Plan Review Details - Permit 12060339
Plan Review Stops For Permit 12060339
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-09-04 Cont ID  
Sent By jwitmer Date 2012-09-04 Time 11:48 Rev Time 0.00
Received By jwitmer Date 2012-09-04 Time 11:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-07-06 Cont ID  
Sent By jwitmer Date 2012-07-06 Time 09:11 Rev Time 0.00
Received By jwitmer Date 2012-07-06 Time 09:11 Sent To  
Notes
2012-07-06 10:26:35BUILDING PLAN REVIEW
 PERMIT: 12060339
 ADD: 3101 VILLAGE BLVD- CLUBHOUSE
 CONT: BISHOP
 TEL: (561)312-1024
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS (SHEET A2.1) INDICATE THE REPLACEMENT OF
 GLAZED OPENINGS, PLEASE SHOW CODE COMPLIANCE WITH
 1609.4.4.1 AND RULE 9N-3 .
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) WALL LOUVERS
  
 3) WITH THE REPLACEMENT OF EXTERIOR WINDOWS & DOORS THE
 PLANS WILL NEED TO DESIGN THE CRITERIA FOR WIND DESIGN.
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 3.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 3.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 3.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 3.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 3.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 4) SHEET A2.1 INDICATES A NEW WOOD TRELLIS, A6.01
 PROVIDES SCHEMATIC DETAILS OF TRELLIS, NOT ENOUGH
 INFORMATION HOW THE MWFRS WILL TRANSFER THROUGH TO THE
 FOUNDATION BELOW, MISSING TIE DOWNS ON THE 2X2 CROSS
 MEMBERS, ALL 2X8 HORIZONTAL FRAMING MEMBERS & 2X112
 CEDAR BEAMS TO COLUMNS BELOW, NOTE THE FOUNDATION
 DETAIL PROVIDES THE STEEL IN THE FOUNDATION AND BOTTOM
 POST BASE BUT THERE IS NO VERTICAL STEEL INDICATED FOR
 THE PIER.
  
 5) SHEET A2.1 ALSO INDICATES A NEW METAL FRAME AND
 CANVAS STRUCTURE OVER THE EXISTING CABANA BAR, THERE IS
 NO FRAMING INFORMATION PROVIDED, SEPERATE PLANS AND
 REVIEWS WILL BE REQUIRED.
  
 6) SHEET A2.1 INDICATES NEW NON-BEARING WALLS NO
 DETAILS WERE PROVIDED, 2010 FBC-B 107.3.5.1.1. MINIMUM
 CRITERIA FOR COMMERCIAL PLAN REVIEW.
  
 7) SHEET A2.1 INDICATES BOTH THE USE OF GLASS WALLS AND
 GLAZING IN SWING DOORS, 2010 FBC-B 2406.4 (1-2).
  
 8) PLANS DO NOT PROVIDE THE OCCUPANT LOAD, 2010 FBC-B
 MINIMUM CRITERIA FOR COMMENRCIAL PLAN REVIEW, &
 1008.1.10 PANIC HARDWARE.
  
 9) SHEET A2.1 THE NEW HANDICAPPED RAMP IS APPROXIMATELY
 8'-0" LONG, 2010 FBC-B 11-405.7.3 PLANS DO NOT INDICATE
 A BOTTOM LANDING.
  
 10) SHEET A2.1 THE NEW HANDICAPPED RAMP DOES NOT
 INDICATE COMPLIANCE WITH 11-405.7.8 RAMPS WITH A RISE
 GREATER THAN 6" SHALL HAVE HANDRAILS COMPLYING WITH
 505.
  
 11) PLANS DO NOT PROVIDE A SITE PLAN SHOWING AN
 ACCESSIBLE DROP OFF ZONE, DROPPED CURB OR ACCESSIBLE
 PARKING SPACE PLEASE SHOW COMPLIANCE WITH:
  
 2010 FBC-B 11-4.202.4.1 ALTERATIONS TO AN AREA
 CONTAINING A PRIMARY FUNCTION. IN ADDITION TO THE
 REQUIREMENTS OF SECTION 11-4.1.6(1), AN ALTERATION THAT
 AFFECTS OR COULD AFFECT THE USABILITY OF OR ACCESS TO
 AN AREA CONTAINING A PRIMARY FUNCTION SHALL BE MADE SO
 AS TO ENSURE THAT, TO THE MAXIMUM EXTENT FEASIBLE, THE
 PATH OF TRAVEL TO THE ALTERED AREA AND THE RESTROOMS,
 TELEPHONES, AND DRINKING FOUNTAINS SERVING THE ALTERED
 AREA, ARE READILY ACCESSIBLE TO AND USABLE BY
 INDIVIDUALS WITH DISABILITIES, UNLESS SUCH ALTERATIONS
 ARE DISPROPORTIONATE TO THE OVERALL ALTERATIONS TIN
 TERMS OF COST AND SCOPE.
  
