Plan Review Details - Permit 12060781
Plan Review Stops For Permit 12060781
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-07-02 Cont ID  
Sent By rlecky Date 2012-07-02 Time 09:33 Rev Time 0.00
Received By rlecky Date 2012-07-02 Time 08:56 Sent To  
Notes
2012-07-02 09:34:44SEPERATE ELECTRICAL PERMIT IS REQUIRED FOR INTERIOR
 SMOKE ALARMS.
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-06-30 Cont ID  
Sent By wjolin Date 2012-06-30 Time 17:55 Rev Time 0.00
Received By wjolin Date 2012-06-30 Time 17:51 Sent To E
Notes
2012-06-30 17:55:391001 SOUTH FLAGLER DRIVE
 PERMIT #12060781
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET 9 OF 12: PROVIDE AN ADDITIONAL NOTIFICATION
 APPLIANCE FOR THE SOUTHEAST AREA OF THE POOL DECK.
  
 A CERTIFICATE OF COMPLETION AND A THIRD PARTY
 MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE SHALL
 BE PROVIDED AT TIME OF FINAL FIRE ALARM INSPECTION.
  
 CODE CHANGE ALERT: EXISTING APARTMENT BUILDINGS NOT
 PROTECTED BY AUTOMATIC SPRINKLERS OR A COMPLETE
 AUTOMATIC SMOKE DETECTION SYSTEM SHALL HAVE SINGLE
 STATION OR MULTI-STATION SMOKE ALARMS (HARD-WIRED OR
 BATTERY POWERED) INSTALLED INSIDE EACH BEDROOM AND
 DIRECTLY OUTSIDE BEDROOM DOORS.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-07-02 Cont ID  
Sent By rlecky Date 2012-07-02 Time 09:34 Rev Time 0.00
Received By rlecky Date 2012-06-27 Time 09:47 Sent To  
Notes
2012-06-28 09:48:00SENT TO FIRE SHELF FOR REVIEW. JG.