Plan Review Details - Permit 12060308
Plan Review Stops For Permit 12060308
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-10-14 Cont ID  
Sent By jwitmer Date 2012-10-14 Time 11:45 Rev Time 0.00
Received By jwitmer Date 2012-10-14 Time 10:15 Sent To  
Notes
2012-10-14 11:07:24 
 BUILDING PLAN REVIEW
 PERMIT: 12060308
 ADD: 428 10TH STREET (FRONT)
 CONT: RECORD CONSTRUCTION
 TEL: (561)662-2775
 2010 FLORIDA BUILDING CODE/ BUILDING W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) ROOM # 3, WEST PALM BEACH MUNI-CODE SECTION 18-99
 (1)
 SIZE OF SLEEPING ROOMS. EVERY SLEEPING ROOM SHALL HAVE
 AT LEAST 70 SQUARE FEET OF FLOOR AREA FOR THE FIRST
 OCCUPANT AND AT LEAST 50 SQUARE FEET OF FLOOR AREA PER
 ADDITIONAL OCCUPANT. RED LINED.
  
 2) ONE HOUR TENANT SEPARATION WALL BETWEEN COMMON
 LAUNDRY ROOM AND UNIT # 2, 2010
 FBC-B 709.1(6) TENANT SEPARATION WALL. RED LINED.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-09-05 Cont ID  
Sent By jwitmer Date 2012-09-05 Time 15:18 Rev Time 0.00
Received By jwitmer Date 2012-09-05 Time 14:48 Sent To  
Notes
2012-09-05 15:05:42BUILDING PLAN REVIEW
 PERMIT: 12060308
 ADD: 428 10TH STREET (FRONT)
 CONT: RECORD CONSTRUCTION
 TEL: (561)662-2775
 2010 FLORIDA BUILDING CODE/ BUILDING W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 ACTION: DENIED
  
 1-2) COMPLIED.
  
 3) 2ND REQUEST, 2010 FBC-B 1209.2 ATTIC SPACES. AN
 OPENING NOT LESS THAN 20 INCHES BY 30 INCHES (559 MM BY
 762 MM) SHALL BE PROVIDED TO ANY ATTIC AREA HAVING A
 CLEAR HEIGHT OF OVER 30 INCHES (762 MM). A 30-INCH (762
 MM) MINIMUM CLEAR HEADROOM IN THE ATTIC SPACE SHALL BE
 PROVIDED AT OR ABOVE THE ACCESS OPENING.
  
 4) 2ND REQUEST, SHEET # 1 ROOM # 3, THE PLANS HAVE
 CHANGED FROM A DWELLING UNIT TO A EFFICIENCY UNIT WHICH
 IS COVERED UNDER SECTION 2010 FBC-B 1208.4.
 2010 FBC-B
 1208.4 EFFICIENCY DWELLING UNITS.
 AN EFFICIENCY LIVING UNIT SHALL CONFORM TO THE
 REQUIREMENTS OF THE CODE EXCEPT AS MODIFIED HEREIN:
 1. THE UNIT SHALL HAVE A LIVING ROOM OF NOT LESS THAN
 220 SQUARE FEET (20.4 M2) OF FLOOR AREA. AN ADDITIONAL
 100 SQUARE FEET (9.3 M2) OF FLOOR AREA SHALL BE
 PROVIDED FOR EACH OCCUPANT OF SUCH UNIT IN EXCESS OF
 TWO.
 2. THE UNIT SHALL BE PROVIDED WITH A SEPARATE CLOSET.
 3. THE UNIT SHALL BE PROVIDED WITH A KITCHEN SINK,
 COOKING APPLIANCE AND REFRIGERATION FACILITIES, EACH
 HAVING A CLEAR WORKING SPACE OF NOT LESS THAN 30 INCHES
 (762 MM) IN FRONT. LIGHT AND VENTILATION CONFORMING TO
 THIS CODE SHALL BE PROVIDED.
 4. THE UNIT SHALL BE PROVIDED WITH A SEPARATE BATHROOM
 CONTAINING A WATER CLOSET, LAVATORY AND BATHTUB OR
 SHOWER.
 NOTE: THE BATHROOM AREA IS REMOVED FROM THE REQUIRED
 220 SQ FT FOR LIVING ROOM AREA. PLANS INDICATE WHEN
 SCALED APPROXIMATELY 205.5 SQ FT.
  