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO ALTERED AREAS SHALL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20 PERCENT OF THE COST OF THE ALTERATION
 TO THE PRIMARY FUNCTION AREA.
  
 DUTY TO PROVIDE ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
  
 (1) WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE
 PATH OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS.
  
 (2)(A) IN CHOOSING WHICH ACCESSIBLE ELEMENTS TO
 PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE ELEMENTS
 THAT WILL PROVIDE THE GREATEST ACCESS, IN THE FOLLOWING
 ORDER:
  
 (I) AN ACCESSIBLE ENTRANCE;
  
 (II) AN ACCESSIBLE ROUTE TO THE ALTERED AREA:
  
 (III) AT LEAST ONE ACCESSIBLE RESTROOM FOR EACH SEX OR
 A SINGLE UNISEX RESTROOM:
  
 (IV) ACCESSIBLE TELEPHONES;
  
 (V) ACCESSIBLE DRINKING FOUNTAINS; AND
  
 (VI) WHEN POSSIBLE, ADDITIONAL ACCESSIBLE ELEMENTS SUCH
 AS PARKING, STORAGE, AND ALARMS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-09-04 Cont ID  
Sent By rlecky Date 2012-09-04 Time 13:02 Rev Time 0.00
Received By rlecky Date 2012-09-04 Time 12:54 Sent To  
Notes
2012-09-04 13:02:39RESTAMPED

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-06-15 Cont ID  
Sent By rlecky Date 2012-06-15 Time 15:38 Rev Time 0.00
Received By rlecky Date 2012-06-15 Time 15:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-08-26 Cont ID  
Sent By wjolin Date 2012-08-26 Time 16:51 Rev Time 0.00
Received By wjolin Date 2012-08-26 Time 16:03 Sent To  
Notes
2012-08-26 16:26:163101 VILLAGE BOULEVARD - CLUBHOUSE
 PERMIT #12060339
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 AS A SUBSTITUTE FOR PANIC HARDWARE, ONLY THE MAIN
 ENTRANCE IS PERMITTED TO HAVE AN INTERIOR KEYED DOOR
 LOCK (AND NO LATCH) WITH A READILY VISIBLE SIGN STATING
 THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING IS
 OCCUPIED. SIGN LETTERS SHALL BE AT LEAST 1 INCH IN
 HEIGHT. A THUMB TURN STYLE LOCK IS NOT PERMITTED TO BE
 SUBSTITUTED FOR A KEYED LOCK.
  
 IF THE EXISTING SET OF DOUBLE DOORS LEADING TO THE POOL
 DO NOT HAVE PANIC HARDWARE, THEN THE OTHER REQUIRED
 EXIT DOORS FROM THE CLUBHOUSE MUST HAVE PANIC HARDWARE.
  
 IF THE EXISTING SET OF DOUBLE DOORS LEADING TO THE POOL
 ARE EQUIPPED WITH PANIC HARDWARE, THEN THE SINGLE
 EXTERIOR EXIT DOOR (NORTH) CAN BE CONSIDERED THE MAIN
 ENTRANCE WHEREBY PANIC HARDWARE IS NOT REQUIRED.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-06-18 Cont ID  
Sent By wjolin Date 2012-06-18 Time 10:32 Rev Time 0.00
Received By wjolin Date 2012-06-18 Time 09:33 Sent To  
Notes
2012-06-18 10:32:513101 VILLAGE BOULEVARD - CLUBHOUSE
 PERMIT #12060339
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FOR OCCUPANCIES WITH AN OCCUPANT LOAD OF 100 OR MORE
 PERSONS, PANIC HARDWARE SHALL BE PROVIDED ON DOORS TO
 RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR LATCHES ARE
 PERMITTED THAT WOULD NOT BE RELEASED BY THE PANIC
 HARDWARE.
  
 PROVIDE RAMP AND HANDRAIL DETAILS FOR NEW RAMP.
  
 COOKING EQUIPMENT IS REQUIRED TO BE PROTECTED BY A TYPE
 I EXHAUST HOOD EQUIPPED WITH AN AUTOMATIC SUPPRESSION
 SYSTEM (WET CHEMICAL).
  
 PROVIDE SAFETY INFORMATION AND EQUIPMENT CUT-SHEETS FOR
 PROPOSED ELECTRIC FIRE PLACE.
  
 NOTE:
 VERIFY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 VERIFY EXISTING PORTABLE FIRE EXTINGUISHERS.
 EXTINGUISHERS SHALL HAVE A MINIMUM RATING OF 2A:10BC
 AND SHALL BE TAGGED BY A LICENSED FIRE EXTINGUISHER
 COMPANY. TRAVEL DISTANCE TO EXTINGUISHERS SHALL NOT
 EXCEED 75 FEET.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-09-10 Cont ID  
Sent By eschneid Date 2012-09-10 Time 14:36 Rev Time 0.00
Received By eschneid Date 2012-08-16 Time 17:40 Sent To  
Notes
2012-08-16 17:43:11B--15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-07-06 Cont ID  
Sent By jwitmer Date 2012-07-06 Time 10:26 Rev Time 0.00
Received By jwitmer Date 2012-06-13 Time 15:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-08-22 Cont ID  
Sent By hmoser Date 2012-08-22 Time 10:25 Rev Time 0.00
Received By hmoser Date 2012-08-22 Time 09:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-07-03 Cont ID  
Sent By hmoser Date 2012-07-03 Time 11:35 Rev Time 0.00
Received By hmoser Date 2012-07-03 Time 09:49 Sent To  
Notes
2012-07-03 11:35:02PLANS DENIED
 1) TYPE 1 HOOD IS REQUIRED AND PROTECTED WITH AN
 AUTOMATIC SUPPRESSION SYSTEM .
 PER SECTION 506.1 GENERAL 2010 FBC (M)
 2) PROVIDE PRODUCT APPROVAL FOR THE OUTSIDE LUVERS.
 PER SECTION 107.3.4.1 GENERAL FBC 2010

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-08-22 Cont ID  
Sent By lwagner Date 2012-08-22 Time 11:06 Rev Time 0.00
Received By lwagner Date 2012-08-22 Time 10:36 Sent To  
Notes
2012-08-22 11:00:49***PROVISO***
 202.3.1 PROHIBITED REDUCTION IN ACCESS. AN ALTERATION
 THAT DECREASES OR HAS THE EFFECT OF DECREASING THE
 ACCESSIBILITY OF A BUILDING OR FACILITY BELOW THE
 REQUIREMENTS FOR NEW CONSTRUCTION AT THE TIME OF THE
 ALTERATION IS PROHIBITED.

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-06-19 Cont ID  
Sent By lwagner Date 2012-06-19 Time 13:31 Rev Time 0.00
Received By lwagner Date 2012-06-19 Time 12:56 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2013-05-17 Cont ID  
Sent By eschneid Date 2013-05-17 Time 11:57 Rev Time 0.25
Received By eschneid Date 2013-05-17 Time 11:57 Sent To  
Notes
2013-05-17 11:58:33MINOR AMENDMENT SUBMITTED. THIS REVIEW DOES NOT COUNT
 AS A RESUBMITTAL.

Review Stop Z ZONING
Rev No 2 Status F Date 2012-09-10 Cont ID  
Sent By eschneid Date 2012-09-10 Time 08:56 Rev Time 0.25
Received By eschneid Date 2012-09-10 Time 08:45 Sent To  
Notes
2012-09-10 08:56:28FAILED
  
 1) REPEATE COMMENT - A MINOR PLANNED DEVELOPMENT
 AMENDMENT IS REQUIRED FOR THE EXTERIOR MODIFICATIONS TO
 THE CLUBHOUSE. APPLICATIONS ARE AVAILABLE FROM THE
 PLANNING DIVISION.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.

Review Stop Z ZONING
Rev No 1 Status F Date 2012-06-25 Cont ID  
Sent By eschneid Date 2012-06-25 Time 18:15 Rev Time 0.00
Received By eschneid Date 2012-06-25 Time 16:04 Sent To  
Notes
2012-06-25 18:19:06FAILED
  
 1) A MINOR PLANNED DEVELOPMENT AMENDMENT IS REQUIRED
 FOR THE EXTERIOR MODIFICATIONS TO THE CLUBHOUSE.
 APPLICATIONS ARE AVAILABLE FROM THE PLANNING DIVISION.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.