| 2012-07-20 16:33:39 | BUILDING PLAN REVIEW |
| | PERMIT: 12070789 |
| | ADD: 2615 OKEECHOBEE BLVD |
| | CONT: BISHOP CONSTRUCTION |
| | TEL: (561)312-1024 |
| | |
| | 2010 FLORIDA BUILDING CODE W * WEST PALM BEACH |
| | ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) SHEET A1.00 SUMMARY OF CODE INDICATES THE PLANS ARE |
| | DESIGNED TO THE 2007/009 FBC-B, PLEASE UPDATE TO THE |
| | 2010 FBC-B, THE 2010 FBC WAS ADOPTED MARCH 15, 2012. |
| | ALSO LOOK AT NOTES E & F 2007 COMMON PATH & DEAD ENDS |
| | TO UPDATE TO THE 2010 FBC. |
| | |
| | 2) SHEET A2.02DETAILS 3 & 6, (6) SCUPPERS AND (3) THE |
| | OVER FLOW DETAIL. THE SCUPPERS AND OVERFLOW DETAIL |
| | WITHIN THE PARAPET APPEAR TO BE THE SAME OPENING, WITH |
| | THE DOWNSPOUT COLLECTOR BEING 4 INCHES ABOVE THE ROOF |
| | DECK. THE QUESTION IS IF THE OVERFLOW IS IN THE SAME |
| | OPENING AND 16" WIDE WHY DOES THE DETIAL SHOW THE |
| | OVERFLOW STARTING 2 INCHES ABOVE THE ROOF, 1503.4.2.1 |
| | REQUIRES THE OVERFLOW A MINIMUM 2 INCHES ABOVE THE ROOF |
| | BUT THIS WILL BLOCK THE SCUPPERS ACTION IF THE SCUPPER |
| | AND OVERFLOW SHARE THE SAME OPENING. PLEASE PROVIDE |
| | ADDITIONAL INFORMATION? |
| | |
| | 3) SHEET A3.02, THE WALL SECTION LEGEND: |
| | |
| | 3A) NOTE # 17 INDICATES THE USE OF PRE-FINISHED |
| | LOUVERED SHUTTER, IT APPEARS THESE SHUTTERS ARE TO BE |
| | FIXED IN PLACE IN THE OPEN POSITION. WILL THESE |
| | SHUTTERS BE LOCKED IN THE OPEN POSITION, IN A HIGH WIND |
| | EVENT? IF SO PLEASE PROVIDE ENGINEERING INDICATING THEY |
| | WERE TESTED THIS WAY, PLEASE PROVIDE COMPLIANCE FOR |
| | EITHER COMPONENTS AND CLADDING |
| | 1609. 1.2 PROTECTION OF OPENINGS OR 3105.5 RIGID |
| | AWNINGS & CANOPY SHUTTERS. |
| | PRODUCT APPROVAL SUBMITTED NOA# 11-0621.02 INSTALATION |
| | NOTE # 6, OWNER / TENANT TO SECURE THE SHUTTER WITH |
| | BRACKETS & STORM BARS, PER THESE APPROVED DRAWINGS |
| | DURING PERIODS OF HURRICANE WARNINGS. |
| | |
| | 3B) NOTE # 18 PLEASE PROVIDE PRODUCT ADHESIVE |
| | SPECIFICATIONS FOR THE EPS FOAM SHAPED BANDS, |
| | ADDITIONAL INFORMATION REQUIRED 107.2.1.3. |
| | |
| | 3C) NOTE # 27 INDICATES THE USE OF A PREFINISHED |
| | ALUMINUM CAP FLASHING PLEASE PROVIDE COMPLIANCE WITH |
| | FBC-B TABLE 1503.2 MINIMUM THICKNESS FOR METAL |
| | FLASHINGS AND MANUFACTURERS SPECIFICATION FOR THE NOTE |
| | #55 TWO PIECE CEMENT PLASTER REGLET. |
| | |
| | 3D) NOTE # 32 INDICATES THE USE OF 3/4 " CEMEENT |
| | PLASTER (STUCCO) OVER PAPER BACKED METAL LATH, PLEASE |
| | MAKE NOTE OF FBC-B 1404.2.1 BOND BREAK REQUIREMENTS |
| | BETWEEN THE WATER RESISTANCE BARRIER AND THE CEMENT |
| | PLASTER. NEW TO THE 2007 FBC-B. |
| | |
| | 4) SHEET A8.05 DETAIL # 12, GALVANIZED STEEL LADDER, |
| | PLEASE PROVIDE MANUFACTURERS SPECIFICATIONS AND FOR |
| | ANCHORING OF SYSTEM. 107.2.1.3 ADDITIONAL DATA. |
| | |
| | 5) PLEASE PROVIDE (2) ORIGINAL SIGNED & SEALED SOILS |
| | REPORT PER FBC-B 1803.2 INVESTIGATION REQUIRED. |
| | |
| | 6) S-2 PROVIDES ROOF UPLIFT PRESSURES FOR DECKING & |
| | ROOFING, PLEASE PROVIDE PRESSURES FOR ZONES 1,2, & 3 |
| | FROM 10 SQ FT AND UP FOR EACH ZONE, FOR "C" EXPOSURE |
| | AND PROVIDE ROOF HEIGHT ADJUSTMENT FACTOR. FBC-B |
| | 1609.1.2.3.1. FOR 170 MPH V(ULT). |
| | |
| | 7) COMPONENTS & CLADDING, PROVIDE PRESSURES FOR WINDOWS |
| | AND DOORS FBC-B 1609.1.2.3.1 AT 170 MPH V(ULT). |
| | |
| | 8) 2007 FBC 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 9) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 10) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 |
| | NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS. PRESSURES NOT PROVIDED REVIEW |
| | COULD NOT VERIFY PRODUCT APPROVALS. |
| | (B) WINDOWS, PRESSURES NOT PROVIDED REVIEW COULD NOT |
| | VERIFY PRODUCT APPROVALS. |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES INCLUDING FOAM ROOF |
| | INSULATION, NO PRODUCT APPROVAL REPORTS SUBMITTED. |
| | (E) SHUTTERS: SEE NOTE 3A. |
| | (F) SKYLIGHTS N/A |
| | (G) PRE-ENGINEERED A/C STANDS NO PRODUCT APPROVALS |
| | SUBMITTED. |
| | |
| | 11) SHEET S-2 VERSES S-3, ON SHEET S2THE ROOF FRAMING |
| | PLAN INDICATES A BEAM RCB-1 IT APPEARS THIS SHOULD BE |
| | LABELED RBC-3 TO BE LOCATED AT 11'-4" AS APPEARS ON |
| | DETAILS ON S-3. |
| | |
| | 12) SHEET S-3 & S-4 THE PERIMETER BEAM AT ELEVATION |
| | 23'-4" IS NOT INDICATED ON THE BEAM SCHEDULE. 107.2.1.3 |
| | ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 13) S-2 SECTION MARKER 1/S-4 THIS WALL INDENTIFIES BEAM |
| | MB-3 AT ELEVATION 18'-4" BUT IS MISSING THE BEAM |
| | IDENTIFICATION MARKER AT ELEVATION 11'-4". |
| | |
| | 14) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |