Plan Review Details - Permit 12060593
Plan Review Stops For Permit 12060593
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-07-11 Cont ID  
Sent By jgomez Date 2012-07-11 Time 08:31 Rev Time 0.00
Received By jgomez Date 2012-07-11 Time 08:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-06-25 Cont ID  
Sent By jgomez Date 2012-06-25 Time 10:48 Rev Time 0.00
Received By jgomez Date 2012-06-25 Time 10:47 Sent To  
Notes
2012-06-25 10:48:30RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW
 COMMENTS.
 2010 FBC.
  
 1- ENGINEER TO REVIEW FLAT ROOF NOA 07-1219.09
 SUBMITTED, THEN, REVIEW SPECIFIC APPROVED ASSEMBLY AND
 THEN PROVIDE THE RAS 117 CALCULATIONS AS REQUIRED BY
 GENERAL LIMITATION #7 ON LAST PAGE OF THE NOA.
 CALCULATIONS SUBMITTED ARE NOT ADDRESSING RAS 117.
  
  
 THE FOLLOWING ARE THE ORIGINAL COMMENTS ON THE FIRST
 CHECKLIST:
  
 1- FLAT ROOF NOA 07-1219.09 SUBMITTED:
 A) SPECIFY WHICH APPROVED ASSEMBLY IS GOING TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.2.1.4.3 OF 2010 FLORIDA
 RESIDENTIAL CODE.
  
 A) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 SUBMITTED. NEED NAIL ENHANCING TO MEET THE DESIGN
 PRESSURES OF SEC. R301.2.1.4.3.
  
 2- ACCORDING TO MIAMI-DADE WEBSITE SHINGLES NOA
 07-1012.02 SUBMITTED WAS SUPERSEDED. NEED TO PROVIDE
 CURRENT NOA AS REQUIRED BY DCA RULE 9N-3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-06-20 Cont ID  
Sent By jgomez Date 2012-06-20 Time 15:41 Rev Time 0.00
Received By jgomez Date 2012-06-20 Time 15:28 Sent To  
Notes
2012-06-20 15:47:10RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS.
 2010 FBC.
  
 1- FLAT ROOF NOA 07-1219.09 SUBMITTED:
 A) SPECIFY WHICH APPROVED ASSEMBLY IS GOING TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.2.1.4.3 OF 2010 FLORIDA
 RESIDENTIAL CODE.
  
 A) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 SUBMITTED. NEED NAIL ENHANCING TO MEET THE DESIGN
 PRESSURES OF SEC. R301.2.1.4.3.
  
 2- ACCORDING TO MIAMI-DADE WEBSITE SHINGLES NOA
 07-1012.02 SUBMITTED WAS SUPERSEDED. NEED TO PROVIDE
 CURRENT NOA AS REQUIRED BY DCA RULE 9N-3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-07-11 Cont ID  
Sent By jgomez Date 2012-07-11 Time 08:07 Rev Time 0.00
Received By jgomez Date 2012-07-11 Time 08:07 Sent To  
Notes
2012-07-11 08:07:41ENGINEER CALCULATIONS SUBMITTAL. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-06-25 Cont ID  
Sent By jgomez Date 2012-06-25 Time 10:47 Rev Time 0.00
Received By jgomez Date 2012-06-25 Time 10:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-06-20 Cont ID  
Sent By jgomez Date 2012-06-20 Time 15:29 Rev Time 0.00
Received By jgomez Date 2012-06-20 Time 15:29 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved