Plan Review Details - Permit 12050659
Plan Review Stops For Permit 12050659
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2012-06-12 Cont ID  
Sent By shill Date 2012-06-12 Time 09:17 Rev Time 0.00
Received By shill Date 2012-06-12 Time 09:17 Sent To  
Notes
2012-06-12 09:28:12****PROVISO****
 ****ISSUED AT CONTRACTOR'S RISK****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. FBC 709.1, FIRE RATED 1 HOUR WALL REQUIRED AT TENANT
 SEPARATION WALLS. PROVIDE A DETAIL AT INSPECTION.
  
 2. FBC 1207.2, 1207.3, SOUND BARRIER REQUIRED BETWEEN
 TENANT SPACES. STC OF 50 AND IIC OF 50 REQUIRED.
 PROVIDE DETAIL AT INSPECTION.
  
 REVISION MAY BE REQUIRED SUBJECT TO INSPECTOR'S
 DISCRETION
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-05-31 Cont ID  
Sent By rlecky Date 2012-05-31 Time 12:06 Rev Time 0.00
Received By rlecky Date 2012-05-31 Time 11:23 Sent To  
Notes
2012-05-31 12:06:42PASSED WITH A PROVISO.
  
 PROVISO:
  
 AFCI PROTECTED CIRCUITS ARE REQUIRED. NEC 210.12
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
 THE BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH
 CIRCUIT. NEC 210.11 (C) (3)
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT
 ALREADY EXIST WITHIN THE RESIDENCE. 2010 FBC R314
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-05-30 Cont ID  
Sent By wjolin Date 2012-05-30 Time 13:58 Rev Time 0.00
Received By wjolin Date 2012-05-30 Time 13:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-06-12 Cont ID  
Sent By shill Date 2012-06-12 Time 09:28 Rev Time 0.00
Received By shill Date 2012-05-23 Time 11:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2012-06-12 Cont ID  
Sent By hmoser Date 2012-06-07 Time 13:33 Rev Time 0.00
Received By hmoser Date 2012-06-07 Time 13:09 Sent To  
Notes
2012-06-07 13:32:54PLANS DENIED
 REFER TO SECTION 403.6.1 EQUIPMENT SIZING 2010
 FLORIDA ENERGY CODE ( HEATING & COOLING LOADS
 ENERGY CALCULATION.
 PLANS CALL FOR A MIN 9 SEER TABLE 503.2.3 2010
 FLORIDA ENERGY CODE CALLS FOR A 13 SEER
 6/12/12
 RICH CALLED MECHANICAL IS GOING TO SUBMIT NEW
 APPLICATION
 AND PLANS SO I CAN CHANGE THE F TO AN N
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2012-06-05 Cont ID  
Sent By eschneid Date 2012-06-05 Time 19:59 Rev Time 0.25
Received By eschneid Date 2012-06-05 Time 19:59 Sent To  
Notes
2012-06-05 20:02:42LESS THAN 50% OF STRUCTURE