Plan Review Details - Permit 12060220
Plan Review Stops For Permit 12060220
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-08-13 Cont ID  
Sent By shill Date 2012-08-13 Time 15:29 Rev Time 0.00
Received By shill Date 2012-08-13 Time 15:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-07-14 Cont ID  
Sent By shill Date 2012-07-14 Time 10:42 Rev Time 0.00
Received By shill Date 2012-07-14 Time 10:42 Sent To  
Notes
2012-07-14 10:47:27****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. AS THE RENOVATION COST IS OVER 30% OF THE VALUE OF
 THE STRUCTURE (PER PAPA), PLEASE SEE FBC 2010 ENERGY
 CONSERVATION, TABLE 101.4.1, BUILDING ENVELOPE
 COMPONENTS ARE TO COMPLY WITH SECTION 502, FBC ENERGY
 CONSERVATION. IF AN APPRAISAL WITH A DIFFERENT VALUE IS
 AVAILABLE, PLEASE PROVIDE.
  
 2. FBC 1403.7, CLEARANCE BETWEEN EXTERIOR WALL
 COVERINGS AND FINAL EARTH GRADE SHALL NOT BE LESS THAN
 6". REVISE DETAIL TO SHOW COMPLIANCE.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-08-13 Cont ID  
Sent By shill Date 2012-08-13 Time 15:28 Rev Time 0.00
Received By shill Date 2012-07-24 Time 11:11 Sent To  
Notes
2012-07-24 11:11:48INCOMING SENT TO ZONING BOX .JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-07-14 Cont ID  
Sent By shill Date 2012-07-14 Time 10:47 Rev Time 0.00
Received By shill Date 2012-06-08 Time 16:56 Sent To  
Notes
2012-06-08 16:56:38IN ZONING BOX

Review Stop Z ZONING
Rev No 2 Status P Date 2012-08-02 Cont ID  
Sent By lfranco Date 2012-08-02 Time 20:03 Rev Time 0.00
Received By lfranco Date 2012-07-24 Time 16:33 Sent To  
Notes
2012-08-02 20:02:08THE SCOPE OF WORK HAS BEEN REDUCED TO LESS THAN THE 50%
 OF THE VALUE OF THE BUILDING, BASED ON THE ASSESSED
 VALUE OF THE BUILDING AS ESTABLISHED BY THE COUNTY
 PROPERTY APPRAISER'S OFFICE, A REVIEW FROM THE BUILDING
 DEPARTMENT WILL NEED TO BE CONFIRMED OF THE REDUCED
 SCOPE OF WORK TO VERIFY THE REDUCED VALUE OF THE PERMIT
 WORK.
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2012-07-12 Cont ID  
Sent By lfranco Date 2012-07-12 Time 15:40 Rev Time 0.00
Received By lfranco Date 2012-06-12 Time 14:33 Sent To  
Notes
2012-07-12 15:51:48PLANNING: **** FAILED ***
  
 1. RESPOND TO COMMENTS IN WRITING AND SUBMIT AS PART OF
 RESUBMITTAL PACKET. THE SUBMITTAL OF THE REQUESTED
 INFORMATION MAY GENERATE ADDITIONAL COMMENTS.
  
 2. THE ELEVATIONS SHOW EXISTING ELEVATIONS OF VARIOUS
 SIDE OF THE BUILDING, HOWEVER, THE PROPOSED SEEMS TO
 ONLY BE FOR THE FRONT FACADE? IS THAT CORRECT? OR IS
 THE REPLACEMENT OF THE WINDOWS THROUGHOUT.
  
 3. THIS PROPERTY IS WITHIN THE NORTHWOOD MIXED USE
 DISTRICT ("NMUD") BUILDING TYPE III, PURSUANT TO
 SECTION 94-213(D)5, THE RENOVATION/ALTERATION EXCEEDS
 THE 50% OF THE VALUE OF THE BUILDING, BASED ON THE
 ASSESSED VALUE OF THE BUILDING AS EXTABLISHED BY THE
 COUNTY PROPERTY APPRAISER'S OFFICE, THEREFORE THE
 REQUIRED STOREFRONT GLAZING IS AS FOLLOWS:
  
  
 EACH STOREFRONT SHALL HAVE CLEAR GLAZED AREAS EQUAL TO
 A MINIMUM OF 70 PERCENT OF ITS FA?ADE, MEASURED BETWEEN
 TWO (2) AND EIGHT (8) FEET FROM THE GROUND AND MUST BE
 EQUALLY DISPERSED THROUGHOUT ALL FRONTAGES.
  
 KEEP IN MIND THAT NO REDUCTION OF GLAZING WILL BE
 ALLOWED. SEE BELOW.
  
 B. RENOVATIONS OR ALTERATIONS OR ADDITIONS (NOT ON THE
 FRONTAGE LINE) TO EXISTING BUILDINGS SHALL NOT REDUCE
 THE ORIGINAL PERCENTAGE OF CLEAR GLAZED AREAS, IF IT IS
 MORE THAN 50 PERCENT OF ITS FACADE, MEASURED BETWEEN
 TWO AND EIGHT FEET FROM THE GROUND. HOWEVER, THE
 STRUCTURE MUST COMPLY WITH SUBSECTION (5)(A) IF THE
 COST OF RENOVATION OR ALTERATION MEETS OR EXCEEDS 50
 PERCENT OF THE VALUE OF THE BUILDING PRIOR TO THE
 COMMENCEMENT OF RENOVATION OR ALTERNATION, BASED ON THE
 ASSESSED VALUE OF THE BUILDING AS ESTABLISHED BY THE
 COUNTY PROPERTY APPRAISER'S OFFICE
  
 PROVIDE ALL DIMENSIONS ON THE ELEVATIONS WHEN
 RESUBMITTING.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO, AICP
 SENIOR PLANNER
 PLANNING DIVISION
 TEL: (561) 822-1443
 EMAIL: [email protected]
  
2012-06-12 14:33:35GIVEN TO LF