 1ST REVIEW: SHEET # 1 ROOM # 3 DOES NOT MEET THE
 REQUIREMENTS OF 2010 FBC-B 1208.3 ROOM AREA FOR A
 DWELLING AREA. EVERY DWELLING UNIT SHALL HAVE AT LEAST
 ONE ROOM THAT SHALL HAVE NOT LESS THAN 120 SQUARE FEET
 (13.9 M2) OF NET FLOOR AREA. OTHER HABITABLE ROOMS
 SHALL HAVE A NET FLOOR AREA OF NOT LESS THAN 70 SQUARE
 FEET (6.5 M2).
 LIVING ROOM AREA OF 94.95 SQ FT
 BEDROOM AREA OF 108.15 SQ FT
  
 5) 2ND REQUEST: SHEET # 1 ROOM # 4 AN EFFICIENCY UNIT
 WILL NEED TO MEET THE REQUIREMENT OF 2010 FBC-B 1208.4
 EFFICIENCY DWELLING UNITS. AN EFFICIENCY LIVING UNIT
 SHALL CONFORM TO THE REQUIREMENTS OF THE CODE EXCEPT AS
 MODIFIED HEREIN:
 1. THE UNIT SHALL HAVE A LIVING ROOM OF NOT LESS THAN
 220 SQUARE FEET (20.4 M2) OF FLOOR AREA. AN ADDITIONAL
 100 SQUARE FEET (9.3 M2) OF FLOOR AREA SHALL BE
 PROVIDED FOR EACH OCCUPANT OF SUCH UNIT IN EXCESS OF
 TWO.
  
 6) SHEET # 1 INDICATES A ONE HOUR SEPERATION WALL
 BETWEEN UNITS, BUT NOT BETWEEN THE LAUNDRY ROOM AND
 UNIT #3. PLEASE REVIEW FBC-B CONTINUITY.
 709.4 CONTINUITY. SMOKE BARRIERS SHALL FORM AN
 EFFECTIVE MEMBRANE CONTINUOUS FROM OUTSIDE WALL TO
 OUTSIDE WALL AND FROM THE TOP OF THE FOUNDATION OR
 FLOOR/CEILING ASSEMBLY BELOW TO THE UNDERSIDE OF THE
 FLOOR OR ROOF SHEATHING, DECK OR SLAB ABOVE, INCLUDING
 CONTINUITY THROUGH CONCEALED SPACES, SUCH AS THOSE
 FOUND ABOVE SUSPENDED CEILINGS, AND INTERSTITIAL
 STRUCTURAL AND MECHANICAL SPACES. THE SUPPORTING
 CONSTRUCTION SHALL BE PROTECTED TO AFFORD THE REQUIRED
 FIRE-RESISTANCE RATING OF THE WALL OR FLOOR SUPPORTED
 IN BUILDINGS OF OTHER THAN TYPE IIB, IIIB OR VB
 CONSTRUCTION.
 SEE EXCEPTION # 1 FOR REQUIRED 1 HR FIRE SEPERATION FOR
 CRAWL SPACES.
 4. THE FIRE PARTITION SEPARATING TENANT SPACES IN A
 MALL, COMPLYING WITH SECTION 402.7.2, ARE NOT REQUIRED
 TO EXTEND BEYOND THE UNDERSIDE OF A CEILING THAT IS NOT
 PART OF A FIRE-RESISTANCE-RATED ASSEMBLY. A WALL IS NOT
 REQUIRED IN ATTIC OR CEILING SPACES ABOVE TENANT
 SEPARATION WALLS.
  
 5. COMPLIED.
  
 6. FIREBLOCKING OR DRAFTSTOPPING IS NOT REQUIRED AT THE
 PARTITION LINE IN BUILDINGS EQUIPPED WITH AN AUTOMATIC
 SPRINKLER SYSTEM INSTALLED THROUGHOUT IN ACCORDANCE
 WITH SECTION 903.3.1.1 OR 903.3.1.2, PROVIDED THAT
 AUTOMATIC SPRINKLERS ARE INSTALLED IN COMBUSTIBLE
 FLOOR/CEILING AND ROOF/CEILING SPACES.
  
