| 2012-05-31 08:30:24 | BUILDING PLAN REVIEW |
| | PERMIT: 12050711 |
| | ADD: 1801 S FLAGLER DR # 204 |
| | CONT: D L PORTER CONSTRUCTORS, INC (TBD) |
| | TEL: (941)650-3311 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PLANS DO NOT IDENTIFY TO WHICH CODE THEY ARE |
| | DESIGNED. MACH 15, 2012 PLANS SUBMITTED FOR |
| | JURISDICTIONAL REVIEW WILL BE DESSIGNED TO THE 2012 |
| | FBC- FL S 553.73. |
| | |
| | 2) 2012 FLORIDA EXISTING BUILDING CODE, THE DESIGNER OF |
| | RECORD HAS NOT INDICATED WHICH COMPLIANCE METHOD THEY |
| | DESIGNED THIS PLAN TOO UNDER EXIST BLDG CODE 101.5 |
| | COMPLIANCE METHOD. |
| | |
| | 3A) PLANS INDICATE NEW WOOD FLOORS, PLEASE PROVIDE |
| | COMPLIANCE WITH 2010 FBC-B 1207.3 STRUCTURE BORNE SOUND |
| | TRANSMITION. THE FLOORING/ CEILING ASSEMBLY SHALL HAVE |
| | AN IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS |
| | THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE |
| | WITH ASTM E 492. |
| | |
| | 3B) ASH 3/8 INCH HARDWOOD FLOORING PLEASE PROVIDE |
| | COMPLIANCE WITH SECTION 2010 FBC-B 603.1.2(2) |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | 4) SHEET A1.01 NOTE # 5 INDICATES THE REPLACEMENT OF |
| | EXTERIOR SLIDING GLASS DOORS, PLEASE PROVIDE THE WIND |
| | DESIGN CRITERIA: |
| | 1609.6.2 WIND DESIGN PROCEDURES |
| | 4.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE |
| | ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION. |
| | |
| | 4.2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH SECTION1609.5. |
| | |
| | 4.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4. |
| | |
| | 4.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4) |
| | |
| | 4.5) PREASURES, POSITIVE/ NEGATIVE |
| | |
| | 5) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 6) COMPONENTS & CLADDING, FLORIDA DEPARTMENT OF |
| | COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | |
| | 7) SHEET A1.01 NOTE # 8 INDICATES THE INSTALATION OF A |
| | NEW SOFFIT/ DROPPED CEILING BUT THERE IS NO FRAMING |
| | INFORMATION, TYPE OF FINISH ON THE SOFFIT, LIMITS OF |
| | DEFLECTION, |
| | 2010 FBC-B 2506.2, TABLE 2506.2 STEEL STUDS NON-LOAD |
| | BEARING ASTM C 645. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |