Plan Review Details - Permit 12050570
Plan Review Stops For Permit 12050570
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-07-11 Cont ID  
Sent By jwitmer Date 2012-07-11 Time 10:32 Rev Time 0.00
Received By jwitmer Date 2012-07-11 Time 10:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-06-25 Cont ID  
Sent By jwitmer Date 2012-06-25 Time 09:46 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2012-06-25 10:19:48BUILDING PLAN REVIEW
 PERMIT: 12050570
 ADD: 222 LAKEVIEW AVE # 148
 CONT: HOLT LEE CONSTRUCTION
 TEL: (954)270-1894
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 ACTION: DENIED
  
 1) SHEET A1.1:
  
 1A)2ND REQUEST, PLEASE PROVIDE THE USAGE FOR THE
 BUSINESS OCCUPANCY FOR ROOM 148 & 150? IT APPEARS THAT
 ROOM 148 IS TO BE OCCUPIED BUT BOTH SUITES INDICATE
 THEY ARE UNOCCUPIED SPACE? 106.1.2 ADDITIONAL
 INFORMATION IS REQUIRED. THE RESPONCE INDICATES BOTH
 ROOMS ARE UNOCCIPIED AND WILL NOT HOUSE ANY PEOPLE BUT
 THE RESPONCE TO COMMENT (1D) INDICATES AN AUTOMATIC
 DOOR OPENER FOR ADA ACCESS WILL BE INSTALLED, THIS
 APPEARS THAT THERE WILL BE AN OCCUPANT LOAD AND WILL BE
 OCCUPIED. THE SPACE # 148 THE RESPONCE INDICATES THIS
 AREA TO BE USED AS A FURNITURE SHOWROOM. 2010 FBC-B
 309.1 INDICATES THE OCCUPANCY TYPE TO BE A MERCANTILE
 "FOR THE DISPLAY AND SALE OF
 MERCHANDISE AND INVOLVES STOCKS OF GOODS AND SALE OF
 MERCHANDISE INCIDENTIAL TO SUCH PURPOSES AND ACCESSIBLE
 TO THE PUBLIC. PLEASE CORRECT THE COVER SHEET AND
 ASSOCIATED OCCUPANT LOAD.
  
 1B) 2ND REQUEST, CEILING NOTE # 2 AND FLOOR PLAN NOTE #
 8 INDICATE THE USE OF NEW STRETCHED FABRIC SAIL CABLE
 MOUNTED TO CEILING DECK ABOVE. SEE DETAIL FB-3 ON SHEET
 A3.1 FOR SPEC.
 MISSING DETAIL ON SHEET A3.1. PLEASE PROVIDE MOUNTING
 DETAIL AND PRODUCT COMPLIANCE FOR 2010 FBC-B 803.1.4
 ACCEPTANCE CRITERIA FOR TEXTILE WALL OR CEILING
 COVERINGS TO ASTM 84 OR UL723.
 SUBMITTED PRODUCT SPEC JUXTAFORM HAS TWO TYPES OF
 FABRIC :
 STANDARD FABRIC SPECIFICATIONS WITH ASTM E84
 MESH FABRIC SPECIFICATIONS NO ASTM E 84 TESTING
 WHICH OF THE FABRICS ARE GOING TO BE INSTALLED?
  
 1C) 2ND REQUEST, PLANS ARE NOT CLEAR AS TO SUITE # 150
 THE UNOCCUPIED SPACE, IS THIS PART OF THE SAME
 TENANTCY, OR IS THE WALL SEPERATING THE TWO ROOMS A
 TENANT SEPERATION WALL THAT WOULD REQUIRE FIRE RATING
 PER 2010 FBC-B SECTION # 709.1(6). IS THE AREA
 UNOCCUPIED AREA # 150 UNDER THIS TENANCY? IF THE AREA #
 150 IS NOT UNDER THE SAME TENANCY THEN IT IS CONSIDERED
 A TENANT SPERATION WALL 2010 FBC-B. IF THIS SPACE IS TO
 BE CONSIDERED A SEPERATE TENDANCY A SHELL SPACE A 1
 HOUR TENANT SEPERATION WALL WILL BE REQUIRED.
  
