Plan Review Details - Permit 12060116
| Plan Review Stops For Permit 12060116 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2012-07-20 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-07-20 |
Time |
09:33 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-07-20 |
Time |
08:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2012-06-13 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-06-13 |
Time |
11:41 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-06-13 |
Time |
10:03 |
Sent To |
|
|
| Notes |
| 2012-06-13 11:30:58 | PROVIDE CONDUCTOR SIZES AND TYPES AND CANDELA | | | RATINGSFOR STROBES. | | | INDICATE THE LOCATION OF THE FIRE ALARM CONTROL UNIT | | | AND POWER SUPPLY. | | | | | | 2010 FBC 907.1.1 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2012-07-14 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2012-07-14 |
Time |
18:08 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2012-07-14 |
Time |
17:30 |
Sent To |
E |
|
| Notes |
| 2012-07-14 18:08:34 | 5840 CORPORATE WAY - SUITE #200 | | | PERMIT #12060116 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | *****PROVISO - SUBMIT REVISION WITH THE FOLLOWING | | | INFORMATION***** | | | | | | THE QUALIFIED SYSTEM DESIGNER SHALL BE IDENTIFIED ON | | | THE PLANS. | | | | | | FOR ADDRESSABLE SYSTEMS, INDICATE THE ADDRESS | | | (NUMBER/LETTER) OF EACH FIRE ALARM DEVICE ON THE | | | SYSTEM. | | | | | | INDICATE THE CIRCUIT CLASS. | | | | | | INDICATE THE CORRECT CANDELA OF THE VISUAL NOTIFICATION | | | APPLIANCES. CURRENTLY ALL DEVICES ARE INDICATED AS 15 | | | CD. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2012-06-09 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2012-06-09 |
Time |
19:05 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2012-06-09 |
Time |
18:47 |
Sent To |
E |
|
| Notes |
| 2012-06-09 19:05:04 | 5840 CORPORATE WAY - SUITE #200 | | | PERMIT #12060116 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | FIRE ALARM PLANS ARE REQUIRED TO BE SEALED BY A | | | PROFESSIONAL ENGINEER WHEN THE FIRE ALARM JOB VALUE | | | EXCEEDS $5,000. | | | | | | FOR IDENTIFICATION PURPOSES, ASSIGN A NUMBERS/LETTERS | | | TO EACH FIRE ALARM DEVICE ON THE SYSTEM. | | | | | | PROVIDE A RISER DIAGRAM AND INDICATE THE WIRE SIZING | | | AND CLASS. | | | | | | PROVIDE A SCALABLE FLOOR PLAN AND INDICATE THE ROOM USE | | | OR NAME ON THE PLANS. | | | | | | INDICATE THE CANDELA OF THE VISUAL NOTIFICATION | | | APPLIANCES. | | | | | | WORK TO BE DONE IN SUITE #100 IS NOT SHOWN ON THE PLANS | | | OR INDICATED ON THE PERMIT APPLICATION. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2012-07-20 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-07-20 |
Time |
09:34 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-07-12 |
Time |
07:35 |
Sent To |
|
|
| Notes |
| 2012-07-13 07:36:17 | SENT TO FIRE SHELF FOR REVIEW. JG. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2012-06-13 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-06-13 |
Time |
11:41 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-06-06 |
Time |
09:03 |
Sent To |
|
|
| Notes |
| 2012-06-06 09:04:09 | TO FIRE |
|
|
|