Plan Review Details - Permit 12050553
Plan Review Stops For Permit 12050553
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-07-09 Cont ID  
Sent By jwitmer Date 2012-07-09 Time 14:22 Rev Time 0.00
Received By jwitmer Date 2012-07-09 Time 14:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-06-01 Cont ID  
Sent By jwitmer Date 2012-06-01 Time 16:00 Rev Time 0.00
Received By jwitmer Date 2012-06-01 Time 14:39 Sent To  
Notes
2012-06-01 16:00:24BUILDING PLAN REVIEW
 PERMIT: 12050553
 ADD: 2271 PALM BEACH LAKES / SUITE "C"
 CONT: RAPP CONSTRUCTION
 TEL: (561)842-3299
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A3.1 FLOOR PLAN/ LIFE SAFETY PLAN, PLEASE
 INDICATE WHERE THE ACCESS AISLES ARE LOCATED AND WHERE
 THE DISPLAYS, FURNISHINGS AND OR KIOSK ARE LOCATED.
 PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B 1017.1 &
 1017.3.
  
 2) PLANS DO NOT INDICATE THE SQUARE FOOTAGE OF THE
 STORAGE AREA AT THE BACK OF THE STORE, AND THE TOTAL
 SQUARE FOOTAGE OF THE STORE. IF THE STORAGE AREA IS
 OVER 10% OF THE TOTAL FLOOR AREA THEN IT IS CONSIDERED
 A ACCESORY OCCUPANCY WHICH WILL MKE THIS A MIXED
 OCCUPANCY. PLEASE REVIEW SECTIONS 2010 FBC-B 508.2.1
 AREA LIMITATIONS,
 508.3 NON-SEPERATED OCCUPANCIES AND 508.4 508.4
 SEPERATED OCCUPANCIES. PLEASE ALSO REVIEW SECTION
 SECTION 311.2 IT APPEARS THAT FURNITURE IS CONSIDERED A
 S1 OCCUPANCY. TABLE 508.4. INDICATES NO OCCUPANCY
 SEPERATION IS REQUIRED BETWEEN MERCANTILE AND A S1
 STORAGE OCCUPANCY.
  
 3) SHEET 3.1 INDICATES SPRAY INSULATION R20 TO THE
 UNDER SIDE OF THE ROOF DECK, PLEASE PROVIDE
 MANUFACTURES SPECS ON THE TYPE OF INSULATION TO BE
 INSTALLED?
 IF A FOAM PLASTIC INSULATION IS TO BE INSTALLED PLEASE
 PROVIDE COMPLIANCE WITH SMOKE DEVELOPMENT & FLAME
 SPREAD, AS WELL AS COMPLIANCE WITH 2603.4.1.6 IGNITION
 BARRIER.
  
 4) SHEET 1.1 CODE SUMMARY INDICATES A SINGLE DRINKING
 FOUNTAIN PLEASE REVIEW THE 2010 FBC-ACCESSIBILITY CODE
 SCOPING 211.2 MINIMUM NUMBER. NO FEWER THAN TWO
 DRINKING FOUNTAINS SHALL BE PROVIDED.ONE DRINKING
 FOUNTAIN SHALL COMPLY WITH 602.1THROUGH 602.6 AND ONE
 DRINKING FOUNTAIN SHALL COMPLY WITH 602.7.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-06-12 Cont ID  
Sent By rlecky Date 2012-06-12 Time 12:17 Rev Time 0.00
Received By rlecky Date 2012-06-12 Time 12:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-05-22 Cont ID  
Sent By rlecky Date 2012-05-22 Time 16:16 Rev Time 0.00
Received By rlecky Date 2012-05-22 Time 16:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-06-15 Cont ID  
Sent By wjolin Date 2012-06-15 Time 13:25 Rev Time 0.00
Received By wjolin Date 2012-06-15 Time 13:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-05-30 Cont ID  
Sent By wjolin Date 2012-05-30 Time 11:02 Rev Time 0.00
Received By wjolin Date 2012-05-30 Time 10:28 Sent To  
Notes
2012-05-30 11:02:472271 PALM BEACH LAKES BOULEVARD - SUITE "C"
 PERMIT #12050553
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 PROVIDE A FURNITURE/DISPLAY LAYOUT.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 STORAGE ROOMS SHALL BE PROTECTED BY AN AUTOMATIC
 SUPPRESSION SYSTEM OR BE ENCLOSED WITH A 1-HOUR FIRE
 BARRIER. OPENINGS AND PENETRATIONS SHALL BE PROTECTED.
  
