| Plan Review Stops For Permit 12060858 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
P |
Date |
2013-03-07 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2013-03-07 |
Time |
15:05 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2013-03-07 |
Time |
15:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
F |
Date |
2013-01-24 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2013-01-24 |
Time |
08:38 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2013-01-24 |
Time |
08:38 |
Sent To |
|
|
| Notes |
| 2013-01-24 08:39:02 | RESIDENTIAL (R3) CHANGE OF USE SIXTH BUILDING REVIEW | | | CHECKLIST. | | | CODE: 2010 FBC. | | | | | | ***ORIGINAL COMMENTS: | | | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | SEC. 107.2 CITY AMENDMENTS TO FBC AND RULE 9N-3 FOR: | | | A) CASEMENT WINDOW AS SHOWN ON PLANS. CLARIFY IF | | | DRAWINGS SUBMITTED ARE ALREADY APPROVED BY DCA OR BY | | | MIAMI-DADE. PROVIDE PRODUCT APPROVAL NUMBER OR NOA | | | NUMBER. OTHERWISE COMPLETE PRODUCT APPROVAL INFORMATION | | | CAN BE SUBMITTED BY THE ENGINEER TO OBTAIN A ONE TIME | | | LOCAL PRODUCT APPROVAL. | | | | | | B) SINGLE HUNG WINDOW AS SHOWN ON PLANS. SAME COMMENT | | | AS FOR CASEMENT WINDOW ABOVE. | | | | | | 2- ARCHITECT TO REVIEW AND APPROVE IN WRITING ABOVE | | | PRODUCT APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS. | | | | | | | | | ***RESPONSE TO INFORMATION SUBMITTED: | | | A) DRAWINGS SUBMITTED ARE ONLY FOR SINGLE HUNG WINDOWS. | | | NEED ALSO PRODUCT APPROVAL FOR CASEMENT WINDOW AS SHOWN | | | ON PLANS. | | | | | | B) DRAWINGS SUBMITTED DON'T SHOW IF THEY WERE APPROVED | | | EITHER BY THE FLORIDA BUILDING COMMISSION OR BY | | | MIAMI-DADE. | | | ***NOTE: IF THEY ARE NOT APPROVED BY EITHER ONE, THEN | | | MANUFACTURER MAY APPLY FOR LOCAL PRODUCT APPROVAL BY | | | SUBMITTING COMPLETE ORIGINAL ENGINEERING ANALYSIS FOR | | | REVIEW. | | | | | | C) IN ADDITION, NEED THE ARCHITECT'S OF RECORD REVIEW | | | AND APPROVAL IN WRITING. | | | | | | ***NOTE: | | | SUBMIT SEPARATE PERMIT APPLICATION FOR MECHANICAL WORK | | | (A/C WORK). | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2013-01-07 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2013-01-07 |
Time |
09:06 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2013-01-07 |
Time |
09:06 |
Sent To |
|
|
| Notes |
| 2013-01-07 09:10:13 | RESIDENTIAL (R3) CHANGE OF USE FIFTH BUILDING REVIEW | | | CHECKLIST. | | | CODE: 2010 FBC. | | | | | | 1- E-MAIL SUBMITTED SHOWS NOA 11-0107.10. THIS NOA IS | | | FOR WINDOW MULLIONS. THERE ARE NOT WINDOW MULLIONS ON | | | THIS PROJECT. NEED TO PROVIDE PRODUCT APPROVALS FOR | | | CASEMENT WINDOWS AND FOR SINGLE HUNG WINDOWS AS SHOWN | | | ON PLANS. SEE COPY OF PREVIOUS CHECKLIST BELOW: | | | | | | | | | | | | | | | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | SEC. 107.2 CITY AMENDMENTS TO FBC AND RULE 9N-3 FOR: | | | A) CASEMENT WINDOW AS SHOWN ON PLANS. CLARIFY IF | | | DRAWINGS SUBMITTED ARE ALREADY APPROVED BY DCA OR BY | | | MIAMI-DADE. PROVIDE PRODUCT APPROVAL NUMBER OR NOA | | | NUMBER. OTHERWISE COMPLETE PRODUCT APPROVAL INFORMATION | | | CAN BE SUBMITTED BY THE ENGINEER TO OBTAIN A ONE TIME | | | LOCAL PRODUCT APPROVAL. | | | | | | B) SINGLE HUNG WINDOW AS SHOWN ON PLANS. SAME COMMENT | | | AS FOR CASEMENT WINDOW ABOVE. | | | | | | 2- ARCHITECT TO REVIEW AND APPROVE IN WRITING ABOVE | | | PRODUCT APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS. | | | | | | 