| Plan Review Stops For Permit 12050552 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2012-09-17 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2012-09-17 |
Time |
10:11 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2012-09-17 |
Time |
09:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2012-05-29 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2012-05-29 |
Time |
12:58 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2012-05-29 |
Time |
11:39 |
Sent To |
|
|
| Notes |
| 2012-05-29 13:11:18 | RESIDENTIAL (R3) RENOVATION BUILDING REVIEW COMMENTS. | | | 2010 FBC. | | | | | | 1- THERE ARE TWO DIFFERENT PLANS SUBMITTED. CLARIFY | | | WHICH ONE IS THE CORRECT HOUSE PLAN. SEC. 107.2.1 OF | | | CITY AMENDMENTS TO FBC. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2012-08-20 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-08-20 |
Time |
08:25 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-08-20 |
Time |
08:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2012-05-23 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-05-23 |
Time |
08:20 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-05-23 |
Time |
08:18 |
Sent To |
|
|
| Notes |
| 2012-05-23 08:22:28 | PROVIDE SCOPE OF ELECTRICAL REPAIRS. SMOKE AND CARBON | | | MONOXIDE ALARMS ARE REQUIRED. FBC R. 314 | | | | | | R.LECKY | | | ELECTRIC PLAN REVIEW | | | 561-305-6718 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2012-10-16 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2012-10-16 |
Time |
15:53 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2012-10-04 |
Time |
08:40 |
Sent To |
|
|
| Notes |
| 2012-10-05 08:41:30 | IN ZONING BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2012-10-02 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2012-10-02 |
Time |
16:33 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2012-09-19 |
Time |
14:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2012-09-17 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2012-09-17 |
Time |
10:11 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2012-08-16 |
Time |
17:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2012-05-29 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2012-05-29 |
Time |
17:26 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2012-05-17 |
Time |
10:31 |
Sent To |
|
|
| Notes |
| 2012-05-22 10:32:38 | SENT TO R1 SHELF FOR REVIEW. JG. | | 2012-05-18 11:27:55 | R-01 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2012-10-01 |
|
|
Cont ID |
|
| Sent By |
H MOSER |
Date |
2012-10-01 |
Time |
11:09 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2012-10-01 |
Time |
11:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2012-09-06 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2012-09-06 |
Time |
14:05 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2012-09-06 |
Time |
14:05 |
Sent To |
|
|
| Notes |
| 2012-09-06 14:10:12 | PLAN DENIED | | | NO AIR CONDITIONING PLANS ,ENERGY CALCULATIONS, | | | SUBMITTED | | | WITH PACKAGE PER SECTION 701 FBC 2010. | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2012-05-23 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2012-05-23 |
Time |
14:43 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2012-05-23 |
Time |
14:43 |
Sent To |
|
|
| Notes |
| 2012-05-29 10:36:47 | PLANS DENIED | | | | | | 1. APPLICATION STATES THAT A/C SYSTEM IS TO BE | | | REPLACED. PROVIDE MORE INFORMATION REGARDING SCOPE OF | | | WORK, FBC 2010 107.3.5.3. | | | | | | IF THIS IS AN EXACT CHANGEOUT, TWO SETS OF THE A/C | | | CHANGE OUT COMPLIANCE FORM REQUIRED: | | | | | | HTTP://WWW.WPB.ORG/CONSTRUCTION/PDF/AC%20CHANGEOUT.PDF | | | | | | IF THIS IS A NEW INSTALLATION, PROVIDE A PLAN FOR | | | PROPOSED WORK. PLEASE NOTE THAT I WAS UNABLE TO LOCATE | | | AN EXISTING MECHANICAL SYSTEM IN OUR RECORDS FOR THIS | | | PROPERTY. OUR RECORDS SHOW A WALL UNIT INSTALLATION IN | | | 1971, BUT I WAS UNABLE TO LOCATE A PERMIT FOR CENTRAL | | | A/C. | | | | | | 2. PROVIDE A REASONABLE VALUE / COST BREAKDOWN FOR | | | PROPOSED WORK, FBC 2010 109.3. | | | | | | 3. FBC 2010 ENERGY, PROVIDE DOCUMENTS REQUIRED BY | | | SECTION 101.4.7. | | | | | | HAROLD MOSER, CHIEF MECHANICAL INSPECTOR | | | 561-805-6732 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2012-05-29 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2012-05-29 |
Time |
13:11 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2012-05-29 |
Time |
13:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2012-10-10 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2012-10-10 |
Time |
14:44 |
Rev Time |
0.50 |
| Received By |
eschneid |
Date |
2012-10-05 |
Time |
|
Sent To |
B |
|
| Notes |
| 2012-10-10 15:02:53 | PASSED | | | | | | A/C UNITS AND PADS TO BE A MINIMUM OF 7.3 FEET FROM | | | WEST PROPERTY LINE. | | | | | 2012-10-05 10:12:48 | GAVE TO E.S. - MD. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2012-10-02 |
|
|
Cont ID |
|
| Sent By |
ESCHNEID |
Date |
2012-10-02 |
Time |
16:33 |
Rev Time |
0.50 |
| Received By |
eschneid |
Date |
2012-10-02 |
Time |
16:08 |
Sent To |
|
|
| Notes |
| 2012-10-02 16:32:13 | FAILED | | | | | | PLEASE RESPOND TO COMMENTS IN WRITING. | | | | | | 1) REPEAT COMMENT (3RD TIME) - THE VALUE OF THE | | | CONSTRUCTION ($25,000) EXCEEDS 50% OF THE STRUCTURE'S | | | VALUE ($24,993) ACCORDING TO THE P.B.C. PROPERTY | | | APPRAISER'S OFFICE; THEREFORE, PURSUANT TO SECTION | | | 94-441(C)(2) OF THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE | | | IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN | | | ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO | | | ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN | | | DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE | | | PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO | | | ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS | | | PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION | | | PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE | | | SITE INTO CONFORMITY. | | | | | | 2) REPEAT COMMENT (2ND TIME)THE SURVEY PROVIDED WITH | | | THE RESUBMITTAL SHOWS A RECTANGULAR BUILDING FOOTPRINT. | | | THE PLANS SUBMITTED WITH THE PERMIT SHOW A "U" SHAPED | | | BUILDING. THE PLANS SHALL ACCURATELY SHOW THE BUILDING | | | CONDITION. | | | | | | 3) REPEAT COMMENT (3RD TIME) - THE INSTALLATION OF AN | | | A/C UNIT ON THE EXTERIOR OF THE HOUSE WILL NEED TO BE | | | SHOWN ON A MARKED UP COPY OF THE SURVEY, WITH THE | | | SETBACKS TO THE PROPERTY LINE CLEARLY SHOWN. | | | | | | CONTACT ERIC SCHNEIDER AT (561) 822-1446. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2012-09-10 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2012-09-10 |
Time |
13:49 |
Rev Time |
1.00 |
| Received By |
eschneid |
Date |
2012-09-10 |
Time |
08:57 |
Sent To |
|
|
| Notes |
| 2012-09-10 14:33:37 | FAILED | | | | | | PLEASE RESPOND TO COMMENTS IN WRITING. | | | | | | 1) REPEAT COMMENT - THE VALUE OF THE CONSTRUCTION | | | ($25,000) EXCEEDS 50% OF THE STRUCTURE'S VALUE | | | ($24,993) ACCORDING TO THE P.B.C. PROPERTY APPRAISER'S | | | OFFICE; THEREFORE, PURSUANT TO SECTION 94-441(C)(2) OF | | | THE ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDR), THE | | | LANDSCAPE ON THE SITE SHALL BE IN COMPLIANCE WITH ALL | | | APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF THE | | | ZLDR. IF THE SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) | | | COPIES OF A LANDSCAPE PLAN DEMONSTRATING COMPLIANCE | | | SHALL BE INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE | | | SITE DOES NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE | | | ZONING APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE | | | PERMIT AND IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING | | | MATERIAL TO BRING THE SITE INTO CONFORMITY. | | | | | | 2) THE SURVEY PROVIDED WITH THE RESUBMITTAL SHOWS A | | | RECTANGULAR BUILDING FOOTPRINT. THE PLANS SUBMITTED | | | WITH THE PERMIT SHOW A "U" SHAPED BUILDING. THE PLANS | | | SHALL ACCURATELY SHOW THE BUILDING CONDITION. | | | | | | 3) REPEAT COMMENT - THE INSTALLATION OF AN A/C UNIT ON | | | THE EXTERIOR OF THE HOUSE WILL NEED TO BE SHOWN ON A | | | MARKED UP COPY OF THE SURVEY, WITH THE SETBACKS TO THE | | | PROPERTY LINE CLEARLY SHOWN. | | | | | | CONTACT ERIC SCHNEIDER AT (561) 822-1446. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2012-05-29 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2012-05-29 |
Time |
16:03 |
Rev Time |
0.75 |
| Received By |
eschneid |
Date |
2012-05-29 |
Time |
16:03 |
Sent To |
|
|
| Notes |
| 2012-05-29 17:26:01 | FAILED | | | | | | PLEASE RESPOND TO COMMENTS IN WRITING. | | | | | | 1) THE VALUE OF THE CONSTRUCTION ($25,000) EXCEEDS 50% | | | OF THE STRUCTURE'S VALUE ($24,993) ACCORDING TO THE | | | P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT | | | TO SECTION 94-441(C)(2) OF THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE | | | SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE | | | REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE | | | SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A | | | LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE | | | INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES | | | NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING | | | APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND | | | IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL | | | TO BRING THE SITE INTO CONFORMITY. | | | | | | 2) THE DRAWINGS SUBMITTED WITH THE PERMIT SEEM TO | | | INDICATE THAT WORK WILL BE FOR A DUPLEX. PLEASE NOTE | | | THAT THE ZONING DOES NOT PERMIT DUPLEXES. | | | | | | 3) THE ADDITION OF ANY SQUARE FOOTAGE OR THE | | | INSTALLATION OF AN A/C UNIT ON THE EXTERIOR OF THE | | | HOUSE WILL REQUIRE TWO COPIES OF A SURVEY, LESS THAN | | | ONE YEAR OLD. | | | | | | 4) THE ADDITION OF ANY SQUARE FOOTAGE OR THE | | | INSTALLATION OF AN A/C UNIT ON THE EXTERIOR OF THE | | | HOUSE WILL NEED TO SHOW THE NEW CONSTRUCTION OR | | | INSTALLATION TO SCALE WITH SETBACK DIMENSIONS ON A SITE | | | PLAN OR MARKED UP SCALE. | | | | | | CONTACT ERIC SCHNEIDER AT (561) 822-1446. | | | |
|
|