 THE LOCK/LATCH RELEASING MECHANISM ON ALL DOORS SHALL
 OPEN THE DOOR WITH NOT MORE THAN ONE RELEASING
 OPERATION. THE RELEASING MECHANISM SHALL HAVE AN
 OBVIOUS METHOD OF OPERATION THAT IS READILY OPERATED
 UNDER ALL LIGHTING CONDITIONS. THE RELEASING DEVICE
 SHOULD BE CAPABLE OF BEING OPERATED WITH ONE HAND AND
 SHOULD NOT REQUIRE TIGHT GRASPING, TIGHT PINCHING OR
 TWISTING OF THE WRIST TO OPERATE.
  
 THUMB-TURN STYLE LOCKS TO BE EQUIPPED WITH A
 LOCK/UNLOCK INDICATOR.
  
 AN APPROVED WRITTEN EMERGENCY PLAN FOR THE EMERGENCY
 EGRESS OF OCCUPANTS IS REQUIRED PRIOR TO OCCUPANCY. ALL
 EMPLOYEES SHALL BE INSTRUCTED AND PERIODICALLY DRILLED
 WITH RESPECT TO THEIR DUTIES UNDER THE PLAN.
  
 EMPLOYEES SHALL BE PERIODICALLY TRAINED OR INSTRUCTED
 IN THE USE OF PORTABLE FIRE EXTINGUISHERS.
  
 SHEET E1.1: ADDITIONAL EXIT SIGNS ARE NEEDED TO
 IDENTIFY THE REAR EXIT.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-07-09 Cont ID  
Sent By jwitmer Date 2012-07-09 Time 14:23 Rev Time 0.00
Received By jwitmer Date 2012-06-12 Time 12:07 Sent To  
Notes
2012-06-12 12:07:44C11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-06-05 Cont ID  
Sent By hmoser Date 2012-06-05 Time 11:09 Rev Time 0.00
Received By hmoser Date 2012-05-17 Time 09:33 Sent To  
Notes
2012-05-21 09:37:43C08

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-06-27 Cont ID  
Sent By hmoser Date 2012-06-27 Time 14:16 Rev Time 0.00
Received By hmoser Date 2012-06-27 Time 13:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-06-05 Cont ID  
Sent By hmoser Date 2012-06-05 Time 11:09 Rev Time 0.00
Received By hmoser Date 2012-06-05 Time 11:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-06-22 Cont ID  
Sent By lwagner Date 2012-06-22 Time 08:59 Rev Time 0.00
Received By lwagner Date 2012-06-22 Time 08:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-06-04 Cont ID  
Sent By lwagner Date 2012-06-04 Time 14:26 Rev Time 0.00
Received By lwagner Date 2012-06-04 Time 13:23 Sent To  
Notes
2012-06-04 14:28:01***PROVISO***
 HI/ LOW DRINKING FOUNTAIN WILL BE REQUIRED PER FBC
 ACCESSIBILITY 2010 211.2

Review Stop Z ZONING
Rev No 1 Status P Date 2012-06-21 Cont ID  
Sent By lfranco Date 2012-06-21 Time 15:41 Rev Time 0.00
Received By lfranco Date 2012-06-19 Time 16:10 Sent To  
Notes
2012-06-21 15:51:08PLANNING: ****** PASSED WITH PROVISO, THE WALL SIGNAGE
 SHOWN ON ON SHEET 3.2 BY ALAN STRASSLER, ELEVATIONS
 NEEDS A SEPARATE PERMIT AND IS NOT PART OF THIS REVIEW.
 THE SIGNAGE SQUARE FOOTAGE SIZE ALLOWED IS GOVERNED BY
 THE ZONING AND LAND DEVELOPMENT REGULATIONS, SECTION
 94-408(D), GENERAL COMMERCIAL ZONING DISTRICTS. ****
  
  
 IN THE SIGNAGE PERMIT, PROVIDE THE TOTAL SQUARE FOOTAGE
 OF SIGNAGE AND HEIGHT AND WIDTH OF EACH INDIVIDUAL
 FACADE. THE MAXIMUM NUMBER OF SIGNS FOR EACH BUILDING
 IS ONE SIGN FOR EACH INDIVIDUAL BUSINESS OCCUPANT OF
 THE BUILDING, PLUS TWO ADDITIONAL SIGNS. IF THE
 BUILDING IS SOLELY FOR THIS BUSINESS, THEN A TOTAL OF
 THREE (3) WALL SIGNS ARE ALLOWED. ADDITIONALLY, IF
 THERE IS A FREE-STANDING SIGN, A PERMIT SHALL BE
 SUBMITTED FOR THAT SIGN TOO.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO, AICP
 SENIOR PLANNER
 PLANNING DIVISION
 TEL: (561) 822-1443
 EMAIL: [email protected]
  
  
  
  