Plan Review Details - Permit 12060193
Plan Review Stops For Permit 12060193
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-06-09 Cont ID  
Sent By wjolin Date 2012-06-09 Time 20:39 Rev Time 0.00
Received By wjolin Date 2012-06-09 Time 20:26 Sent To M
Notes
2012-06-09 20:34:03303 BANYAN BOULEVARD - 3RD FLOOR LOBBY
 PERMIT #12060193
 MASTER #12050115
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO- SUBMIT REVISION BEFORE FINAL FIRE
 INSPECTION*****
  
 SPRINKLERS LOCATED IN THE 10'-6" CEILING HAVE THEIR
 SPRAY OBSTRUCTED BY THE 9'-6" SOFFIT. PROVIDE
 ADDITIONAL SPRINKLERS IN SOFFIT AREA OR RELOCATE
 CEILING SPRINKLERS TO SOFFIT.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-06-13 Cont ID  
Sent By hmoser Date 2012-06-13 Time 09:41 Rev Time 0.00
Received By hmoser Date 2012-06-08 Time 09:00 Sent To  
Notes
2012-06-08 09:01:47TO FIRE
 TRAVELING W/12060192

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-06-13 Cont ID  
Sent By hmoser Date 2012-06-13 Time 09:41 Rev Time 0.00
Received By hmoser Date 2012-06-13 Time 09:10 Sent To  
Notes
***NONE***