 7) 709.4.1 ROOF CONSTRUCTION. WHEN THE FIRE PARTITION
 IS CONTINUOUS TO THE UNDERSIDE OF THE ROOF SHEATHING IN
 OCCUPANCIES OF GROUPS R-1, R-2 AND R-3 AS APPLICABLE IN
 SECTION 101.2, IN TYPE III, IV AND V CONSTRUCTION THE
 FOLLOWING SHALL BE PROVIDED:
  
 709.4.1.1 ROOF SHEATHING. THE ROOF SHEATHING OR DECK
 SHALL BE OF APPROVED NONCOMBUSTIBLE MATERIALS OR OF
 FIRE-RETARDANT-TREATED WOOD, FOR A DISTANCE OF 4 FEET
 (1220 MM); OR
  
 709.4.1.2 ROOF PROTECTION. THE ROOF SHALL BE PROTECTED
 WITH 0.625-INCH (15.88 MM) TYPE X GYPSUM BOARD DIRECTLY
 BENEATH THE UNDERSIDE OF THE ROOF SHEATHING OR DECK,
 SUPPORTED BY A MINIMUM OF NOMINAL 2-INCH (51 MM)
 LEDGERS ATTACHED TO THE SIDES OF THE ROOF FRAMING
 MEMBERS, FOR A MINIMUM DISTANCE OF 4 FEET (1220 MM).
  
 8) SEMI- COMPLIED, ELEVATIONS DO NOT INDICATE WHICH
 WINDOWS WILL BE INSTALLED WITH THE 45 MINUTE FIRE RATED
 WINDOWS.
 SHEET # 2 INDICATES ON THE RIGHT ELEVATION WINDOWS AND
 DOORS WITH IN 10'-0" OF THE EXTERIOR STAIR, PLEASE
 PROVIDE COMPLIANCE WITH 2010 FBC-B:
 1026.6 EXTERIOR RAMPS AND STAIRWAY PROTECTION. EXTERIOR
 EXIT RAMPS AND STAIRWAYS SHALL BE SEPARATED FROM THE
 INTERIOR OF THE BUILDING AS REQUIRED IN SECTION 1022.1.
 OPENINGS SHALL BE LIMITED TO THOSE NECESSARY FOR EGRESS
 FROM NORMALLY OCCUPIED SPACES.
 EXCEPTIONS:
 1.SEPARATION FROM THE INTERIOR OF THE BUILDING IS NOT
 REQUIRED FOR OCCUPANCIES, OTHER THAN THOSE IN GROUP R-1
 OR R-2, IN BUILDINGS THAT ARE NO MORE THAN TWO STORIES
 ABOVE GRADE PLANE WHERE THE LEVEL OF EXIT DISCHARGE IS
 THE FIRST STORY ABOVE GRADE PLANE.
  
 9) FIRES COMMENTS INDICATING THIS WAS A ROOMING HOUSE
 AND WILL NOW BE USED AS A APARTMENT BUILDING CREATES A
 CHANGE OF OCCUPANCY CLASSIFICATION 2010 EXIST BUILD
 CODE SECTION 901.3 THIS INCLUDES A CHANGE OF OCCUPANCY
 WITHIN THE SAME GROUP, ROOMING HOUSE TO APTARTMENTS.
  
 2010 EXIST BUILD CODE 904.1 FIRE PROTECTION
 REQUIREMENTS OF SECTION 912 SHALL APPLY WHERE A
 BUILDING OR PORTION OF BUILDING THERE OF UNDERGO A
 CHANGE OF OCCUPANCY CLASSIFICATION.
  
 2010 EXIST BUILD CODE 912.2.1 FIRE SPRINKLER SYSTEM.
 WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT
 REQUIRES AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE
 PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH
 CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH
 SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE
 CHANGE OF OCCUPANCY OCCURS.
  
 2010 FBC-B 903.2.8 GROUP R. [F]
 AN AUTOMATIC SPRINKLER SYSTEM INSTALLED IN ACCORDANCE
 WITH SECTION 903.3 SHALL BE PROVIDED THROUGHOUT ALL
 BUILDINGS WITH A GROUP R FIRE AREA.
 THE CODE COMMENTARY MAKES IT CLEAR THE ONLY EXCEPTION
 IS RESIDENTIAL UNITS THAT ARE COVERED UNDER THE FBC-R
 RESIDENTIAL CODE ONE AND TWO FAMILY RESIDENCES.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-07-05 Cont ID  
Sent By jwitmer Date 2012-07-05 Time 11:31 Rev Time 0.00
Received By jwitmer Date 2012-07-05 Time 11:31 Sent To  
Notes
2012-07-05 11:53:43BUILDING PLAN REVIEW
 PERMIT: 12060308
 ADD: 428 10TH STREET (FRONT)
 CONT: RECORD CONSTRUCTION
 TEL: (561)662-2775
 2010 FLORIDA BUILDING CODE/ RESIDENTIAL W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, THE
 CONTRACTOR SUBMITTED PRODUCT APPROVALS FOR EXTERIOR
 DOORS AND MULLIONS BUT NO WINDOW APPROVALS
 WERE SUBMITTED WTIHIN THIS PERMIT PACKAGE.
  
 2) 2010 WPB ADMINISTRATIVE CODE 107.3.4.1 DESIGN
 PROFESSIONALS SHALL REVIEW PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9N-3 , SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 3) 2010 FBC-B 1209.2 ATTIC SPACES. AN OPENING NOT LESS
 THAN 20 INCHES BY 30 INCHES (559 MM BY 762 MM) SHALL BE
 PROVIDED TO ANY ATTIC AREA HAVING A CLEAR HEIGHT OF
 OVER 30 INCHES (762 MM). A 30-INCH (762 MM) MINIMUM
 CLEAR HEADROOM IN THE ATTIC SPACE SHALL BE PROVIDED AT
 OR ABOVE THE ACCESS OPENING.
  
 4) SHEET # 1 ROOM # 3 DOES NOT MEET THE REQUIREMENTS OF
 2010 FBC-B 1208.3 ROOM AREA. EVERY DWELLING UNIT SHALL
 HAVE AT LEAST ONE ROOM THAT SHALL HAVE NOT LESS THAN
 120 SQUARE FEET (13.9 M2) OF NET FLOOR AREA. OTHER
 HABITABLE ROOMS SHALL HAVE A NET FLOOR AREA OF NOT LESS
 THAN 70 SQUARE FEET (6.5 M2).
 LIVING ROOM AREA OF 94.95 SQ FT
 BEDROOM AREA OF 108.15 SQ FT
  
 5) SHEET # 1 ROOM # 4 AN EFFICIENCY UNIT WILL NEED TO
 MEET THE REQUIREMENT OF 2010 FBC-B 1208.4 EFFICIENCY
 DWELLING UNITS. AN EFFICIENCY LIVING UNIT SHALL CONFORM
 TO THE REQUIREMENTS OF THE CODE EXCEPT AS MODIFIED
 HEREIN:
 1. THE UNIT SHALL HAVE A LIVING ROOM OF NOT LESS THAN
 220 SQUARE FEET (20.4 M2) OF FLOOR AREA. AN ADDITIONAL
 100 SQUARE FEET (9.3 M2) OF FLOOR AREA SHALL BE
 PROVIDED FOR EACH OCCUPANT OF SUCH UNIT IN EXCESS OF
 TWO.
  
