Plan Review Details - Permit 12060228
Plan Review Stops For Permit 12060228
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2012-06-14 Cont ID  
Sent By jwitmer Date 2012-06-14 Time 16:47 Rev Time 0.00
Received By jwitmer Date 2012-06-14 Time 16:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-07-02 Cont ID  
Sent By jleahy Date 2012-07-02 Time 08:37 Rev Time 0.00
Received By jleahy Date 2012-07-02 Time 08:37 Sent To  
Notes
2012-07-02 08:39:53GAVE TO LM 7/2/12 JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-06-14 Cont ID  
Sent By wjolin Date 2012-06-14 Time 14:58 Rev Time 0.00
Received By wjolin Date 2012-06-14 Time 13:55 Sent To  
Notes
2012-06-14 14:58:19401 SOUTH DIXIE HIGHWAY
 PERMIT #12060228
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE ADDRESS 401 S DIXIE HWY NEEDS TO BE UPDATED TO
 REFLECT THE ADDRESS CHANGE TO 400 FERN STREET.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-07-09 Cont ID  
Sent By hmoser Date 2012-07-09 Time 10:29 Rev Time 0.00
Received By hmoser Date 2012-07-03 Time 17:15 Sent To  
Notes
2012-07-03 17:16:49TO MECHANICAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-07-03 Cont ID  
Sent By rlecky Date 2012-07-02 Time 17:30 Rev Time 0.00
Received By rlecky Date 2012-06-15 Time 09:44 Sent To  
Notes
2012-06-22 09:45:52IN MECHANICAL BOX, NEEDS ELECTRIC NEXT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-06-14 Cont ID  
Sent By jwitmer Date 2012-06-14 Time 16:47 Rev Time 0.00
Received By jwitmer Date 2012-06-08 Time 16:39 Sent To  
Notes
2012-06-08 16:40:02B-14

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-07-09 Cont ID  
Sent By hmoser Date 2012-07-09 Time 10:29 Rev Time 0.00
Received By hmoser Date 2012-07-09 Time 09:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-06-26 Cont ID  
Sent By hmoser Date 2012-06-26 Time 13:28 Rev Time 0.00
Received By hmoser Date 2012-06-26 Time 12:57 Sent To E
Notes
2012-06-26 13:28:12PLANS DENIED
 REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROL'S.
 2010 FLORIDA ENERGY CODE.
 PROVIDE HEATING AND COOLING LOAD CALCULATIONS .
 PER SECTION 503.2.1 2010 FLORIDA ENERGY CODE.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-06-22 Cont ID  
Sent By lwagner Date 2012-06-22 Time 09:21 Rev Time 0.00
Received By lwagner Date 2012-06-22 Time 09:21 Sent To M
Notes
***NONE***