Plan Review Details - Permit 12060014
Plan Review Stops For Permit 12060014
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-06-08 Cont ID  
Sent By rlecky Date 2012-06-08 Time 14:45 Rev Time 0.00
Received By rlecky Date 2012-06-08 Time 14:37 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-06-18 Cont ID  
Sent By wjolin Date 2012-06-18 Time 13:54 Rev Time 0.00
Received By wjolin Date 2012-06-18 Time 13:35 Sent To  
Notes
2012-06-18 13:45:321889 PALM BEACH LAKES BOULEVARD
 PERMIT #12060014
 MASTER #12030394
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - SUBMIT REVISION*****
  
 FOR IDENTIFICATION PURPOSES, ASSIGN A NUMBERS/LETTERS
 TO EACH FIRE ALARM DEVICE ON THE SYSTEM.
  
  
 NOTE:
 PER LOCAL AHJ POLICY, DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM CONDITION.
  
 A CERTIFICATE OF COMPLETION AND A THIRD PARTY
 MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE SHALL
 BE PROVIDED AT TIME OF FINAL FIRE ALARM INSPECTION.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-06-08 Cont ID  
Sent By wjolin Date 2012-06-08 Time 14:10 Rev Time 0.00
Received By wjolin Date 2012-06-08 Time 13:33 Sent To E
Notes
2012-06-08 14:10:071889 PALM BEACH LAKES BOULEVARD
 PERMIT #12060014
 MASTER #12030394
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FIRE ALARM BATTERY CALCULATIONS WERE NOT SIGNED/SEALED
 BY THE ENGINEER.
  
 FOR IDENTIFICATION PURPOSES, ASSIGN A NUMBERS/LETTERS
 TO EACH FIRE ALARM DEVICE ON THE SYSTEM.
  
 PER LOCAL AHJ POLICY, DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM CONDITION.
  
 A CERTIFICATE OF COMPLETION AND A THIRD PARTY
 MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE SHALL
 BE PROVIDED AT TIME OF FINAL FIRE ALARM INSPECTION.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-06-18 Cont ID  
Sent By wjolin Date 2012-06-18 Time 13:54 Rev Time 0.00
Received By wjolin Date 2012-06-18 Time 13:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-06-11 Cont ID  
Sent By hmoser Date 2012-06-11 Time 13:24 Rev Time 0.00
Received By hmoser Date 2012-06-01 Time 12:51 Sent To  
Notes
2012-06-01 12:51:53SENT TO FIRE BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-06-11 Cont ID  
Sent By hmoser Date 2012-06-11 Time 13:24 Rev Time 0.00
Received By hmoser Date 2012-06-11 Time 13:24 Sent To  
Notes
***NONE***