3- FOUR TIMES FOR THE PORTION OF PLAN REVIEW FEE WAS | | | CHARGED TO THE ARCHITECT AS REQUIRED BY FLORIDA STATUTE | | | 553.80(2)(B) AND AS MENTIONED ON THE PREVIOUS THIRD | | | REVIEW CHECKLIST. TOTAL FEE IS $332.52 (83.13 X 4 = | | | 332.52). | | | | | | ***NOTE: | | | SUBMIT SEPARATE PERMIT APPLICATIONS FOR ELECTRICAL AND | | | FOR MECHANICAL WORK. ONLY PERMIT APPLICATIONS FOR THE | | | BUILDING AND PLUMBING WORK WERE SUBMITTED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2012-12-17 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2012-12-17 |
Time |
10:59 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2012-12-17 |
Time |
10:58 |
Sent To |
|
|
| Notes |
| 2012-12-17 13:12:16 | RESIDENTIAL (R3) CHANGE OF USE FOURTH BUILDING REVIEW | | | CHECKLIST. | | | CODE: 2010 FBC. | | | | | | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | SEC. 107.2 CITY AMENDMENTS TO FBC AND RULE 9N-3 FOR: | | | A) CASEMENT WINDOW AS SHOWN ON PLANS. CLARIFY IF | | | DRAWINGS SUBMITTED ARE ALREADY APPROVED BY DCA OR BY | | | MIAMI-DADE. PROVIDE PRODUCT APPROVAL NUMBER OR NOA | | | NUMBER. OTHERWISE COMPLETE PRODUCT APPROVAL INFORMATION | | | CAN BE SUBMITTED BY THE ENGINEER TO OBTAIN A ONE TIME | | | LOCAL PRODUCT APPROVAL. | | | | | | B) SINGLE HUNG WINDOW AS SHOWN ON PLANS. SAME COMMENT | | | AS FOR CASEMENT WINDOW ABOVE. | | | | | | 2- ARCHITECT TO REVIEW AND APPROVE IN WRITING ABOVE | | | PRODUCT APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS. | | | | | | 3- FOUR TIMES FOR THE PORTION OF PLAN REVIEW FEE WAS | | | CHARGED TO THE ARCHITECT AS REQUIRED BY FLORIDA STATUTE | | | 553.80(2)(B) AND AS MENTIONED ON THE PREVIOUS THIRD | | | REVIEW CHECKLIST. TOTAL FEE IS $332.52 (83.13 X 4 = | | | 332.52). | | | | | | ***NOTE: | | | SUBMIT SEPARATE PERMIT APPLICATIONS FOR ELECTRICAL AND | | | FOR MECHANICAL WORK. ONLY PERMIT APPLICATIONS FOR THE | | | BUILDING AND PLUMBING WORK WERE SUBMITTED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2012-11-05 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2012-11-05 |
Time |
11:13 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2012-11-05 |
Time |
11:13 |
Sent To |
|
|
| Notes |
| 2012-11-05 11:16:23 | BUILDING REVIEW THIRD CHECKLIST: | | | | | | 1- PLANS NEED TO BE SIGNED AND SEALED BY THE ARCHITECT. | | | SEC. 107.1 CITY AMENDMENTS TO FBC. PLANS SUBMITTED THIS | | | TIME ARE NOT SIGNED AND SEALED. | | | | | | 2- (A) EGRESS WINDOW W2 SPECIFIED ON PLANS DON'T COMPLY | | | WITH THE MINIMUM OPENING SIZE REQUIRED BY SEC. R310 OF | | | 2010 FBC-RESIDENTIAL. REVISE AS REQUIRED. ALSO, CLARIFY | | | IF ORDERING CUSTOM SIZE WINDOW. (REPEAT COMMENT. THREE | | | TIMES). | | | | | | ***REVIEW RESPONSE: 37" X 54" SINGLE HUNG WINDOW | | | DOESN'T MEET THE EGRESS REQUIREMENTS. I ENTERED WINDOW | | | SIZE ON JELD WEN WEBSITE AND THE RESULT IS THAT IT | | | DOESN'T MEET THE EGRESS REQUIREMENTS. SEE BELOW. | | | | | | SINGLE-HUNG | | | NET FRAME WIDTH: 37" | | | NET FRAME HEIGHT: 54" | | | DOES NOT MEET EGRESS REQUIREMENTS. | | | CLEAR OPENING WIDTH 34.75 (COMPLIES). | | | CLEAR OPENING HEIGHT 20.562 (DOESN'T COMPLY). | | | CLEAR OPENING SQ. FT. 4.962 (DOESN'T COMPLY). | | | | | | (B) THIRD DENIED REVIEW: ARCHITECT TO PAY A FEE OF FOUR | | | TIMES THE ATTRIBUTED TO PLAN REVIEW AS REQUIRED BY SEC. | | | 553.80(2)(B) FLORIDA STATUTE. (SEC. 107.1 CITY | | | AMENDMENTS TO FBC). | | | | | | IMPORTANT NOTICE DESIGN PROFESSIONALS FLORIDA STATUTE | | | 553.80(2)(B) DESIGN PROFESSIONAL DOCUMENTS: | | | WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? | | | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN | | | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING | | | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS | | | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO | | | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY | | | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, | | | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, | | | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, | | | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER | | | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING | | | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL | | | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH | | | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION A | | | FEE OF FOUR TIMES THE AMOUNT OF THE PORTION OF THE | | | PERMIT FEE ATTRIBUTED TO PLAN REVIEW. | | | | | | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | SEC. 107.2 CITY AMENDMENTS TO FBC AND RULE 9N-3 FOR: | | | A) ENTRY DOOR AS SHOWN ON PLANS. OWNER SAID NOT | | | REPLACING DOOR. THEN, ARCHITECT TO REVISE PLANS | | | ACCORDINGLY. | | | | | | B) CASEMENT WINDOW AS SHOWN ON PLANS. (REPEAT COMMENT. | | | NO RESPONSE). | | | | | | C) SINGLE HUNG WINDOW THAT MEETS THE DESIGN PRESSURES | | | CALCULATED BY THE ARCHITECT. NOA 09-0916.05 SUBMITTED | | | DOESN'T MEET THE DESIGN PRESSURES CALCULATED BY THE | | | ARCHITECT. | | | | | | 4- ARCHITECT TO REVIEW AND APPROVE IN WRITING (NOT | | | SIGNING AND SEALING) ALL PRODUCT APPROVALS. SEC. | | | 107.3.4.1 CITY AMENDMENTS. (REPEAT COMMENT. NOT | | | ADDRESSED). | | | | | | ***NOTE: | | | SUBMIT SEPARATE PERMIT APPLICATIONS FOR ELECTRICAL AND | | | FOR MECHANICAL WORK. ONLY PERMIT APPLICATIONS FOR THE | | | BUILDING AND PLUMBING WORK WERE SUBMITTED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2012-10-05 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2012-10-05 |
Time |
10:45 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2012-10-05 |
Time |
10:44 |
Sent To |
|
|
| Notes |
| 2012-10-05 10:45:59 | RESIDENTIAL (R3) CHANGE OF USE/ALTERATION SECOND | | | BUILDING REVIEW COMMENTS. | | | CODE: 2010 FBC-RESIDENTIAL. | | | | | | 1- (ORIGINAL COMMENT): | | | EGRESS WINDOW W2 SPECIFIED ON PLANS DON'T COMPLY WITH | | | THE MINIMUM OPENING SIZE REQUIRED BY SEC. R310 OF 2010 | | | FBC-RESIDENTIAL. REVISE AS REQUIRED. ALSO, CLARIFY IF | | | ORDERING CUSTOM SIZE WINDOW. PGT SIZE CHART DOESN'T | | | INCLUDE THIS SIZE OF WINDOW. SEE PRODUCT APPROVAL | | | SUBMITTED. | | | | | | ***REVIEW RESPONSE: PROVIDE MANUFACTURER'S CUT SHEETS | | | SHOWING COMPLIANCE WITH THE EGRESS OPENING OF 5.7S.F. | | | AS SPECIFIED BY THE ARCHITECT. SEC. 107.2.1 CITY | | | AMENDMENTS TO FBC. | | | | | | 2- (ORIGINAL COMMENT): | | | PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY SEC. | | | 107.2 CITY AMENDMENTS TO FBC AND RULE 9N-3 FOR: | | | A) ENTRY DOOR AS SHOWN ON PLANS. | | | B) CASEMENT WINDOW AS SHOWN ON PLANS. | | | C) SINGLE HUNG WINDOW. ONLY ONE NOA WAS SUBMITTED. NEED | | | TWO COPIES. | | | D) STORM SHUTTERS IF GLASS IN DOORS AND WINDOWS DON'T | | | HAVE HURRICANE IMPACT GLASS. | | | AND, PROVIDE COMPLETE INSTALLATION SCHEDULE SHOWING | | | CONNECTION TYPE, ANCHOR TYPE AND SPACING. | | | | | | ***REVIEW RESPONSE: THERE WAS NOT RESPONSE TO THIS | | | ITEM. ONLY THE