 6) SHEET # 1 INDICATES A ONE HOUR SEPERATION WALL
 BETWEEN UNITS, BUT NOT BETWEEN THE LAUNDRY ROOM AND
 UNIT #3. PLEASE REVIEW FBC-B CONTINUITY.
 709.4 CONTINUITY. SMOKE BARRIERS SHALL FORM AN
 EFFECTIVE MEMBRANE CONTINUOUS FROM OUTSIDE WALL TO
 OUTSIDE WALL AND FROM THE TOP OF THE FOUNDATION OR
 FLOOR/CEILING ASSEMBLY BELOW TO THE UNDERSIDE OF THE
 FLOOR OR ROOF SHEATHING, DECK OR SLAB ABOVE, INCLUDING
 CONTINUITY THROUGH CONCEALED SPACES, SUCH AS THOSE
 FOUND ABOVE SUSPENDED CEILINGS, AND INTERSTITIAL
 STRUCTURAL AND MECHANICAL SPACES. THE SUPPORTING
 CONSTRUCTION SHALL BE PROTECTED TO AFFORD THE REQUIRED
 FIRE-RESISTANCE RATING OF THE WALL OR FLOOR SUPPORTED
 IN BUILDINGS OF OTHER THAN TYPE IIB, IIIB OR VB
 CONSTRUCTION.
 SEE EXCEPTION # 1 FOR REQUIRED 1 HR FIRE SEPERATION FOR
 CRAWL SPACES.
 4. THE FIRE PARTITION SEPARATING TENANT SPACES IN A
 MALL, COMPLYING WITH SECTION 402.7.2, ARE NOT REQUIRED
 TO EXTEND BEYOND THE UNDERSIDE OF A CEILING THAT IS NOT
 PART OF A FIRE-RESISTANCE-RATED ASSEMBLY. A WALL IS NOT
 REQUIRED IN ATTIC OR CEILING SPACES ABOVE TENANT
 SEPARATION WALLS.
  
 5. FIREBLOCKING OR DRAFTSTOPPING IS NOT REQUIRED AT THE
 PARTITION LINE IN GROUP R-2 BUILDINGS THAT DO NOT
 EXCEED FOUR STORIES IN HEIGHT, PROVIDED THE ATTIC SPACE
 IS SUBDIVIDED BY DRAFTSTOPPING INTO AREAS NOT EXCEEDING
 3,000 SQUARE FEET (279 M2) OR ABOVE EVERY TWO DWELLING
 UNITS, WHICHEVER IS SMALLER.
  
 6. FIREBLOCKING OR DRAFTSTOPPING IS NOT REQUIRED AT THE
 PARTITION LINE IN BUILDINGS EQUIPPED WITH AN AUTOMATIC
 SPRINKLER SYSTEM INSTALLED THROUGHOUT IN ACCORDANCE
 WITH SECTION 903.3.1.1 OR 903.3.1.2, PROVIDED THAT
 AUTOMATIC SPRINKLERS ARE INSTALLED IN COMBUSTIBLE
 FLOOR/CEILING AND ROOF/CEILING SPACES.
  
 7) 709.4.1 ROOF CONSTRUCTION. WHEN THE FIRE PARTITION
 IS CONTINUOUS TO THE UNDERSIDE OF THE ROOF SHEATHING IN
 OCCUPANCIES OF GROUPS R-1, R-2 AND R-3 AS APPLICABLE IN
 SECTION 101.2, IN TYPE III, IV AND V CONSTRUCTION THE
 FOLLOWING SHALL BE PROVIDED:
  
 709.4.1.1 ROOF SHEATHING. THE ROOF SHEATHING OR DECK
 SHALL BE OF APPROVED NONCOMBUSTIBLE MATERIALS OR OF
 FIRE-RETARDANT-TREATED WOOD, FOR A DISTANCE OF 4 FEET
 (1220 MM); OR
  
 709.4.1.2 ROOF PROTECTION. THE ROOF SHALL BE PROTECTED
 WITH 0.625-INCH (15.88 MM) TYPE X GYPSUM BOARD DIRECTLY
 BENEATH THE UNDERSIDE OF THE ROOF SHEATHING OR DECK,
 SUPPORTED BY A MINIMUM OF NOMINAL 2-INCH (51 MM)
 LEDGERS ATTACHED TO THE SIDES OF THE ROOF FRAMING
 MEMBERS, FOR A MINIMUM DISTANCE OF 4 FEET (1220 MM).
  
