Plan Review Details - Permit 12060134
Plan Review Stops For Permit 12060134
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-12-10 Cont ID  
Sent By jwitmer Date 2012-12-10 Time 08:28 Rev Time 0.00
Received By jwitmer Date 2012-12-10 Time 08:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-07-05 Cont ID  
Sent By jwitmer Date 2012-07-05 Time 16:39 Rev Time 0.00
Received By jwitmer Date 2012-07-05 Time 16:22 Sent To  
Notes
2012-07-05 16:56:02BUILDING PLAN REVIEW
 PERMIT: 12060134
 ADD: 427 SUMMA ST
 CONT: O/B VIGHETTO, EDWARD
 TEL: (561)379-5733
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLEASE PROVIDE HOW MANY IF ANY CHILDREN ARE
 INCAPABLE OF SELF- PRESERVATION? 313.2
 SUB-CLASSIFICATION?
  
 2) 436.10.5 SMOKE DETECTION SYSTEMS.
  
 436.10.5.1 SINGLE-STATION SMOKE ALARMS INSTALLED IN
 ACCORDANCE WITH THE HOUSEHOLD FIRE WARNING EQUIPMENT
 REQUIREMENTS OF CHAPTER 2 OF NFPA 72 SHALL BE INSTALLED
 WITHIN DAY CARE HOMES.
  
 EXCEPTION: SYSTEM SMOKE DETECTORS INSTALLED IN
 ACCORDANCE WITH NFPA 72 AND ARRANGED TO FUNCTION IN THE
 SAME MANNER SHALL BE PERMITTED.
  
 436.10.5.2 NOT APPLICABLE.
  
 436.10.5.3 SINGLE-STATION SMOKE ALARMS SHALL BE POWERED
 BY THE BUILDING ELECTRICAL SYSTEM.
  
 436.10.5.4 SINGLE-STATION SMOKE ALARMS SHALL BE
 PROVIDED IN ALL ROOMS USED FOR SLEEPING.
  
 436.10.5.5 WHERE TWO OR MORE SMOKE ALARMS ARE REQUIRED
 WITHIN A LIVING UNIT, SUITE OF ROOMS, OR SIMILAR AREA,
 THEY SHALL BE ARRANGED SO THAT OPERATION OF ANY SMOKE
 ALARM SHALL CAUSE ALL SMOKE ALARMS WITHIN THE LIVING
 UNIT, SUITE OF ROOMS OR SIMILAR AREA TO SOUND.
  
 436.10.5.5.1 THE ALARMS SHALL SOUND ONLY WITHIN AN
 INDIVIDUAL LIVING UNIT, SUITE OF ROOMS OR SIMILAR AREA
 AND SHALL NOT ACTUATE THE BUILDING FIRE ALARM SYSTEM.
 REMOTE ANNUNCIATION SHALL BE PERMITTED.
  
 3) 1034.6 SPECIAL MEANS OF EGRESS FEATURES. EVERY ROOM
 OR SPACE NORMALLY SUBJECT TO CLIENT OCCUPANCY, OTHER
 THAN BATHROOMS, SHALL HAVE AT LEAST ONE OUTSIDE WINDOW
 FOR EMERGENCY RESCUE AND VENTILATION. SUCH WINDOW SHALL
 BE OPENABLE FROM THE INSIDE WITHOUT THE USE OF TOOLS
 AND SHALL PROVIDE A CLEAR OPENING OF NOT LESS THAN 20
 INCHES (508 MM) IN WIDTH, 24 INCHES (610 MM) IN HEIGHT,
 AND 5.7 SQUARE FEET (0.53 M2) IN AREA. THE BOTTOM OF
 THE OPENING SHALL BE NOT MORE THAN 44 INCHES (1118 MM)
 ABOVE THE FLOOR. THE CLEAR OPENING SHALL PERMIT A
 RECTANGULAR SOLID, WITH A MINIMUM WIDTH AND HEIGHT THAT
 PROVIDES THE REQUIRED 5.7 SQUARE FOOT (0.53 M2) OPENING
 AND A MINIMUM DEPTH OF 20 INCHES (8 MM), TO PASS FULLY
 THROUGH THE OPENING.
  
 4) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
2012-06-08 07:48:296/8 ASSIGNED TO B10
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-12-17 Cont ID  
Sent By rlecky Date 2012-12-17 Time 11:17 Rev Time 0.00
Received By rlecky Date 2012-12-17 Time 10:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-06-11 Cont ID  
Sent By rlecky Date 2012-06-11 Time 09:57 Rev Time 0.00
Received By rlecky Date 2012-06-11 Time 08:25 Sent To  
Notes
2012-06-11 09:57:17FIRE ALARM SYSTEM IS REQUIRED. FBC 436.7
 A SMOKE DETECTION SYSTEM IS REQUIRED. FBC436.7.2
 RECEPTACLES IN BATHROOMS AND KITCHEN AREAS SHALL BE
 GFCI PROTECTED. NEC 210.8
 ALL RECEPTACLES SHALL BE TAMPER RESISTANT. NEC 406.14
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-12-10 Cont ID  
Sent By wjolin Date 2012-12-10 Time 09:05 Rev Time 0.00
Received By wjolin Date 2012-12-10 Time 09:05 Sent To  
Notes
2012-12-10 08:54:27427 SUMMA STREET
 PERMIT #12060134
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 ARTWORK AND TEACHING MATERIALS ATTACHED TO THE WALLS
 SHALL NOT EXCEED 20 PERCENT OF THE INDIVIDUAL WALL
 AREA.
  
 AN EMERGENCY PLAN TO BE DEVELOPED AND POSTED IN
 BUILDING PRIOR TO OCCUPANCY.
  
 EMERGENCY EGRESS DRILLS SHALL BE CONDUCTED MONTHLY. ALL
 DRILLS SHALL BE SOUNDED ON THE FIRE ALARM SYSTEM.
  
 FIRE PREVENTION INSPECTIONS SHALL BE CONDUCTED MONTHLY
 BY A TRAINED SENIOR MEMBER OF THE STAFF, AFTER WHICH A
 COPY OF THE LATEST INSPECTION REPORT SHALL BE POSTED IN
 A CONSPICUOUS PLACE IN THE DAY-CARE FACILITY. IT SHALL
 BE THE DUTY OF THE STAFF TO INSPECT ALL EXITS DAILY TO
 ENSURE THAT ALL DOORS AND EXIT PATHS ARE MAINTAINED
 CLEAR OF OBSTRUCTIONS.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-06-12 Cont ID  
Sent By wjolin Date 2012-06-12 Time 13:32 Rev Time 0.00
Received By wjolin Date 2012-06-12 Time 12:53 Sent To  
Notes
2012-06-12 13:32:15427 SUMMA STREET
 PERMIT #12060134
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SMOKE ALARMS OR SMOKE DETECTORS SHALL BE PROVIDED IN
 ALL ROOMS USED FOR SLEEPING.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 BEDROOMS SHALL HAVE ESCAPE/RESCUE WINDOWS WHEREBY:
 (1) SUCH WINDOWS SHALL BE OPERABLE FROM THE INSIDE
 WITHOUT THE USE OF TOOLS AND SHALL PROVIDE A CLEAR
 OPENING OF NOT LESS THAN 20-INCHES IN WIDTH, 24-INCHES
 IN HEIGHT, AND 5.7 SQ.FT. IN AREA.
 (2) THE BOTTOM OF THE OPENING SHALL BE NOT MORE THAN
 44-INCHES ABOVE THE FLOOR.
 (3) THE CLEAR OPENING SHALL ALLOW A RECTANGULAR SOLID,
 WITH A WIDTH AND HEIGHT THAT PROVIDES NOT LESS THAN THE
 REQUIRED 5.7 SQ.FT. OPENING AND A DEPTH OF NOT LESS
 THAN 20-INCEHS TO PASS FULLY THROUGH THE OPENING.
  
 ARTWORK AND TEACHING MATERIALS ATTACHED TO THE WALLS
 SHALL NOT EXCEED 20 PERCENT OF THE INDIVIDUAL WALL
 AREA.
  
 SPECIAL PROTECTIVE COVERS FOR ALL ELECTRICAL
 RECEPTACLES SHALL BE INSTALLED IN ALL AREAS OCCUPIED BY
 CLIENTS.
  
 AN EMERGENCY PLAN TO BE DEVELOPED AND POSTED IN
 BUILDING PRIOR TO OCCUPANCY.
  
 EMERGENCY EGRESS DRILLS SHALL BE CONDUCTED MONTHLY. ALL
 DRILLS SHALL BE SOUNDED ON THE FIRE ALARM SYSTEM.
  
 FIRE PREVENTION INSPECTIONS SHALL BE CONDUCTED MONTHLY
 BY A TRAINED SENIOR MEMBER OF THE STAFF, AFTER WHICH A
 COPY OF THE LATEST INSPECTION REPORT SHALL BE POSTED IN
 A CONSPICUOUS PLACE IN THE DAY-CARE FACILITY. IT SHALL
 BE THE DUTY OF THE STAFF TO INSPECT ALL EXITS DAILY TO
 ENSURE THAT ALL DOORS AND EXIT PATHS ARE MAINTAINED
 CLEAR OF OBSTRUCTIONS.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-12-17 Cont ID  
Sent By rlecky Date 2012-12-17 Time 11:17 Rev Time 0.00
Received By rlecky Date 2012-12-06 Time 17:20 Sent To  
Notes
2012-12-06 17:24:43B--10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-07-06 Cont ID  
Sent By jwitmer Date 2012-07-06 Time 08:32 Rev Time 0.00
Received By jwitmer Date 2012-06-06 Time 13:50 Sent To  
Notes
2012-06-07 13:51:46SENT TO C11 SHELF FOR REVIEW. (NO ROOM ON B BOARD. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2012-12-18 Cont ID  
Sent By jwitmer Date 2012-12-18 Time 15:05 Rev Time 0.00
Received By jwitmer Date 2012-12-18 Time 15:05 Sent To  
Notes
2012-12-18 15:06:52IMPACT FEES
 RECEIPT # 2012-1219-6
 TOTAL $3,373.40

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2012-12-10 Cont ID  
Sent By jwitmer Date 2012-12-10 Time 08:28 Rev Time 0.00
Received By jwitmer Date 2012-12-10 Time 08:28 Sent To  
Notes
2012-12-10 08:29:04BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2012-07-05 Cont ID  
Sent By jwitmer Date 2012-07-05 Time 16:59 Rev Time 0.00
Received By jwitmer Date 2012-07-05 Time 16:59 Sent To  
Notes
2012-07-05 16:59:19BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-12-10 Cont ID  
Sent By lwagner Date 2012-12-10 Time 14:37 Rev Time 0.00
Received By lwagner Date 2012-12-10 Time 14:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-07-05 Cont ID  
Sent By lwagner Date 2012-07-05 Time 15:08 Rev Time 0.00
Received By lwagner Date 2012-07-05 Time 14:55 Sent To  
Notes
2012-07-05 15:07:45FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 FBC PLUMBING 403.1
 TYPE D OCCUPANCY REQUIRES A SERVICE SINK (A LAUNDRY TUB
 WOULD BE OK) AND DRINKING FOUNTAIN FOR OVER 15
 OCCUPANTS.
  
 FBC ACCESSIBILITY 211.2
 211.2 MINIMUM NUMBER. NO FEWER THAN TWO DRINKING
 FOUNTAINS SHALL BE PROVIDED. ONE DRINKING FOUNTAIN
 SHALL COMPLY WITH 602.1 THROUGH 602.6 AND ONE DRINKING
 FOUNTAIN SHALL COMPLY WITH 602.7.
 EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES
 WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING
 FOUNTAINS.
  

Review Stop Z ZONING
Rev No 1 Status P Date 2012-07-02 Cont ID  
Sent By avann Date 2012-07-02 Time 15:13 Rev Time 0.00
Received By jroach Date 2012-06-22 Time 14:34 Sent To  
Notes
2012-07-02 15:13:41PROVISO
  
 1. NO WORK PROPOSED AS PART OF THIS CHANGE OF
 OCCUPANCY. ALL ITEMS ON THIS PLAN WERE IDENTIFIED AS
 EXISTING BY THE OWNER. ANY FUTURE IMPROVEMENTS THAT ARE
 REQUIRED/PROPOSED SHALL BE SUBJECT TO FURTHER REVIEW.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.
  