Plan Review Details - Permit 12060116
Plan Review Stops For Permit 12060116
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-07-20 Cont ID  
Sent By rlecky Date 2012-07-20 Time 09:33 Rev Time 0.00
Received By rlecky Date 2012-07-20 Time 08:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-06-13 Cont ID  
Sent By rlecky Date 2012-06-13 Time 11:41 Rev Time 0.00
Received By rlecky Date 2012-06-13 Time 10:03 Sent To  
Notes
2012-06-13 11:30:58PROVIDE CONDUCTOR SIZES AND TYPES AND CANDELA
 RATINGSFOR STROBES.
 INDICATE THE LOCATION OF THE FIRE ALARM CONTROL UNIT
 AND POWER SUPPLY.
  
 2010 FBC 907.1.1
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-07-14 Cont ID  
Sent By wjolin Date 2012-07-14 Time 18:08 Rev Time 0.00
Received By wjolin Date 2012-07-14 Time 17:30 Sent To E
Notes
2012-07-14 18:08:345840 CORPORATE WAY - SUITE #200
 PERMIT #12060116
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - SUBMIT REVISION WITH THE FOLLOWING
 INFORMATION*****
  
 THE QUALIFIED SYSTEM DESIGNER SHALL BE IDENTIFIED ON
 THE PLANS.
  
 FOR ADDRESSABLE SYSTEMS, INDICATE THE ADDRESS
 (NUMBER/LETTER) OF EACH FIRE ALARM DEVICE ON THE
 SYSTEM.
  
 INDICATE THE CIRCUIT CLASS.
  
 INDICATE THE CORRECT CANDELA OF THE VISUAL NOTIFICATION
 APPLIANCES. CURRENTLY ALL DEVICES ARE INDICATED AS 15
 CD.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-06-09 Cont ID  
Sent By wjolin Date 2012-06-09 Time 19:05 Rev Time 0.00
Received By wjolin Date 2012-06-09 Time 18:47 Sent To E
Notes
2012-06-09 19:05:045840 CORPORATE WAY - SUITE #200
 PERMIT #12060116
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FIRE ALARM PLANS ARE REQUIRED TO BE SEALED BY A
 PROFESSIONAL ENGINEER WHEN THE FIRE ALARM JOB VALUE
 EXCEEDS $5,000.
  
 FOR IDENTIFICATION PURPOSES, ASSIGN A NUMBERS/LETTERS
 TO EACH FIRE ALARM DEVICE ON THE SYSTEM.
  
 PROVIDE A RISER DIAGRAM AND INDICATE THE WIRE SIZING
 AND CLASS.
  
 PROVIDE A SCALABLE FLOOR PLAN AND INDICATE THE ROOM USE
 OR NAME ON THE PLANS.
  
 INDICATE THE CANDELA OF THE VISUAL NOTIFICATION
 APPLIANCES.
  
 WORK TO BE DONE IN SUITE #100 IS NOT SHOWN ON THE PLANS
 OR INDICATED ON THE PERMIT APPLICATION.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-07-20 Cont ID  
Sent By rlecky Date 2012-07-20 Time 09:34 Rev Time 0.00
Received By rlecky Date 2012-07-12 Time 07:35 Sent To  
Notes
2012-07-13 07:36:17SENT TO FIRE SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-06-13 Cont ID  
Sent By rlecky Date 2012-06-13 Time 11:41 Rev Time 0.00
Received By rlecky Date 2012-06-06 Time 09:03 Sent To  
Notes
2012-06-06 09:04:09TO FIRE