Plan Review Details - Permit 12060646
Plan Review Stops For Permit 12060646
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-07-18 Cont ID  
Sent By jwitmer Date 2012-07-18 Time 15:06 Rev Time 0.00
Received By jwitmer Date 2012-07-18 Time 15:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-07-16 Cont ID  
Sent By jwitmer Date 2012-07-16 Time 13:04 Rev Time 0.00
Received By jwitmer Date 2012-07-16 Time 13:00 Sent To  
Notes
2012-07-16 13:05:31BUILDING PLAN REVIEW
 PERMIT: 12060646
 ADD: 1200 S FLAGLER DR # 1402
 CONT: SUNRISE CONSTRUCTION
 TEL: (772)260-8111
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION INDICATES NEW FLOORS AND THE
 PLANS INDICATE THE USE OF SOUND PROOFING, PLAESE
 PROVIDE CODE COMPLIANCE FOR;
  
 COMPLIED.
  
 1B)2010 FBC-B 603.1 ALLOWABLE MATERIALS. COMBUSTIBLE
 MATERIALS SHALL BE PERMITTED IN BUILDINGS OF TYPE I OR
 TYPE II CONSTRUCTION IN THE FOLLOWING APPLICATIONS AND
 IN ACCORDANCE WITH SECTIONS 603.1.1 THROUGH 603.1.3:
 603.1.3.2 EXCEPTIONS:
 1 INSULATION PLACED BETWEEN TWO LAYERS OF
 NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 100.
 2. INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND
 SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE
 ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN
 200.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 7/11/12 RESUBMITTAL FOR USE OF ACCOUSTICORK CONTRACTOR
 BROUGHT IN INFORMATION TO MEET 2010 FBC-B 1207.3
 STRUCTURE BORNE SOUND/ THERE IS ALSO A LEGACY REPORT
 ER-5314
 CONFIRMING CODE COMPLIANCE.
  
 STILL MISSING IS THE FLAME SPREAD REQUIREMENTS OF 2010
 FBC-B 603.1.3.2 (1).
 INSULATION PLACED BETWEEN TWO LAYERS OF NONCOMBUSTIBLE
 MATERIALS WITHOUT AN INTERVENING AIRSPACE SHALL BE
 ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN
 100.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-07-09 Cont ID  
Sent By jwitmer Date 2012-07-09 Time 16:37 Rev Time 0.00
Received By jwitmer Date 2012-07-09 Time 16:37 Sent To  
Notes
2012-07-09 16:40:37 
  
  
 BUILDING PLAN REVIEW
 PERMIT: 12060646
 ADD: 1200 S FLAGLER DR # 1402
 CONT: SUNRISE CONSTRUCTION
 TEL: (772)260-8111
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 REVIEW
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION INDICATES NEW FLOORS AND THE
 PLANS INDICATE THE USE OF SOUND PROOFING, PLAESE
 PROVIDE CODE COMPLIANCE FOR;
  
 1A) 2010 FBC-B 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 1B)2010 FBC-B 603.1 ALLOWABLE MATERIALS. COMBUSTIBLE
 MATERIALS SHALL BE PERMITTED IN BUILDINGS OF TYPE I OR
 TYPE II CONSTRUCTION IN THE FOLLOWING APPLICATIONS AND
 IN ACCORDANCE WITH SECTIONS 603.1.1 THROUGH 603.1.3:
 603.1.3.2 EXCEPTIONS:
 1 INSULATION PLACED BETWEEN TWO LAYERS OF
 NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 100.
 2. INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND
 SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE
 ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN
 200.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 7/11/12 RESUBMITTAL FOR USE OF ACCOUSTICORK CONTRACTOR
 BROUGHT IN INFORMATION TO MEET 2010 FBC-B 1207.3
 STRUCTURE BORNE SOUND/ THERE IS ALSO A LEGACY REPORT
 ER-5314
 CONFIRMING CODE COMPLIANCE.
  
 STILL MISSING IS THE FLAME SPREAD REQUIREMENTS OF 2010
 FBC-B 603.1.3.2 (1).
 NSULATION PLACED BETWEEN TWO LAYERS OF NONCOMBUSTIBLE
 MATERIALS WITHOUT AN INTERVENING AIRSPACE SHALL BE
 ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN
 100.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-07-02 Cont ID  
Sent By rlecky Date 2012-07-02 Time 11:43 Rev Time 0.00
Received By rlecky Date 2012-07-02 Time 11:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-07-02 Cont ID  
Sent By wjolin Date 2012-07-02 Time 08:57 Rev Time 0.00
Received By wjolin Date 2012-07-02 Time 08:49 Sent To  
Notes
2012-07-02 08:52:271200 SOUTH FLAGLER DRIVE - #1402
 PERMIT #12060646
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 EXISTING APARTMENT BUILDINGS NOT PROTECTED BY AUTOMATIC
 SPRINKLERS OR A COMPLETE AUTOMATIC SMOKE DETECTION
 SYSTEM SHALL HAVE SINGLE STATION OR MULTI-STATION SMOKE
 ALARMS (HARD-WIRED OR BATTERY POWERED) INSTALLED INSIDE
 EACH BEDROOM AND DIRECTLY OUTSIDE BEDROOM DOORS.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-07-16 Cont ID  
Sent By hmoser Date 2012-07-11 Time 11:55 Rev Time 0.00
Received By jwitmer Date 2012-07-11 Time 08:54 Sent To  
Notes
2012-07-12 08:55:01JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-07-16 Cont ID  
Sent By hmoser Date 2012-07-16 Time 11:55 Rev Time 0.00
Received By hmoser Date 2012-06-22 Time 11:35 Sent To  
Notes
2012-06-25 11:36:08B23

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-07-16 Cont ID  
Sent By hmoser Date 2012-07-16 Time 11:54 Rev Time 0.00
Received By hmoser Date 2012-07-16 Time 11:49 Sent To  
Notes
2012-07-16 11:54:20PLANS PASS PROVISO
 REFER TO SECTION 403.6.1 EQUIPMENT SIZING.2010 ENERGY
 CODE
 PROVIDE HEAT LOAD CALCULATIONS AT FIRST MECHANICAL
 INSPECTION.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-06-26 Cont ID  
Sent By lwagner Date 2012-06-26 Time 08:54 Rev Time 0.00
Received By lwagner Date 2012-06-26 Time 08:44 Sent To  
Notes
***NONE***