Plan Review Details - Permit 12060026
| Plan Review Stops For Permit 12060026 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2012-11-13 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2012-11-13 |
Time |
18:54 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2012-11-13 |
Time |
18:54 |
Sent To |
|
|
| Notes |
| 2012-11-13 18:54:17 | REVIEW OF POLE DESIGN/EMBEDMENT CALCULATIONS AND POLE | | | FOUNDATION DETAIL AND FOR THE 19'-7" LIGHT POLE AND THE | | | 16'-4" LIGHT POLE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2012-11-09 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2012-11-09 |
Time |
17:25 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2012-11-09 |
Time |
17:25 |
Sent To |
|
|
| Notes |
| 2012-11-09 17:33:06 | *** PROVISO****: MUST SUBMIT SIGNED AND SEALED COPY OF | | | THE POLE FOUNDATION DETAIL SHEET 1 OF 1, AND POLE | | | DESIGN/EMBEDMENT CALCULATIONS FOR BOTH THE 19'-7" LIGHT | | | POLE AND THE 16'-4" LIGHT POLE. | | | | | | REVIEW OF POLE DESIGN/EMBEDMENT CALCULATIONS AND POLE | | | FOUNDATION DETAIL AND FOR THE 19'-7" LIGHT POLE AND THE | | | 16'-4" LIGHT POLE. | | | | | | ROBERT BROWN | | | TELEPHONE: (561) 805 6652 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2012-06-04 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-06-04 |
Time |
14:38 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-06-04 |
Time |
14:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2012-06-11 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2012-06-11 |
Time |
|
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
2012-06-11 |
Time |
|
Sent To |
|
|
| Notes |
| 2012-06-11 14:32:37 | PROVISO: | | | | | | #1 CONTRACTOR TO CALL 811 BEFORE DIGG. | | | | | | #2 IDENTIFY ALL POSSIBLE CONFLICTS | | | | | | #3 ANY WORK RESULTING IN MODIFICATION TO ANY CITY | | | INFRSTRUCTURE MUST BE COORDINATED THRU ESD (ENGINEERING | | | SERVICES DEPARTMENT) | | | | | | #4 PROPER ROW PERMITS MUST BE OBTAINED TO CLOSE ANY | | | PEDESTRIAN AND/OR TRAFFIC. PROPER MOT MUST BE IN PLACE. | | | | | | MANUEL JULIAN GONZALEZ | | | ENGINEERING PROJECT COORDINATOR | | | ENGINEERING SERVICES DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1085 | | | FAX: (561) 494-1116 | | | MOBILE: (561) 644-7301 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2012-06-04 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-06-04 |
Time |
14:38 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-06-01 |
Time |
18:02 |
Sent To |
|
|
| Notes |
|
|
|