 1D) COMPLIED.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-06-07 Cont ID  
Sent By jwitmer Date 2012-06-07 Time 16:14 Rev Time 0.00
Received By jwitmer Date 2012-06-07 Time 14:50 Sent To  
Notes
2012-06-07 16:22:03BUILDING PLAN REVIEW
 PERMIT: 12050570
 ADD: 222 LAKEVIEW AVE # 148
 CONT: HOLT LEE CONSTRUCTION
 TEL: (954)270-1894
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A1.1:
  
 1A) PLEASE PROVIDE THE USAGE FOR THE BUSINESS OCCUPANCY
 FOR ROOM 148 & 150? IT APPEARS THAT ROOM IS TO BE
 OCCUPIED BUT BOTH SUITES INDICATE THEY ARE UNOCCUPIED
 SPACE? 106.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 1B) CEILING NOTE # 2 AND FLOOR PLAN NOTE # 8 INDICATE
 THE USE OF NEW STRETCHED FABRIC SAIL CABLE MOUNTED TO
 CEILING DECK ABOVE. SEE DETAIL FB-3 ON SHEET A3.1 FOR
 SPEC.
 MISSING DETAIL ON SHEET A3.1. PLEASE PROVIDE MOUNTING
 DETAIL AND PRODUCT COMPLIANCE FOR 2010 FBC-B 803.1.4
 ACCEPTANCE CRITERIA FOR TEXTILE WALL OR CEILING
 COVERINGS TO ASTM 84 OR UL723.
  
 1C) PLANS ARE NOT CLEAR AS TO SUITE # 150 THE
 UNOCCUPIED SPACE, IS THIS PART OF THE SAME TENANTCY, OR
 IS THE WALL SEPERATING THE TWO ROOMS A TENANT
 SEPERATION WALL THAT WOULD REQUIRE FIRE RATING PER 2010
 FBC-B SECTION # 709.1(6).
  
 1D) THE FLOOR PLAN NOTE # 10 INDICATES AUTOMATIC DOOR
 OPENERS, ARE THESE ELECTRIC ACCESS CONTROLED DOORS,
 (TOUCH PADS) PLEASE PROVIDE ADDITIONAL INFORMATTION
 INDICATING COMPLIANCE WITH FBC-B 1008.1.4.2 FOR
 POWER-OPERATED DOORS AND 1008.1.4.4 FOR
 ACCESS-CONTROLLED EGRESS DOORS.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-05-22 Cont ID  
Sent By rlecky Date 2012-05-22 Time 10:03 Rev Time 0.00
Received By rlecky Date 2012-05-22 Time 09:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2012-07-19 Cont ID  
Sent By wjolin Date 2012-07-19 Time 12:55 Rev Time 0.00
Received By wjolin Date 2012-07-19 Time 12:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2012-06-18 Cont ID  
Sent By wjolin Date 2012-06-18 Time 12:49 Rev Time 0.00
Received By wjolin Date 2012-06-18 Time 11:58 Sent To M
Notes
2012-06-18 12:49:03222 LAKEVIEW AVENUE - SUITE #148
 PERMIT #12050570
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 IF SUITE #148 IS TO BE UTILIZED AS A FURNITURE
 SHOWROOM, THIS WOULD NOT BE CLASSIFIED AS A BUSINESS
 OCCUPANCY AS INDICATED ON THE COVER SHEET.
  
 SUITE #150 NEEDS TO HAVE PERMANENT SIGNAGE INDICATING,
 "SHELL SPACE ONLY - NO STORAGE ALLOWED."
  
 THE FLAME SPREAD AND SMOKE DEVELOPMENT OF FLEXIBLE AIR
 DUCTS NEED TO BE LISTED AND LABELED AS CLASS 0 OR CLASS
 1 PER UL 181. UL CURRENTLY DOES NOT LIST "FABRICAIR
 INC." AS MEETING THE REQUIREMENTS OF UL 181.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-05-29 Cont ID  
Sent By wjolin Date 2012-05-29 Time 14:15 Rev Time 0.00
Received By wjolin Date 2012-05-29 Time 13:35 Sent To  
Notes
2012-05-29 14:15:53222 LAKEVIEW AVENUE - SUITE #148
 PERMIT #12050570
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 CLARIFY HOW THE SPACES #148 AND #150 WILL BE UTILIZED;
 BOTH SPACES ARE INDICATED AS "UNOCCUPIED".
  
 SPACE #150 APPEARS TO BE UNOCCUPIED SHELL/STORAGE ROOM.
 IS A FIRE BARRIER WITH PROTECTED OPENINGS AND
 PENETRATIONS INTENDED FOR THIS SPACE?
  
 CONFIRM THE FABRIC SAILS WILL ONLY BE MOUNTED
 VERTICALLY. HORIZONTAL FABRIC SAILS MAY OBSTRUCT
 SPRINKLER SPRAY.
  
 THUMB-TURN LOCKS TO BE EQUIPPED WITH A LOCK/UNLOCK
 INDICATOR.
  
 NO FIRE ALARM NOTIFICATION APPLIANCES SHOWN ON PLANS.
  
 ELECTRICAL SHEET INDICATES PUSH BUTTONS ON EACH SIDE OF
 THE EXTERIOR DOUBLE DOORS. ARE THESE DOORS INTENDED TO
 HAVE ACCESS-CONTROLLED EGRESS?
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-07-25 Cont ID  
Sent By jwitmer Date 2012-07-25 Time 14:09 Rev Time 0.00
Received By jwitmer Date 2012-07-11 Time 10:32 Sent To  
Notes
2012-07-11 10:33:49INCOMING SENT TO B07. JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-06-25 Cont ID  
Sent By jwitmer Date 2012-06-25 Time 10:19 Rev Time 0.00
Received By jwitmer Date 2012-06-15 Time 17:50 Sent To  
Notes
2012-06-15 17:51:07IN FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-06-07 Cont ID  
Sent By jwitmer Date 2012-06-07 Time 16:44 Rev Time 0.00
Received By jwitmer Date 2012-05-18 Time 11:30 Sent To  
Notes
2012-05-18 11:30:28B19

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2012-07-25 Cont ID  
Sent By jwitmer Date 2012-07-25 Time 14:06 Rev Time 0.00
Received By jwitmer Date 2012-07-25 Time 10:06 Sent To  
Notes
2012-07-25 14:09:54SEE ATTACHED PAPERWORK FOR TESTING TO UL 181 REQUIRED
 BY 2010 FBC-M 603.5& 603.6.1. ICC-ES REPORT AC 167.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2012-06-21 Cont ID  
Sent By hmoser Date 2012-06-21 Time 08:39 Rev Time 0.00
Received By hmoser Date 2012-06-21 Time 08:36 Sent To  
Notes
2012-06-21 08:39:48PLANS DENIED
 REFER TO SECTION 603.5 NONMETALLIC DUCTS. 2010 FBC (M)
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]
 SENT TO JIM WITMER

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-06-05 Cont ID  
Sent By hmoser Date 2012-06-05 Time 12:08 Rev Time 0.00
Received By hmoser Date 2012-06-05 Time 11:50 Sent To  
Notes
2012-06-05 12:12:09PLANS DENIED
 PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS AND
 PRODUCT APPROVALS FOR THE DUCTSOCK WITH THE PLANS
 REFER TO SECTION 503.2.1 CALCULATION OF HEATING AND
 COOLING LOADS
 2010 FLORIDA ENERGY CODE.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-05-31 Cont ID  
Sent By lwagner Date 2012-05-31 Time 10:08 Rev Time 0.00
Received By lwagner Date 2012-05-31 Time 08:22 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2012-05-31 Cont ID  
Sent By aaponte Date 2012-05-31 Time 14:12 Rev Time 0.00
Received By aaponte Date 2012-05-31 Time 14:12 Sent To  
Notes
2012-05-31 14:13:04INTERIOR IMPROVEMETNS ONLY.