Plan Review Details - Permit 12050616
Plan Review Stops For Permit 12050616
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-06-21 Cont ID  
Sent By shill Date 2012-06-21 Time 09:00 Rev Time 0.00
Received By shill Date 2012-06-21 Time 09:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-06-04 Cont ID  
Sent By shill Date 2012-06-04 Time 12:39 Rev Time 0.00
Received By shill Date 2012-06-04 Time 12:39 Sent To  
Notes
2012-06-04 12:53:21****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. WIND SPEED TO BE A MINIMUM OF 169MPH, 160 SUBMITTED,
 SEE FBC 1609.1.1.
  
 2. EITHER REVISE EXPOSURE TO EXPOSURE D OR PROVIDE A
 SIGNED, SEALED LETTER STATING RATIONALE FOR EXPOSURE C
 DESIGN PRESSURES, FBC 1609.4.
  
 3. WHEN RESUBMITTING, INCLUDE THE SHUTTER TO GLASS
 SEPARATION, SEE SHEET 19 OF THE PRODUCT APPROVAL (6.25"
 FOR WIND ZONE 4, SEE FBC 1609.1.2.4).
  
 4. SHEET 19 LIMITS USE OF THIS PRODUCT TO -110PSF WHEN
 WORKING WITH HV WINDOW BLADE, FBC 1609.1.1.
  
  
 3.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-06-21 Cont ID  
Sent By shill Date 2012-06-21 Time 09:00 Rev Time 0.00
Received By shill Date 2012-06-12 Time 08:46 Sent To  
Notes
2012-06-13 08:46:55ROUTED TO SH

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-06-04 Cont ID  
Sent By shill Date 2012-06-04 Time 12:53 Rev Time 0.00
Received By shill Date 2012-05-21 Time 10:52 Sent To  
Notes
2012-05-22 10:52:27SENT TO MISCELLANEOUS SHELF #1 FOR REVIEW. JG.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved