Plan Review Details - Permit 12060676
Plan Review Stops For Permit 12060676
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2012-07-16 Cont ID  
Sent By jwitmer Date 2012-07-16 Time 15:55 Rev Time 0.00
Received By jwitmer Date 2012-07-16 Time 15:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-07-05 Cont ID  
Sent By rlecky Date 2012-07-05 Time 08:41 Rev Time 0.00
Received By rlecky Date 2012-07-05 Time 08:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-06-30 Cont ID  
Sent By wjolin Date 2012-06-30 Time 20:20 Rev Time 0.00
Received By wjolin Date 2012-06-30 Time 20:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-07-30 Cont ID  
Sent By hmoser Date 2012-07-30 Time 12:38 Rev Time 0.00
Received By hmoser Date 2012-07-24 Time 16:13 Sent To  
Notes
2012-07-24 16:13:36INCOMING SENT TO MECH BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-07-18 Cont ID  
Sent By eschneid Date 2012-07-18 Time 08:26 Rev Time 0.00
Received By eschneid Date 2012-06-22 Time 13:50 Sent To  
Notes
2012-06-25 13:51:42C14

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-07-30 Cont ID  
Sent By hmoser Date 2012-07-30 Time 12:38 Rev Time 0.00
Received By hmoser Date 2012-07-30 Time 12:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-07-16 Cont ID  
Sent By hmoser Date 2012-07-16 Time 13:22 Rev Time 0.00
Received By hmoser Date 2012-07-16 Time 12:57 Sent To  
Notes
2012-07-16 13:22:02PLANS DENIED
 1) PROVIDE FRESH AIR CALCULATIONS ON THE PLANS PER
 TABLE
 403.3 2010 FBC (M)
 2) DUCT DETECTOR MUST BE INSTALLED IN SUPPLY DUCT
 PER SECTION 606.2.1 SUPPLY AIR SYSTEM. 2010 FBC (M)
 3) SUBMIT HEATING AND COOLING CALCULATIONS WITH PLANS.
 PER SECTION 503.2.1 FLORIDA ENERGY CODE 2010.
 4) REFER TO SECTION 503.2.4.4 SHUT OFF DAMPER CONTROLS.
 FLORIDA ENERGY CODE 2010
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2012-07-17 Cont ID  
Sent By eschneid Date 2012-07-17 Time 17:45 Rev Time 0.50
Received By eschneid Date 2012-07-17 Time 16:53 Sent To  
Notes
2012-07-17 17:46:25INTERIOR WORK (AND ROOFTOP A/C) LESS THAN 50% OF
 STRUCTURE VALUE.