Plan Review Details - Permit 12050770
Plan Review Stops For Permit 12050770
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-07-27 Cont ID  
Sent By jwitmer Date 2012-07-27 Time 09:47 Rev Time 0.00
Received By jwitmer Date 2012-07-26 Time 13:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-07-12 Cont ID  
Sent By jwitmer Date 2012-07-12 Time 09:43 Rev Time 0.00
Received By jwitmer Date 2012-07-12 Time 09:32 Sent To  
Notes
2012-07-12 09:44:23BUILDING PLAN REVIEW
 PERMIT: 12050770
 ADD: 401 S DIXIE 1ST FLOOR
 CONT:TBD
 TEL: (561)389-3887
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 ACTION: DENIED
  
 1) SHEET A3.0 ELEVATIONS INDICATE THE OPENINGS TO BE
 OVER 120" TALL, 10'-6". THE VERTICAL OPENING EXCEEDS
 THE TABLES IN THE SUBMITTED PRODUCT APPROVALS EITHER
 NEW APPROVALS WOULD BE REQUIRED OR MULLIONS THAT WILL
 MEET THE VERTICAL LENGTH REQUIREMENTS AND ASSOCATED
 PRESSUES.
 107.3.1*, FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS / MULLIONS
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-06-08 Cont ID  
Sent By jwitmer Date 2012-06-08 Time 10:29 Rev Time 0.00
Received By jwitmer Date 2012-06-08 Time 09:53 Sent To  
Notes
2012-06-08 10:42:57BUILDING PLAN REVIEW
 PERMIT: 12050770
 ADD: 401 S DIXIE 1ST FLOOR
 CONT:TBD
 TEL: (561)389-3887
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A3.0 MISSING THE WIND DESIGN CRITERIA:
 1609.6.2 WIND DESIGN PROCEDURES
 1.1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE
 ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION.
  
 1.2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION1609.5.
  
 1.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4.
  
 1.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4)
  
 1.5) COMPONENTS & CLADDING FOR PRESSURES +/-.
  
 2) SHEET A3.0 ELEVATIONS INDICATE THE OPENINGS TO BE
 OVER 120" TALL, 10'-6". THE VERTICAL OPENING EXCEEDS
 THE TABLES IN THE SUBMITTED PRODUCT APPROVALS EITHER
 NEW APPROVALS WOULD BE REQUIRED OR MULLIONS THAT WILL
 MEET THE VERTICAL LENGTH REQUIREMENTS AND ASSOCATED
 PRESSUES.
 107.3.1*, FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS / MULLIONS
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-07-23 Cont ID  
Sent By rlecky Date 2012-07-23 Time 11:54 Rev Time 0.00
Received By rlecky Date 2012-07-23 Time 11:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-05-29 Cont ID  
Sent By rlecky Date 2012-05-29 Time 11:41 Rev Time 0.00
Received By rlecky Date 2012-05-29 Time 11:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-06-12 Cont ID  
Sent By wjolin Date 2012-06-12 Time 08:55 Rev Time 0.00
Received By wjolin Date 2012-06-12 Time 08:47 Sent To  
Notes
2012-06-12 08:55:14401 SOUTH DIXIE HIGHWAY
 PERMIT #12050770
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SEE ZONING REVIEW COMMENTS REGARDING APPROPRIATE
 ADDRESS FOR THE BUILDING AND SUITES.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY THE
 FIRE DEPARTMENT AFTER ALL PLAN REVIEWER COMMENTS HAVE
 BEEN SATISFIED.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-07-31 Cont ID  
Sent By hmoser Date 2012-07-31 Time 13:29 Rev Time 0.00
Received By hmoser Date 2012-07-31 Time 13:29 Sent To  
Notes
2012-07-23 10:39:54SENT TO B24 SHELF FOR JIM'S REVIEW. PRODUCT APPROVALS
 SUBMITTED BEFORE THE SECOND REVIEW CYCLE WAS FINISHED.
 JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-07-31 Cont ID  
Sent By hmoser Date 2012-07-31 Time 13:29 Rev Time 0.00
Received By hmoser Date 2012-06-29 Time 13:38 Sent To  
Notes
2012-07-13 09:29:40NEW MEP DRAWINGS SUBMITTED ON 7/12/12. SENT TO B24
 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-06-26 Cont ID  
Sent By hmoser Date 2012-06-26 Time 12:38 Rev Time 0.00
Received By hmoser Date 2012-05-29 Time 11:10 Sent To  
Notes
2012-05-29 11:13:29B07

