Plan Review Details - Permit 12060211
Plan Review Stops For Permit 12060211
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-07-19 Cont ID  
Sent By jwitmer Date 2012-07-19 Time 07:10 Rev Time 0.00
Received By jwitmer Date 2012-07-19 Time 07:10 Sent To  
Notes
2012-07-19 07:54:28BUILDING PROVISO:
 REVISION DATED 7/11/12 SHEET A-1 IN THE CONFERANCE ROOM
 NEW SECOND EGRESS DOOR ADDED (DOOR A) AND RATED WALLS,
 MISSING SHEET A-3 RATING OF DOOR "A":
 PROVISO: PER 207 FBC-B TABLE 715.4 THIS DOOR REQUIES A
 20 MINUTE RATING.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-07-06 Cont ID  
Sent By jwitmer Date 2012-07-06 Time 08:08 Rev Time 0.00
Received By jwitmer Date 2012-07-06 Time 08:08 Sent To  
Notes
2012-07-06 08:20:53BUILDING PLAN REVIEW
 PERMIT: 12060211/ 11110602
 ADD: 1601 FORUM PL # 805
 CONT: ANDERSON MOORE
 TEL: (561)662-1819
  
 2007 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE REVISION SHEET A-5 PLUMBING FIXTURES INDICATES
 IT IS DESIGNED TO THE 2010 FBC. THE 2010 FBC WAS
 ADOPTED STATEWIDE ON MARCH 15/ 2012, BUT THIS IS A
 PERMIT THAT WAS APPLIED FOR BEFORE THAT DATE KEEPING
 THE ASSOCIATED REVISIONS ALSO IN THE 2007 FBC.
  
 2) COMPLIED. 28 OCCUPANTS.
  
 3) COMPLIED. 28 OCCUPANTS.
  
 4) THIS REVISION IS TO BE REVIEWED UNDER THE 2007 FBC
 CHAPTER 11 ACCESSIBILITY CODE. SECTION 11-4.1.3(11) IF
 TOILET ROOMS ARE PROVIDED, THEN EACH PUBLIC AND COMMON
 USE TOILET ROOMS SHALL COMPLY WITH SECTION 11-4.22(
 TOLIET ROOMS). OTHER TOILET ROOMS PROVIDED FOR THE USE
 OF OCCUPANTS OF SPECIFIC SPACES (I.E., A PRIVATE TOILET
 ROOM FOR THE OCCUPANT OF A PRIVATE OFFICE) SHALL BE
 ADAPTABLE.
 1-4.22.2 DOORS.
  
 11-4.22.2 (1) ALL DOORS TO ACCESSIBLE TOILET ROOMS
 SHALL COMPLY WITH SECTION 11-4.13. DOORS SHALL NOT
 SWING INTO THE CLEAR FLOOR SPACE REQUIRED FOR ANY
 FIXTURE.
  
 11-4.22.3 CLEAR FLOOR SPACE. THE ACCESSIBLE FIXTURES
 AND CONTROLS REQUIRED IN SECTIONS 11-4.22.4, 11-4.22.5,
 11-4.22.6 AND 11-4.22.7 SHALL BE ON AN ACCESSIBLE
 ROUTE. AN UNOBSTRUCTED TURNING SPACE COMPLYING WITH
 SECTION 11-4.2.3 SHALL BE PROVIDED WITHIN AN ACCESSIBLE
 TOILET ROOM. THE CLEAR FLOOR SPACE AT FIXTURES AND
 CONTROLS, THE ACCESSIBLE ROUTE, AND THE TURNING SPACE
 MAY OVERLAP.
  
 11-4.22.4 WATER CLOSETS. IF TOILET STALLS ARE PROVIDED,
 THEN AT LEAST ONE SHALL BE A STANDARD TOILET STALL
 COMPLYING WITH SECTION 11-4.17; WHERE SIX OR MORE
 STALLS ARE PROVIDED, IN ADDITION TO THE STALL COMPLYING
 WITH SECTION 11-4.17.3, AT LEAST ONE STALL 36 INCHES
 (915 MM) WIDE WITH AN OUTWARD SWINGING, SELF-CLOSING
 DOOR AND PARALLEL GRAB BARS COMPLYING WITH FIGURE 30(D)
 AND SECTION 11-4.26 SHALL BE PROVIDED. WATER CLOSETS IN
 SUCH STALLS SHALL COMPLY WITH SECTION 11-4.16. IF WATER
 CLOSETS ARE NOT IN STALLS, THEN AT LEAST ONE SHALL
 COMPLY WITH SECTION 11-4.16.
  
 11-4.22.5 URINALS. IF URINALS ARE PROVIDED, THEN AT
 LEAST ONE SHALL COMPLY WITH SECTION 11-4.18.
  
 11-4.22.6 LAVATORIES AND MIRRORS. IF LAVATORIES AND
 MIRRORS ARE PROVIDED, THEN AT LEAST ONE OF EACH SHALL
 COMPLY WITH SECTION 11-4.19.
  
 11-4.22.7 CONTROLS AND DISPENSERS. IF CONTROLS,
 DISPENSERS, RECEPTACLES, OR OTHER EQUIPMENT ARE
 PROVIDED, THEN AT LEAST ONE OF EACH SHALL BE ON AN
 ACCESSIBLE ROUTE AND SHALL COMPLY WITH SECTION 11-4.27.
  
 5) INFORMATIONAL ONLY. 2007 VS 2010 INTHE 2010 FBC
 ACCESSIBILITY THE MINIMUM NUMBER OF DRINKING FOUNTAINS
 IS (2) 602.4 FOR WHEELCHAIR BOUND AND 602.7 DRINKING
 FOUNTAINS FOR STANDING PERSONS.
  
 6) COMPLIED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-06-14 Cont ID  
Sent By jwitmer Date 2012-06-14 Time 14:09 Rev Time 0.00
Received By jwitmer Date 2012-06-14 Time 13:09 Sent To  
Notes
2012-06-14 14:23:08BUILDING PLAN REVIEW
 PERMIT: 12060211/ 11110602
 ADD: 1601 FORUM PL # 805
 CONT: ANDERSON MOORE
 TEL: (561)662-1819
  
 2007 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE REVISION THAT WAS SUBMITTED INDICATES IT IS
 DESIGNED TO THE 2010 FBC. THE 2010 FBC WAS ADOPTED
 STATEWIDE ON MARCH 15/ 2012, BUT THIS IS A PERMIT THAT
 WAS ISSUED BEFORE THAT DATE KEEPING THE ASSOCIATED
 REVISIONS ALSO IN THE 2007 FBC.
  
 2) THE CONFERENCE ROOM IS OVER 750 SQ FT, MAKING IT A
 ACCESORY OCCUPANCY (ASSEMBLY A-3) THIS WILL REQUIRE A
 RATED CORRIDOR SEE 2007 FBC-BTABLE 1017.1.
  
 3) WITH THE OCCUPANT LOAD OF THE CONFERENCE ROOM OVER
 50 WHEN FIGURED AT 15 SQ FT PER OCCUPANT 2007 FBC-B
 TABLE 1019.2 WOULD REQUIRE 2 DOORS.
  
 4) 2007 VS 2010 FBC IN THE 2010 FBC- ACCESSIBILITY THE
 PRIVATE OFFICES CAN ONLY OCCUR WHEN GOING THROUGH A
 PRIVATE OFFICE, ACCESSIBILTY 604.4 EXCEPTION# 1.
 WITHIN THE 2007 CODE THE LANGUAGE IS NOT AS STRICT HOW,
 OR WHO WILL BE USING THESE RESTROOMS AS PRIVATE
 RESTROOMS 11-4.1.3(11).
  
 5) 2007 VS 2010 INTHE 2010 FBC ACCESSIBILITY THE
 MINIMUM NUMBER OF DRINKING FOUNTAINS IS (2) 602.4 FOR
 WHEELCHAIR BOUND AND 602.7 DRINKING FOUNTAINS FOR
 STANDING PERSONS.
  
 6) PLEASE PROVIDE COMPLIANCE WITH 2007 FBC-B 11-4.31,
 TELEPHONES.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-07-19 Cont ID  
Sent By rlecky Date 2012-07-19 Time 09:24 Rev Time 0.00
Received By rlecky Date 2012-07-19 Time 09:17 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-06-13 Cont ID  
Sent By rlecky Date 2012-06-13 Time 16:45 Rev Time 0.00
Received By rlecky Date 2012-06-13 Time 16:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2012-07-19 Cont ID  
Sent By wjolin Date 2012-07-19 Time 10:49 Rev Time 0.00
Received By wjolin Date 2012-07-19 Time 10:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2012-07-06 Cont ID  
Sent By wjolin Date 2012-07-06 Time 12:17 Rev Time 0.00
Received By wjolin Date 2012-07-06 Time 12:12 Sent To  
Notes
2012-07-06 12:17:221601 FORUM PLACE - SUITE #805
 TRACKING #12060211
 MASTER #11110602
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT: THE CONFERENCE ROOM (ASSEMBLY USE)
 APPEARS TO BE APPROXIMATELY 800 SQ.FT. WHICH EQUATES TO
 AN OCCUPANT LOAD OF 54 PERSONS BASED UPON 15 SQ.FT. PER
 PERSON. THIS WOULD RESULT IN AN ASSEMBLY OCCUPANCY AND
 NOT A BUSINESS OCCUPANCY WHEREBY THE LIFE SAFETY DESIGN
 WOULD NEED TO MODIFIED TO ACCOMPANY THIS OCCUPANCY
 TYPE.
  
 POSTING A MAXIMUM OCCUPANT LOAD SIGN WILL NOT SOLVE
 THIS ISSUE AND WOULD BE VERY DIFFICULT TO
 MONITOR/ENFORCE. THIS ROOM MAY BE USED BY ANOTHER
 TENANT LONG AFTER THE CURRENT TENANT HAS VACATED.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-06-12 Cont ID  
Sent By wjolin Date 2012-06-12 Time 09:29 Rev Time 0.00
Received By wjolin Date 2012-06-12 Time 08:58 Sent To  
Notes
2012-06-12 09:24:561601 FORUM PLACE - SUITE #805
 TRACKING #12060211
 MASTER #11110602
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE CONFERENCE ROOM (ASSEMBLY USE) APPEARS TO BE
 APPROXIMATELY 800 SQ.FT. WHICH EQUATES TO AN OCCUPANT
 LOAD OF 54 PERSONS BASED UPON 15 SQ.FT. PER PERSON.
 THIS WOULD RESULT IN AN ASSEMBLY OCCUPANCY AND NOT A
 BUSINESS OCCUPANCY WHEREBY THE LIFE SAFETY DESIGN WOULD
 NEED TO MODIFIED TO ACCOMPANY THIS OCCUPANCY TYPE.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-07-06 Cont ID  
Sent By wjolin Date 2012-07-06 Time 12:17 Rev Time 0.00
Received By wjolin Date 2012-07-02 Time 17:05 Sent To  
Notes
2012-07-05 17:05:57GAVE TO JIM ON 7/5
 EXPEDITED

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-06-26 Cont ID  
Sent By hmoser Date 2012-06-26 Time 10:59 Rev Time 0.00
Received By hmoser Date 2012-06-08 Time 15:45 Sent To  
Notes
2012-06-08 15:55:22EXPEDITED
 B--9
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-06-26 Cont ID  
Sent By hmoser Date 2012-06-26 Time 10:47 Rev Time 0.00
Received By hmoser Date 2012-06-25 Time 16:14 Sent To  
Notes
2012-06-26 10:55:59PROVISO
 REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-06-18 Cont ID  
Sent By lwagner Date 2012-06-18 Time 10:33 Rev Time 0.00
Received By lwagner Date 2012-06-18 Time 10:11 Sent To  
Notes
2012-06-18 10:27:55PLEASE SEE BUILDING REVIEW NOTES CONCERNING THE PRIVATE
 RESTROOMS. PLUMBING IS OK.