Plan Review Details - Permit 12050775
Plan Review Stops For Permit 12050775
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-05-29 Cont ID  
Sent By rlecky Date 2012-05-29 Time 12:03 Rev Time 0.00
Received By rlecky Date 2012-05-29 Time 12:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-05-30 Cont ID  
Sent By wjolin Date 2012-05-30 Time 09:45 Rev Time 0.00
Received By wjolin Date 2012-05-30 Time 09:09 Sent To  
Notes
2012-05-30 09:45:011225 PALM BEACH LAKES BOULEVARD
 PERMIT #12050775
 MASTER #11050304
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 A CERTIFICATE OF COMPLETION AND A THIRD PARTY
 MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE SHALL
 BE PROVIDED AT TIME OF FINAL FIRE ALARM INSPECTION
 (#302).
  
 FIRE ALARM CIRCUIT BREAKER TO BE MARKED IN RED AND
 IDENTIFIED AS "FIRE ALARM." PROVIDE CIRCUIT BREAKER
 LOCK FOR DEDICATED BRANCH CIRCUIT.
  
 PER LOCAL AHJ POLICY, DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM CONDITION.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-05-30 Cont ID  
Sent By wjolin Date 2012-05-30 Time 09:45 Rev Time 0.00
Received By wjolin Date 2012-05-29 Time 11:59 Sent To  
Notes
2012-05-29 12:03:36TO FIRE