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2013-01-07 Cont ID  
Sent By tgordon Date 2013-01-07 Time 14:49 Rev Time 0.00
Received By tgordon Date 2013-01-07 Time 14:49 Sent To  
Notes
2013-01-07 14:51:21REVISION TO MECH. PLAN M2.1 REV. TRACKING #13010040
 *** PROVISO ***
  
 1) BEFORE FINAL INSPECTION, SUBMIT FOR REVIEW AN UP TO
 DATE PRODUCT APPROVAL FOR THE WALL MOUNTED A/C
 CONDENSER STAND. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 1, 2010, (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS: (G) EXTERIOR COOLER, FREEZERS &
 "PER-ENGINEERED A/C STANDS". ALSO SEE 2010 FBC
 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL. OR SIGNED AND
 SEALED ENGINEERING.
  
 MECHANICAL PLAN REVIEW BY:
 TOM GORDON (HY-BYRD INC.) (561) 805-6732

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-07-31 Cont ID  
Sent By hmoser Date 2012-07-31 Time 13:27 Rev Time 0.00
Received By hmoser Date 2012-07-31 Time 13:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2012-06-26 Cont ID  
Sent By hmoser Date 2012-06-26 Time 12:37 Rev Time 0.00
Received By hmoser Date 2012-06-26 Time 12:37 Sent To  
Notes
2012-06-26 12:38:28NO MECHANICAL PLANS REQUIRED.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-07-17 Cont ID  
Sent By lwagner Date 2012-07-17 Time 12:47 Rev Time 0.00
Received By lwagner Date 2012-07-17 Time 10:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2012-06-14 Cont ID  
Sent By lwagner Date 2012-06-14 Time 11:06 Rev Time 0.00
Received By lwagner Date 2012-06-14 Time 10:50 Sent To  
Notes
2012-06-14 11:13:05NO PLUMBING SHOWN AT THIS TIME

Review Stop Z ZONING
Rev No 2 Status P Date 2012-07-30 Cont ID  
Sent By aaponte Date 2012-07-30 Time 14:30 Rev Time 0.00
Received By aaponte Date 2012-07-30 Time 14:30 Sent To  
Notes
2012-07-30 14:32:14NEW DOORS SWING TO OUTSIDE SIDEWALK, BUT BEHIND MINIMUM
 SETBACK REQUIRED.

Review Stop Z ZONING
Rev No 1 Status F Date 2012-06-11 Cont ID  
Sent By aaponte Date 2012-06-11 Time 15:24 Rev Time 0.00
Received By aaponte Date 2012-06-11 Time 15:24 Sent To  
Notes
2012-06-11 15:32:261. SIDEWALK CANNOT BE ALTERED IN THE PROPOSED WAY.
 DIFFERENCE IN GRADE ELEVATION SHALL BE ABSORBED WITHIN
 THE BUILDING AND NOT IN THE SIDEWALK. IF THAT IS NOT
 POSSIBLE THE SIDEWALK GRADE ELEVATION SHALL BE ALTERED
 IN A WAY IT IS NOT PERCEIVED BY PEDESTRIANS.
 2. TITLE BLOCK HAS THE WRONG ADDRESS FOR THE PROJECT.
 PLEASE CONTACT ANA MARIA APONTE AT 561-822-1439 FOR
 FURTHER DISCUSSIONS.