FLORIDA PRODUCT APPROVALS FOR THE | | | SIMPSON STRUCTURAL CONNECTORS WERE ADDRESSED. THERE WAS | | | NOT RESPONSE FOR THE OTHER PRODUCT APRPOVALS. | | | | | | 3- (ORIGINAL COMMENT): | | | ARCHITECT TO REVIEW AND APPROVE IN WRITING (NOT SIGNING | | | AND SEALING) ALL PRODUCT APPROVALS. SEC. 107.3.4.1 CITY | | | AMENDMENTS. | | | | | | ***REVIEW RESPONSE: NOT RESPONSE TO THIS ITEM. NOT | | | ADDRESSED. | | | | | | 4- (ORIGINAL COMMENT): | | | BRING PLANS TO PALM BEACH COUNTY BUILDING (2300 N. JOG | | | RD) TO VERIFY IF IMPACT FEES ARE DUE. THEN, BRING BACK | | | STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. | | | THIS IS REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF | | | THE UNIFIED LAND DEVELOPMENT CODE. | | | | | | ***REVIEW RESPONSE: THIS ITEM WAS NOT ADDRESSED. | | | | | | | | | ***NOTE: | | | SUBMIT SEPARATE PERMIT APPLICATIONS FOR A/C WORK, | | | ELECTRICAL WORK. ONLY PERMIT APPLICATIONS FOR THE | | | BUILDING AND PLUMBING WORK WERE SUBMITTED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2012-07-18 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2012-07-18 |
Time |
10:45 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2012-07-17 |
Time |
15:49 |
Sent To |
|
|
| Notes |
| 2012-07-18 10:45:46 | RESIDENTIAL (R3) CHANGE OF USE, BUILDING REVIEW | | | COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. | | | 101.4.4 AND SEC. 103.2 OF 2010 FBC-ENERGY CONSERVATION. | | | | | | 2- EGRESS WINDOW W2 SPECIFIED ON PLANS DON'T COMPLY | | | WITH THE MINIMUM OPENING SIZE REQUIRED BY SEC. R310 OF | | | 2010 FBC-RESIDENTIAL. REVISE AS REQUIRED. ALSO, CLARIFY | | | IF ORDERING CUSTOM SIZE WINDOW. PGT SIZE CHART DOESN'T | | | INCLUDE THIS SIZE OF WINDOW. SEE PRODUCT APPROVAL | | | SUBMITTED. | | | | | | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | SEC. 107.2 CITY AMENDMENTS TO FBC AND RULE 9N-3 FOR: | | | A) ENTRY DOOR AS SHOWN ON PLANS. | | | B) CASEMENT WINDOW AS SHOWN ON PLANS. | | | C) SINGLE HUNG WINDOW. ONLY ONE NOA WAS SUBMITTED. NEED | | | TWO COPIES. | | | D) STORM SHUTTERS IF GLASS IN DOORS AND WINDOWS DON'T | | | HAVE HURRICANE IMPACT GLASS. AND, PROVIDE COMPLETE | | | INSTALLATION SCHEDULE SHOWING CONNECTION TYPE, ANCHOR | | | TYPE AND SPACING. | | | E) SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS. | | | PROVIDE ONLY THE COVER PAGE AND PAGE SHOWING THE | | | SPECIFIED CONNECTOR. | | | | | | 4- ARCHITECT TO REVIEW AND APPROVE IN WRITING (NOT | | | SIGNING AND SEALING) ALL PRODUCT APPROVALS. SEC. | | | 107.3.4.1 CITY AMENDMENTS. | | | | | | 5- ARCHITECT TO REVISE/CLARIFY SPECIFICATIONS SHOWN ON | | | PLANS. SEC.107.2.1 CITY AMENDMENTS TO FBC: | | | A) THIS IS NOT ALTERATION LEVEL 1. THIS IS A CHANGE OF | | | OCCUPANCY FROM GARAGE TO LIVING AREA. SEC. | | | 406-FBC-EXISTING BUILDING. REVISE AS REQUIRED. | | | B) ARCHITECT SPECIFIES ALUMINUM IMPACT GLASS PER FBC | | | 1026.2. THIS SECTION IS NOT RELATED TO IMPACT GLASS. | | | CITE CORRECT SECTION. SEE 2010 FLORIDA RESIDENTIAL CODE | | | AND REVISE AS REQUIRED. | | | C) ARCHITECT SPECIFIES 5.0 SF MIN. OPENING FOR EGRESS | | | WINDOW @ GRADE PER SEC. 1026.2.1. THIS SECTION IS NOT | | | RELATED TO WINDOW EGRESS. SEE 2010 FLORIDA RESIDENTIAL | | | CODE AND REVISE AS REQUIRED. | | | | | | 6- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH | | | COUNTY BUILDING TO VERIFY IF IMPACT FEES ARE DUE. BRING | | | BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE | | | DUE. THIS IS REQUIRED BY THE COUNTY IMPACT FEE | | | ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE. | | | | | | | | | ***NOTE: | | | SUBMIT SEPARATE PERMIT APPLICATIONS FOR A/C WORK, | | | ELECTRICAL WORK. ONLY PERMIT APPLICATIONS FOR THE | | | BUILDING AND PLUMBING WORK WERE SUBMITTED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2012-12-05 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-12-05 |