 8) SHEET # 2 INDICATES ON THE RIGHT ELEVATION WINDOWS
 AND DOORS WITH IN 10'-0" OF THE EXTERIOR STAIR, PLEASE
 PROVIDE COMPLIANCE WITH 2010 FBC-B:
 1026.6 EXTERIOR RAMPS AND STAIRWAY PROTECTION. EXTERIOR
 EXIT RAMPS AND STAIRWAYS SHALL BE SEPARATED FROM THE
 INTERIOR OF THE BUILDING AS REQUIRED IN SECTION 1022.1.
 OPENINGS SHALL BE LIMITED TO THOSE NECESSARY FOR EGRESS
 FROM NORMALLY OCCUPIED SPACES.
 EXCEPTIONS:
 1. SEPARATION FROM THE INTERIOR OF THE BUILDING IS NOT
 REQUIRED FOR OCCUPANCIES, OTHER THAN THOSE IN GROUP R-1
 OR R-2, IN BUILDINGS THAT ARE NO MORE THAN TWO STORIES
 ABOVE GRADE PLANE WHERE THE LEVEL OF EXIT DISCHARGE IS
 THE FIRST STORY ABOVE GRADE PLANE.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2012-10-23 Cont ID  
Sent By rlecky Date 2012-10-23 Time 12:33 Rev Time 0.00
Received By rlecky Date 2012-10-23 Time 12:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2012-10-10 Cont ID  
Sent By rlecky Date 2012-10-10 Time 15:48 Rev Time 0.00
Received By rlecky Date 2012-10-10 Time 14:53 Sent To  
Notes
2012-10-10 15:52:0112060405
 428 10TH STREET
 APARTMENT RENOVATIONS
  
 THE FOLLOWING COMMENT FROM THE PREVIOUS REVIEWS WAS NOT
 ADDRESSED.
  
 SHEET E2
 THE 3/0 SERVICE FEEDERS APPEAR TO BE UNDER SIZED.
 PROVIDE A SUMMARY LOAD CALCULATION FOR THE ELECTRICAL
 SERVICE. INDICATE THE CORRECTED SIZE OF THE MAIN
 SERVICE DISCONNECT AND SERVICE FEEDERS. NEC 215.5,
 220.40
  
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2012-08-14 Cont ID  
Sent By rlecky Date 2012-08-14 Time 16:01 Rev Time 0.00
Received By rlecky Date 2012-08-14 Time 15:16 Sent To  
Notes
2012-08-14 15:59:5812060405
 428 10TH STREET
 APARTMENT RENOVATIONS
  
 THE FOLLOWING COMMENTS WERE NOT ADEQUATELY ADDRESSED.
  
 PROVIDE A SUMMARY LOAD CALCULATION FOR THE ELECTRICAL
 SERVICE. NEC 215.5, 220.40
  
 MAXIMUM NUMBER OF DISCONNECTS FOR THE ELECTRICAL
 SERVICE IS LIMITED TO SIX GROUPED IN ONE LOCATION. A
 BUILDING SHALL BE SUPPLIED BY ONLY ONE SERVICE. NEC
 230.70, 230.2
  
 INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE
 NEW SERVICE, SWITCH GEAR AND ELECTRIC PANELS. NEC
 110.9, 110.10
  
 ADD RECEPTACLES SO THAT AT NO POINT ALONG THE FLOOR IN
 ANY WALL IS MORE THAN 6 FEET FROM A RECEPTACLE OUTLET
 AND AT WALL SPACES 2 FEET OR MORE IN WIDTH. NEC 210.52
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-06-15 Cont ID  
Sent By rlecky Date 2012-06-15 Time 11:43 Rev Time 0.00
Received By rlecky Date 2012-06-15 Time 10:12 Sent To  
Notes
2012-06-15 11:46:0212060405
 428 10TH STREET
 APARTMENT RENOVATIONS
  
