Plan Review Details - Permit 12060428
| Plan Review Stops For Permit 12060428 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
N |
Date |
2012-11-27 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2012-11-27 |
Time |
10:50 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2012-11-27 |
Time |
10:50 |
Sent To |
|
|
| Notes |
| 2012-11-27 10:52:41 | MET WITH CONTRACTOR (MIKE MERRITT) TO GO OVER PROCEDURE | | | TO CHANGE NOA IF USING A DIFFERENT ONE THAN THE ONE | | | THAT WAS APPROVED. I TOLD HIM WE DON'T SELECT THE NOA. | | | TOLD HIM WE REVIEW AND APPROVE THE NOA THAT WAS | | | SUBMITTED BY THE APPLICANT. JG. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2012-11-16 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2012-11-16 |
Time |
09:12 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2012-11-16 |
Time |
09:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2012-09-12 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2012-09-12 |
Time |
08:39 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2012-09-12 |
Time |
08:34 |
Sent To |
|
|
| Notes |
| 2012-09-12 08:57:35 | RESIDENTIAL (R3) RE-ROOF THIRD BUILDING REVIEW | | | CHECKLIST. | | | CODE: 2010 FBC. | | | | | | 1- ENGINEER (H. JOHN GRIFFIN II) SPECIFIES MAXIMUM | | | DESIGN PRESSURES NOT TO EXCEED -56.0PSF FOR CORNERS AND | | | PERIMETERS. THIS IS INCORRECT. ENGINEER TO PROVIDE THE | | | DESIGN PRESSURES CALCULATIONS FOR EXPOSURE "C" AS | | | REQUIRED BY SEC. R301.2.1.4.3 OF 2010 FLORIDA | | | RESIDENTIAL CODE. DESIGN PRESSURES FOR PERIMETER AND | | | CORNER AREAS ARE HIGHER THAN -56.0PSF. | | | SEC. 107.2.1.2 CITY AMENDMENTS TO FBC. | | | | | | 2- ENGINEER TO REVIEW NOA SUBMITTED AND SPECIFIC | | | APPROVED ASSEMBLY TO BE INSTALLED. THEN, PROVIDE THE | | | ACTUAL RAS 117 CALCULATIONS. INFORMATION SUBMITTED IS | | | NOT PROVIDING THE RAS 117 CALCULATIONS. ENGINEER NEEDS | | | TO REVIEW RAS 117 STANDARD. THERE IS A DIFFERENCE ON | | | THE FASTENER NUMBER AND SPECIFIC FASTENER ATTACHMENT | | | PATTERN FOR ROOF ASSEMBLIES WITH INSULATION AND ROOF | | | ASSEMBLIES WITHOUT INSULATION. PROVIDE COMPLETE | | | CALCULATIONS AND FASTENER PATTERN AS REQUIRED BY RAS | | | 117. SEC. 107.2.1.2 OF CITY AMENDMENTS TO FBC. | | | | | | IF ENGINEER HAS ANY QUESTIONS AFTER REVIEWING RAS 117 | | | STANDARD, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2012-09-06 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2012-09-06 |
Time |
16:53 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2012-09-06 |
Time |
16:47 |
Sent To |
|
|
| Notes |
| 2012-09-06 16:53:21 | RESIDENTIAL (R3) RE-ROOF, SECOND BUILDING REVIEW | | | COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS | | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | | SUBMITTED. NEED TO MEET THE DESIGN PRESSURES REQUIRED | | | BY SEC. R301.2.1.4.3. | | | | | | NOTE: | | | DESIGN PROFESSIONAL DOING THE RAS 117 CALCULATIONS TO | | | TAKE INTO CONSIDERATION THAT ACCORDING TO SEC. | | | R301.2.1.4.3 THIS BUILDING IS LOCATED ON EXPOSURE "C". | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2012-06-15 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2012-06-15 |
Time |
11:39 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2012-06-15 |
Time |
11:30 |
Sent To |
|
|
| Notes |
| 2012-06-15 11:44:18 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW COMMENTS. | | | 2010 FLORIDA BUILDING CODES. | | | | | | 1- CLEARLY SPECIFY WHICH APPROVED ASSEMBLY FROM NOA | | | 08-1112.14 SUBMITTED IS GOING TO BE USED TO VERIFY | | | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. | | | R301.2.1.4.3 OF 2010 FLORIDA RESIDENTIAL CODE. | | | NOTE: ASSEMBLIES WITH GENERAL LIMITATION #9 CAN'T BE | | | USED IN THIS BUILDING. THEY DON'T MEET THE REQUIRED | | | DESIGN PRESSURES. | | | | | | 2- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS | | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | | SUBMITTED. NEED TO MEET THE DESIGN PRESSURES REQUIRED | | | BY SEC. R301.2.1.4.3. | | | | | | NOTE: DESIGN PROFESSIONAL DOING THE RAS 117 | | | CALCULATIONS TO TAKE INTO CONSIDERATION THAT ACCORDING | | | TO SEC. R301.2.1.4.3 THIS BUILDING IS LOCATED ON | | | EXPOSURE "C". | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2012-11-16 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2012-11-16 |
Time |
08:36 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2012-11-16 |
Time |
08:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2012-09-12 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2012-09-12 |
Time |
08:33 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2012-09-12 |
Time |
08:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2012-06-15 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2012-06-15 |
Time |
11:30 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2012-06-15 |
Time |
11:30 |
Sent To |
|
|
| Notes |
|
|
|