date 2012-10-05 Time 13:32 Rev Time 0.00
Received By jgomez Date 2012-10-05 Time 13:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-07-18 Cont ID  
Sent By jgomez Date 2012-07-18 Time 10:06 Rev Time 0.00
Received By jgomez Date 2012-07-18 Time 10:06 Sent To  
Notes
2012-07-18 10:24:42RESIDENTIAL (R3) GARAGE CHANGE OF USE, PLUMBING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- LOCATION OF VENT TO ROOF SHOWN ON THE PLUMBING RISER
 DIAGRAM DOESN'T COMPLY WITH SEC. P3108.2.1 OF 2010
 FBC-RESIDENTIAL. NO MORE THAN ONE WET-VENTED FIXTURE
 DRAIN SHALL DISCHARGE UPSTREAM OF THE DRY-VENTED
 FIXTURE DRAIN CONNECTION. REVISE AS REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop Z ZONING
Rev No 2 Status P Date 2012-12-12 Cont ID  
Sent By fmittner Date 2012-12-12 Time 13:41 Rev Time 0.00
Received By fmittner Date 2012-12-12 Time 13:41 Sent To  
Notes
2012-12-03 14:19:42NEW SHEETS SUBMITTED. JG.

Review Stop Z ZONING
Rev No 1 Status P Date 2012-06-28 Cont ID  
Sent By fmittner Date 2012-06-28 Time 14:14 Rev Time 0.00
Received By fmittner Date 2012-06-28 Time 14:14 Sent To  
Notes
***NONE***