Plan Review Details - Permit 12060465
Plan Review Stops For Permit 12060465
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-07-23 Cont ID  
Sent By shill Date 2012-07-23 Time 09:21 Rev Time 0.00
Received By shill Date 2012-07-14 Time 12:10 Sent To  
Notes
2012-07-23 09:31:25****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. IN ORDER TO FACILITATE INSPECTIONS AND PLAN REVIEW,
 PLEASE COMPLETE THE INSTALLATION SCHEDULE. ANCHOR
 SPACING, DESIGN PRESSURE COLUMNS WERE LEFT BLANK.
 ANOTHER SHEET STATES THAT THIS PROJECT IS DESIGNED TO
 -66PSF, BUT ANCHOR SPACING PROPOSED DOES NOT COMPLY
 (SEE OTHER COMMENTS). THERE ARE TOO MANY OPENINGS TO
 PROVIDE A GENERIC STATEMENT REGARDING SPACING;
 INSTALLATION PROPOSED IS TO BE REVIEWED FOR COMPLIANCE
 WITH FBC RESIDENTIAL 301.1, RESISTANCE TO WIND LOADS.
  
 2. MANY ITEMS WERE HIGHLIGHTED ON THE PRODUCT APPROVAL;
 MULTIPLE FASTENERS, FASTENING METHODS, DESIGN
 PRESSURES, EDGE DISTANCE, SUBSTRATE. PLEASE ONLY NOTE
 ITEMS APPLICABLE TO THIS PROJECT IF YOU WISH TO USE
 HIGHLIGHTING OR CIRCLING AS A METHOD TO ASSIST WITH
 PLAN REVIEW AND INSPECTIONS.
  
 3. HORIZONTAL INSTALLATIONS TYPICALLY SHOULD USE THE
 HOLLOW BLOCK CHART (SEE SHEET 4) AS THEY ARE FILLED
 CELLS RATHER THAN FORMED AND POURED CONCRETE. EITHER
 PROVIDE EVIDENCE THAT THE SUBSTRATE IS FORMED AND
 POURED AT SIDES OF EACH OPENING, OR USE THE ANCHOR
 SPACING FOR HOLLOW BLOCK, FBC 301.1.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-06-29 Cont ID  
Sent By shill Date 2012-06-29 Time 18:09 Rev Time 0.00
Received By shill Date 2012-06-29 Time 18:09 Sent To  
Notes
2012-06-29 18:10:35****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE
 ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER
 FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED.
 THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET
 AT
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_
 INSTALLATION.PDF
  
 2. THIS PARCEL APPEARS TO BE LOCATED IN EXPOSURE D, FBC
 RESIDENTIAL 301.2.1.4.3. WORST CASE PRESSURES FOR A 15'
 MRH, 10SF, ZONE 5 ARE +46 / -61.6. PRESSURES PROPOSED
 ARE TOO LOW FOR EXPOSURE D.
  
 3. REVISE PLAN TO SHOW EMERGENCY MEANS OF ESCAPE, FBC
 RESIDENTIAL 310.4.
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2012-06-18 Cont ID  
Sent By fmittner Date 2012-06-18 Time 11:54 Rev Time 0.00
Received By fmittner Date 2012-06-18 Time 11:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-07-23 Cont ID  
Sent By shill Date 2012-07-23 Time 09:37 Rev Time 0.00
Received By shill Date 2012-07-09 Time 09:51 Sent To  
Notes
2012-07-10 09:52:30SENT TO S HILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-06-29 Cont ID  
Sent By shill Date 2012-06-29 Time 18:10 Rev Time 0.00
Received By shill Date 2012-06-18 Time 08:44 Sent To  
Notes
2012-06-19 08:46:01UNDER 5 K BUILDING