Time |
13:25 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-12-05 |
Time |
13:19 |
Sent To |
|
|
| Notes |
| 2012-12-03 14:19:17 | NEW SHEETS SUBMITTED. JG. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2012-07-09 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-07-09 |
Time |
12:25 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-07-09 |
Time |
12:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
3 |
Status |
P |
Date |
2013-03-07 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2013-03-07 |
Time |
16:08 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2013-03-07 |
Time |
16:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
2 |
Status |
P |
Date |
2012-12-12 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2012-12-12 |
Time |
13:41 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2012-12-12 |
Time |
13:41 |
Sent To |
|
|
| Notes |
| 2012-12-03 14:18:35 | NEW SHEETS SUBMITTED. JG. |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2012-06-28 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2012-06-28 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2012-06-28 |
Time |
14:14 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2013-03-07 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2013-03-07 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2013-02-21 |
Time |
08:50 |
Sent To |
|
|
| Notes |
| 2013-02-22 08:50:23 | SENT TO JULIO'S DESK FOR REVIEW. JG. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2013-01-24 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2013-01-24 |
Time |
08:37 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2013-01-24 |
Time |
08:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2013-01-07 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2013-01-07 |
Time |
09:05 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2013-01-07 |
Time |
09:05 |
Sent To |
|
|
| Notes |
| 2013-01-07 09:06:01 | OWNER SENT E-MAIL WITH PRODUCT APPROVALS. JG. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2012-12-17 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2012-12-17 |
Time |
16:50 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2012-11-30 |
Time |
14:17 |
Sent To |
|
|
| Notes |
| 2012-12-03 14:17:28 | NEW SHEETS SUBMITTED. SENT TO R1 SHELF FOR REVIEW. JG. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2012-11-05 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2012-11-05 |
Time |
14:42 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2012-11-01 |
Time |
15:44 |
Sent To |
|
|
| Notes |
| 2012-11-01 15:45:16 | SENT TO J GOMEZ |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2012-10-05 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2012-10-05 |
Time |
13:32 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2012-10-03 |
Time |
12:13 |
Sent To |
|
|
| Notes |
| 2012-10-04 12:15:11 | GAVE TO JULIO |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2012-07-18 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2012-07-18 |
Time |
10:46 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2012-06-29 |
Time |
08:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
P |
Date |
2012-11-05 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2012-11-05 |
Time |
14:49 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2012-11-05 |
Time |
14:49 |
Sent To |
|
|
| Notes |
| 2012-11-05 14:50:55 | NO FEES DUE. PALM BEACH COUNTY STAMPED BY W. SWOOPE ON | | | DATE 10/31/12 ON DRAWING SUBMITTED. JG. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2012-10-05 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2012-10-05 |
Time |
13:30 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2012-10-05 |
Time |
13:30 |
Sent To |
|
|
| Notes |
| 2012-10-05 13:30:47 | SECOND REVIEW: | | | AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH | | | COUNTY BUILDING TO VERIFY IF IMPACT FEES ARE DUE. BRING | | | BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE | | | DUE. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2012-07-18 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2012-07-18 |
Time |
10:28 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2012-07-18 |
Time |
10:28 |
Sent To |
|
|
| Notes |
| 2012-07-18 10:29:50 | AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH | | | COUNTY BUILDING TO VERIFY IF IMPACT FEES ARE DUE. BRING | | | BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE | | | DUE. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2012-12-13 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2012-12-13 |
Time |
11:40 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2012-12-13 |
Time |
11:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2012-07-18 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2012-07-18 |
Time |
10:35 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2012-07-18 |
Time |
10:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2012-12-17 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2012-12-17 |
Time |
16:51 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2012-12-17 |
Time |
16:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2012-10-05 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2012-10-05 |
Time |
13:32 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2012-10-05 |
Time |
13:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2012-07-18 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2012-07-18 |
Time |
10:06 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2012-07-18 |
Time |
10:06 |
Sent To |
|
|
| Notes |
| 2012-07-18 10:24:42 | RESIDENTIAL (R3) GARAGE CHANGE OF USE, PLUMBING REVIEW | | | COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- LOCATION OF VENT TO ROOF SHOWN ON THE PLUMBING RISER | | | DIAGRAM DOESN'T COMPLY WITH SEC. P3108.2.1 OF 2010 | | | FBC-RESIDENTIAL. NO MORE THAN ONE WET-VENTED FIXTURE | | | DRAIN SHALL DISCHARGE UPSTREAM OF THE DRY-VENTED | | | FIXTURE DRAIN CONNECTION. REVISE AS REQUIRED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2012-12-12 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2012-12-12 |
Time |
13:41 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2012-12-12 |
Time |
13:41 |
Sent To |
|
|
| Notes |
| 2012-12-03 14:19:42 | NEW SHEETS SUBMITTED. JG. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2012-06-28 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2012-06-28 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2012-06-28 |
Time |
14:14 |
Sent To |
|
|
| Notes |
|
|