 PROVIDE A LOAD CALCULATION FOR THE ELECTRICAL SERVICE.
 NEC 215.5, 220.40
 MAXIMUM NUMBER OF DISCONNECTS FOR THE ELECTRICAL
 SERVICE IS LIMITED TO SIX SWITCHES GROUPED IN ONE
 LOCATION. NEC 230.70
 INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE
 NEW SERVICE, SWITCH GEAR AND ELECTRIC PANELS. NEC
 110.9, 110.10
 SHOW LOCATION OF ALL ELECTRICAL PANELBOARDS. NEC 110.26
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT
 ALREADY EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE
 HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE
 A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET
 OF EACH ROOM USED FOR SLEEPING. 2007 FBC R313
 GFCI PROTECTED OUTLETS UNIT ARE REQUIRED FOR EACH
 DWELLING AT GRADE LEVEL AND ON BALCONIES. NEC 210.52(E)
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2012-10-11 Cont ID  
Sent By wjolin Date 2012-10-11 Time 11:28 Rev Time 0.00
Received By wjolin Date 2012-10-11 Time 10:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2012-08-25 Cont ID  
Sent By wjolin Date 2012-08-25 Time 19:14 Rev Time 0.00
Received By wjolin Date 2012-08-13 Time 09:05 Sent To  
Notes
2012-08-25 19:03:32428 10TH STREET
 PERMIT #12060308
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE LAST FIRE INSPECTION ON RECORD FOR THIS LOCATION
 WAS IN 2002 FOR A ROOMING HOUSE. A RECENT AUGUST
 INSPECTION CONFIRMED AN EXISTING ROOMING HOUSE
 OCCUPANCY . DURING INSPECTION IT WAS OBSERVED THAT THE
 BUILDING HAS BEEN SEVERLY DAMAGED BY VANDALS, WATER AND
 POSSIBLY TERMITES.
  
 WHEN AN OCCUPANCY CHANGES FROM AN EXISTING ROOM HOUSE
 TO NEW APARTMENTS, THE APARTMENT BUILDING IS REQUIRED
 TO BE PROTECTED BY AN AUTOMATIC SUPERVISED FIRE
 SPRINKLER SYSTEM.
  
 UPGRADING AND REPAIRING THE STAIRS NEEDS TO BE ADDED TO
 PERMIT APPLICATION SCOPE OF WORK. GUARDS, AT LEAST
 42-INCHES TALL, SHALL BE PROVIDED AT THE OPEN SIDES OF
 MEANS OF EGRESS (STAIRS, MEZZANINE, ETC.) THAT EXCEED
 30-INCHES ABOVE THE FLOOR. OPEN GUARDS SHALL PROHIBIT
 THE PASSAGE OF A 4-INCH DIAMETER SPHERE UP TO A HEIGHT
 OF 34-INCHES. THE TRIANGULAR OPENINGS FORMED BY THE
 RISER, TREAD AND BOTTOM ELEMENT OF THE GUARDRAIL SHALL
 PROHIBIT THE PASSAGE OF A 6-INCH DIAMETER SPHERE.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-06-15 Cont ID  
Sent By wjolin Date 2012-06-15 Time 13:15 Rev Time 0.00
Received By wjolin Date 2012-06-15 Time 12:07 Sent To  
Notes
2012-06-15 13:15:55428 10TH STREET
 PERMIT #12060308
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NOTE: UPSTAIRS UNIT #5 AND UNIT #6 ARE INDICATED AS
 "EXISTING" ON THE PLANS WHILE UNIT #1-#4 ARE NOT
 INDICATED AS EXISTING AND THEREFORE WILL BE TREATED AS
 "NEW."
  
 NEW APARTMENTS ARE REQUIRED TO BE PROTECTED BY AN
 AUTOMATIC SUPERVISED FIRE SPRINKLER SYSTEM.
  
 PROVIDE A DETAIL FOR THE NEW FIRE-RATED WALLS.
  
 PROVIDE AN EXISTING FLOOR PLAN OR A DEMOLITION DRAWING
 TO SHOW CURRENT CONDITIONS.
  
 DESIGN SHALL CONFORM TO THE 2010 EDITION OF THE FLORIDA
 FIRE PREVENTION CODE WHICH CONTAINS THE 2009 EDITION OF
 BOTH NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS.
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING
 SHALL BE PROHIBITED. ALL DEMOLITION OR CONSTRUCTION
 AREAS SHALL HAVE "NO SMOKING" SIGNS POSTED.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS
 CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO
 THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS
 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED
 REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTER R/F/RF
 DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA
 ADMINISTRATIVE CODE 69A-60.0081.
  
 GUARDS, AT LEAST 42-INCHES TALL, SHALL BE PROVIDED AT
 THE OPEN SIDES OF MEANS OF EGRESS (STAIRS, MEZZANINE,
 ETC.) THAT EXCEED 30-INCHES ABOVE THE FLOOR. OPEN
 GUARDS SHALL PROHIBIT THE PASSAGE OF A 4-INCH DIAMETER
 SPHERE UP TO A HEIGHT OF 34-INCHES. THE TRIANGULAR
 OPENINGS FORMED BY THE RISER, TREAD AND BOTTOM ELEMENT
 OF THE GUARDRAIL SHALL PROHIBIT THE PASSAGE OF A 6-INCH
 DIAMETER SPHERE.
  
 FOR APARTMENTS WITH FOSSIL FUEL BURNING APPLIANCES, A
 CARBON MONOXIDE ALARM SHALL BE INSTALLED WITHIN 10 FEET
 OF EACH ROOM USED FOR SLEEPING PURPOSES. INDICATE THE
 POWER SOURCE FOR THE SMOKE AND CARBON MONOXIDE ALARMS.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2012-10-23 Cont ID  
Sent By rlecky Date 2012-10-23 Time 12:39 Rev Time 0.00
Received By rlecky Date 2012-10-18 Time 08:34 Sent To  
Notes
2012-10-19 08:53:45SENT TO ELECTRICAL BOX.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-10-14 Cont ID  
Sent By jwitmer Date 2012-10-14 Time 11:30 Rev Time 0.00
Received By jwitmer Date 2012-10-09 Time 17:11 Sent To  
Notes
2012-10-09 17:01:56SENT TO B8 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-09-25 Cont ID  
Sent By lmartine Date 2012-09-05 Time 10:36 Rev Time 0.00
Received By lmartine Date 2012-08-03 Time 09:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-07-09 Cont ID  
Sent By hmoser Date 2012-07-09 Time 12:33 Rev Time 0.00
Received By hmoser Date 2012-06-12 Time 15:12 Sent To  
Notes
2012-06-12 15:22:18B 19

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2012-08-23 Cont ID  
Sent By hmoser Date 2012-08-21 Time 14:14 Rev Time 0.00
Received By hmoser Date 2012-08-21 Time 14:00 Sent To  
Notes
2012-08-23 13:18:078/13 /12 PERMIT NOT REQUIRED WINDOW UNITS. HM.
2012-08-21 14:14:10NO PLANS SUBMITTED WITH PACKAGE.
 CALLED CONTRACTOR PHONE NOT IN SERVICE.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-07-09 Cont ID  
Sent By hmoser Date 2012-07-09 Time 12:33 Rev Time 0.00
Received By hmoser Date 2012-07-09 Time 12:24 Sent To  
Notes
2012-07-09 12:33:44NO MECHANICAL PLANS SUBMITTED.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2012-10-12 Cont ID  
Sent By lwagner Date 2012-10-12 Time 15:21 Rev Time 0.00
Received By lwagner Date 2012-10-12 Time 15:15 Sent To  
Notes
2012-10-09 17:05:29NEED RE-STAMP PLANS. JG.

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-08-10 Cont ID  
Sent By lwagner Date 2012-08-10 Time 12:35 Rev Time 0.00
Received By lwagner Date 2012-08-10 Time 11:24 Sent To  
Notes
2012-08-10 12:36:10RE-STAMP

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-06-18 Cont ID  
Sent By lwagner Date 2012-06-18 Time 14:14 Rev Time 0.00
Received By lwagner Date 2012-06-18 Time 14:14 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2012-09-04 Cont ID  
Sent By aaponte Date 2012-09-04 Time 16:06 Rev Time 0.00
Received By aaponte Date 2012-09-04 Time 16:06 Sent To  
Notes
2012-09-04 16:07:29PROVISO:
 EXISTING GRAVEL INCLUDED IN PERMIT ON FRONT YARD SHALL
 BE REPLACED WITH GRASS.

Review Stop Z ZONING
Rev No 1 Status P Date 2012-06-26 Cont ID  
Sent By aaponte Date 2012-06-26 Time 09:27 Rev Time 0.00
Received By aaponte Date 2012-06-26 Time 09:26 Sent To  
Notes
2012-06-26 09:29:05PROVISO: EXISTING GRAVEL SHALL BE REPLACED BY GRASS,
 GROUND COVER OR OTHER SUITABLE PLANT MATERIAL.


Account Summary | Usage Policy | Privacy Policy