Plan Review Details - Permit 12050713
Plan Review Stops For Permit 12050713
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-07-05 Cont ID  
Sent By jgomez Date 2012-07-05 Time 13:02 Rev Time 0.00
Received By jgomez Date 2012-07-05 Time 12:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-05-23 Cont ID  
Sent By jgomez Date 2012-05-23 Time 15:21 Rev Time 0.00
Received By jgomez Date 2012-05-23 Time 15:21 Sent To  
Notes
2012-05-23 15:31:40RE-ROOF BUILDING REVIEW COMMENTS.
 2010 FBC.
  
 1- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 10-1230.03 SUBMITTED. NEED NAIL ENHANCING TO MEET THE
 DESIGN PRESSURES AS REQUIRED BY SEC. 1609. PROVIDE 2
 COPIES WITH ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTES.
  
 2- PROVIDE TAS 105 FASTENER WITHDRAWAL TEST AS REQUIRED
 BY GENERAL LIMITATION #5 ON LAST PAGE OF NOA SUBMITTED.
 NEED TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF
 SEC. 1609. PROVIDE 2 COPIES WITH ORIGINAL SEAL AND
 SIGNATURE AS REQUIRED BY CHAPTER 471 FLORIDA STATUTES.
  
 3- FOR YOUR INFORMATION: ANY ROOF EQUIPMENT REMOVAL
 REQUIRES SEPARATE PERMITS. AND, ANY RETROFIT ROOF
 DRAINS REQUIRE PLUMBING REVIEW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-07-05 Cont ID  
Sent By jgomez Date 2012-07-05 Time 13:02 Rev Time 0.00
Received By jgomez Date 2012-07-05 Time 12:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-05-23 Cont ID  
Sent By jgomez Date 2012-05-23 Time 15:21 Rev Time 0.00
Received By jgomez Date 2012-05-23 Time 15:21 Sent To  
Notes
***NONE***