| 2012-07-06 08:20:53 | BUILDING PLAN REVIEW |
| | PERMIT: 12060211/ 11110602 |
| | ADD: 1601 FORUM PL # 805 |
| | CONT: ANDERSON MOORE |
| | TEL: (561)662-1819 |
| | |
| | 2007 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) THE REVISION SHEET A-5 PLUMBING FIXTURES INDICATES |
| | IT IS DESIGNED TO THE 2010 FBC. THE 2010 FBC WAS |
| | ADOPTED STATEWIDE ON MARCH 15/ 2012, BUT THIS IS A |
| | PERMIT THAT WAS APPLIED FOR BEFORE THAT DATE KEEPING |
| | THE ASSOCIATED REVISIONS ALSO IN THE 2007 FBC. |
| | |
| | 2) COMPLIED. 28 OCCUPANTS. |
| | |
| | 3) COMPLIED. 28 OCCUPANTS. |
| | |
| | 4) THIS REVISION IS TO BE REVIEWED UNDER THE 2007 FBC |
| | CHAPTER 11 ACCESSIBILITY CODE. SECTION 11-4.1.3(11) IF |
| | TOILET ROOMS ARE PROVIDED, THEN EACH PUBLIC AND COMMON |
| | USE TOILET ROOMS SHALL COMPLY WITH SECTION 11-4.22( |
| | TOLIET ROOMS). OTHER TOILET ROOMS PROVIDED FOR THE USE |
| | OF OCCUPANTS OF SPECIFIC SPACES (I.E., A PRIVATE TOILET |
| | ROOM FOR THE OCCUPANT OF A PRIVATE OFFICE) SHALL BE |
| | ADAPTABLE. |
| | 1-4.22.2 DOORS. |
| | |
| | 11-4.22.2 (1) ALL DOORS TO ACCESSIBLE TOILET ROOMS |
| | SHALL COMPLY WITH SECTION 11-4.13. DOORS SHALL NOT |
| | SWING INTO THE CLEAR FLOOR SPACE REQUIRED FOR ANY |
| | FIXTURE. |
| | |
| | 11-4.22.3 CLEAR FLOOR SPACE. THE ACCESSIBLE FIXTURES |
| | AND CONTROLS REQUIRED IN SECTIONS 11-4.22.4, 11-4.22.5, |
| | 11-4.22.6 AND 11-4.22.7 SHALL BE ON AN ACCESSIBLE |
| | ROUTE. AN UNOBSTRUCTED TURNING SPACE COMPLYING WITH |
| | SECTION 11-4.2.3 SHALL BE PROVIDED WITHIN AN ACCESSIBLE |
| | TOILET ROOM. THE CLEAR FLOOR SPACE AT FIXTURES AND |
| | CONTROLS, THE ACCESSIBLE ROUTE, AND THE TURNING SPACE |
| | MAY OVERLAP. |
| | |
| | 11-4.22.4 WATER CLOSETS. IF TOILET STALLS ARE PROVIDED, |
| | THEN AT LEAST ONE SHALL BE A STANDARD TOILET STALL |
| | COMPLYING WITH SECTION 11-4.17; WHERE SIX OR MORE |
| | STALLS ARE PROVIDED, IN ADDITION TO THE STALL COMPLYING |
| | WITH SECTION 11-4.17.3, AT LEAST ONE STALL 36 INCHES |
| | (915 MM) WIDE WITH AN OUTWARD SWINGING, SELF-CLOSING |
| | DOOR AND PARALLEL GRAB BARS COMPLYING WITH FIGURE 30(D) |
| | AND SECTION 11-4.26 SHALL BE PROVIDED. WATER CLOSETS IN |
| | SUCH STALLS SHALL COMPLY WITH SECTION 11-4.16. IF WATER |
| | CLOSETS ARE NOT IN STALLS, THEN AT LEAST ONE SHALL |
| | COMPLY WITH SECTION 11-4.16. |
| | |
| | 11-4.22.5 URINALS. IF URINALS ARE PROVIDED, THEN AT |
| | LEAST ONE SHALL COMPLY WITH SECTION 11-4.18. |
| | |
| | 11-4.22.6 LAVATORIES AND MIRRORS. IF LAVATORIES AND |
| | MIRRORS ARE PROVIDED, THEN AT LEAST ONE OF EACH SHALL |
| | COMPLY WITH SECTION 11-4.19. |
| | |
| | 11-4.22.7 CONTROLS AND DISPENSERS. IF CONTROLS, |
| | DISPENSERS, RECEPTACLES, OR OTHER EQUIPMENT ARE |
| | PROVIDED, THEN AT LEAST ONE OF EACH SHALL BE ON AN |
| | ACCESSIBLE ROUTE AND SHALL COMPLY WITH SECTION 11-4.27. |
| | |
| | 5) INFORMATIONAL ONLY. 2007 VS 2010 INTHE 2010 FBC |
| | ACCESSIBILITY THE MINIMUM NUMBER OF DRINKING FOUNTAINS |
| | IS (2) 602.4 FOR WHEELCHAIR BOUND AND 602.7 DRINKING |
| | FOUNTAINS FOR STANDING PERSONS. |
| | |
| | 6) COMPLIED. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |