Plan Review Details - Permit 12050659
| Plan Review Stops For Permit 12050659 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2012-06-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2012-06-12 |
Time |
09:17 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2012-06-12 |
Time |
09:17 |
Sent To |
|
|
| Notes |
| 2012-06-12 09:28:12 | ****PROVISO**** | | | ****ISSUED AT CONTRACTOR'S RISK**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. FBC 709.1, FIRE RATED 1 HOUR WALL REQUIRED AT TENANT | | | SEPARATION WALLS. PROVIDE A DETAIL AT INSPECTION. | | | | | | 2. FBC 1207.2, 1207.3, SOUND BARRIER REQUIRED BETWEEN | | | TENANT SPACES. STC OF 50 AND IIC OF 50 REQUIRED. | | | PROVIDE DETAIL AT INSPECTION. | | | | | | REVISION MAY BE REQUIRED SUBJECT TO INSPECTOR'S | | | DISCRETION | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2012-05-31 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-05-31 |
Time |
12:06 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-05-31 |
Time |
11:23 |
Sent To |
|
|
| Notes |
| 2012-05-31 12:06:42 | PASSED WITH A PROVISO. | | | | | | PROVISO: | | | | | | AFCI PROTECTED CIRCUITS ARE REQUIRED. NEC 210.12 | | | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | | THE BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH | | | CIRCUIT. NEC 210.11 (C) (3) | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT | | | ALREADY EXIST WITHIN THE RESIDENCE. 2010 FBC R314 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2012-05-30 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2012-05-30 |
Time |
13:58 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2012-05-30 |
Time |
13:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2012-06-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2012-06-12 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2012-05-23 |
Time |
11:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2012-06-12 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2012-06-07 |
Time |
13:33 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2012-06-07 |
Time |
13:09 |
Sent To |
|
|
| Notes |
| 2012-06-07 13:32:54 | PLANS DENIED | | | REFER TO SECTION 403.6.1 EQUIPMENT SIZING 2010 | | | FLORIDA ENERGY CODE ( HEATING & COOLING LOADS | | | ENERGY CALCULATION. | | | PLANS CALL FOR A MIN 9 SEER TABLE 503.2.3 2010 | | | FLORIDA ENERGY CODE CALLS FOR A 13 SEER | | | 6/12/12 | | | RICH CALLED MECHANICAL IS GOING TO SUBMIT NEW | | | APPLICATION | | | AND PLANS SO I CAN CHANGE THE F TO AN N | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2012-06-05 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2012-06-05 |
Time |
19:59 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
2012-06-05 |
Time |
19:59 |
Sent To |
|
|
| Notes |
| 2012-06-05 20:02:42 | LESS THAN 50% OF STRUCTURE |
|
|
|