Plan Review Details - Permit 12050524
Plan Review Stops For Permit 12050524
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-07-27 Cont ID  
Sent By jwitmer Date 2012-07-27 Time 13:02 Rev Time 0.00
Received By jwitmer Date 2012-07-27 Time 13:02 Sent To  
Notes
2012-07-27 13:03:52BUILDING PROVISO:
 SHEET A-2 NOTE 20 INDICATES A NEW SHOWER CEILING M.R.
 G.W.B. THE PLANS DO NOT INDICATE THE THICKNESS OF THE
 MOISTURE RESISTANT BYPSUM WALL BOARD NOR DO THEY
 INDICATE THE FRAMING SPACING. 2509.3. ON CEILINGS WHERE
 FRAME SPACING EXCEEDS 12 INCHES (305 MM) O.C. FOR
 1/2-INCH-THICK (12.7 MM) WATER-RESISTANT GYPSUM BACKING
 BOARD AND MORE THAN 16 INCHES (406 MM) O.C. FOR
 5/8-INCH-THICK (15.9 MM) WATER-RESISTANT GYPSUM BACKING
 BOARD.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-06-04 Cont ID  
Sent By jwitmer Date 2012-06-04 Time 12:31 Rev Time 0.00
Received By jwitmer Date 2012-06-01 Time 16:32 Sent To  
Notes
2012-06-04 12:31:36BUILDING PLAN REVIEW
 PERMIT:
 ADD:
 CONT:
 TEL: (561)###-####
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEWREVIEW
 ACTION: DENIED
  
 1) SHEET A-2:
  
 1A) NOTE #16 INDICATES THE USE OF NEW ENGINEERED WOOD
 WITH CORK UNDER LAYMENT. PLEASE PROVIDE COMPLIANCE FOR:
 1A)(1) 2010 FBC-B 603.1.2 (2) INSULATION INSTALLED
 BETWEEN A FINISHED FLOOR AND SOLID DECKING WITHOUT
 INTERVENING AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME
 SPREAD INDEX OF NOT MORE
 THAN 200.
  
 1B) (2) 2010 FBC-B 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 2) SHEET A-2 NOTE 20 INDICATES A NEW SHOWER CEILING
 M.R. G.W.B. THE PLANS DO NOT INDICATE THE THICKNESS OF
 THE MOISTURE RESISTANT BYPSUM WALL BOARD NOR DO THEY
 INDICATE THE FRAMING SPACING. 2509.3. ON CEILINGS WHERE
 FRAME SPACING EXCEEDS 12 INCHES (305 MM) O.C. FOR
 1/2-INCH-THICK (12.7 MM) WATER-RESISTANT GYPSUM BACKING
 BOARD AND MORE THAN 16 INCHES (406 MM) O.C. FOR
 5/8-INCH-THICK (15.9 MM) WATER-RESISTANT GYPSUM BACKING
 BOARD.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 6/06/12 E-MAILS FROM DESIGNER KERMIT WHITE PROVIDING
 DOCUMENTS FOR
 FLAME SPREAD & SMOKE DEVELOPMENT AND COMPLIANCE WITH
 1207.3 STRUCTURE BORN SOUNDINSULATION. OK, APPROVED FOR
 THESE COMPONENTS. JW
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-07-23 Cont ID  
Sent By rlecky Date 2012-07-23 Time 16:03 Rev Time 0.00
Received By rlecky Date 2012-07-23 Time 16:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-05-22 Cont ID  
Sent By rlecky Date 2012-05-22 Time 08:56 Rev Time 0.00
Received By rlecky Date 2012-05-22 Time 08:53 Sent To  
Notes
2012-05-22 08:57:24MAXIMUM OVERCURRENT PROTECTION FOR 3/0 ALUMINUM FEEDERS
 IS 155 AMPS. NEC T. 310.16
 NON METALLIC SHEATHED CABLE (SEE PLAN NOTE 5) IS NOT
 ACCEPTABLE FOR TYPE I AND TYPE II CONSTRUCTION. NEC
 334.12
 JACUZZI/ HOT TUB REQUIRE GFCI PROTECTION. NEC 680.43(A)
 LIGHTING OUTLETS ABOVE HOT TUB MUST BE GFCI PROTECTED
 AND SUITABLE FOR DAMP LOCATIONS. NEC 680.43 (B)
 ADD GFCI PROTECTED KITCHEN COUNTER TOP RECEPTACLES AT
 THE SPACES SEPARATED BY APPLIANCES AND SINKS AND SO
 THAT NO POINT ALONG THE COUNTER IS MORE THAN 24 INCHES
 FROM A RECEPTACLE. NEC 210.52 (C)
  
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-07-27 Cont ID  
Sent By jwitmer Date 2012-07-27 Time 13:30 Rev Time 0.00
Received By jwitmer Date 2012-07-13 Time 09:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-06-13 Cont ID  
Sent By lwagner Date 2012-06-13 Time 12:15 Rev Time 0.00
Received By hmoser Date 2012-05-18 Time 14:25 Sent To  
Notes
2012-05-18 14:25:56INCOMING SENT TO B04. JW

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2012-07-27 Cont ID  
Sent By jwitmer Date 2012-07-27 Time 13:29 Rev Time 0.00
Received By jwitmer Date 2012-07-27 Time 13:29 Sent To  
Notes
2012-07-27 13:30:09SEE MECHANICAL PERMIT 12070543 FOR APPROVAL. JW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-06-13 Cont ID  
Sent By hmoser Date 2012-06-13 Time 12:15 Rev Time 0.00
Received By hmoser Date 2012-06-13 Time 12:10 Sent To  
Notes
2012-06-13 12:15:26NO MECHANICAL PLANS SUBMITTED IN PACKAGE
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-06-13 Cont ID  
Sent By lwagner Date 2012-06-13 Time 10:24 Rev Time 0.00
Received By lwagner Date 2012-06-13 Time 10:14 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2012-05-31 Cont ID  
Sent By aaponte Date 2012-05-31 Time 14:16 Rev Time 0.00
Received By aaponte Date 2012-05-31 Time 14:16 Sent To  
Notes
***NONE***