Plan Review Details - Permit 12050519
Plan Review Stops For Permit 12050519
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-08-24 Cont ID  
Sent By jwitmer Date 2012-08-24 Time 12:47 Rev Time 0.00
Received By jwitmer Date 2012-08-24 Time 12:47 Sent To  
Notes
2012-08-24 12:47:31BUILDING PROVISO:
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) 8/24/12 AS PER DISCUSSION WITH HENRY SHAWAH WITH
 WHITING-TURNER SINCE THE WIND PRESSURES ARE CODE
 COMPLIANT, THE PRODUCT APPROVALS WILL COME IN AT A
 LATER DATE, TO BE REVIEWED AS A REVISION UNDER SEPERATE
 REVIEW AND ASSOCIATED FEES.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-08-24 Cont ID  
Sent By jwitmer Date 2012-08-24 Time 11:47 Rev Time 0.00
Received By jwitmer Date 2012-08-24 Time 11:47 Sent To  
Notes
2012-08-24 12:07:29BUILDING PLAN REVIEW
 PERMIT: 12050519
 ADD: 4847 FRED GLADSTONE DR
 CONT: THE WHITING TURNER CO.
 TEL: (954)776-0800/ HENRY SHAWAH
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 1) COMPLIED.
  
 2) 2ND REQUEST, 2A) THE PRODUCT APPROVALS SUBMITTED,
 NONE OF THE PRODUCT APPROVALS PROVIDED THE TECHNICAL
 SHEETS, AND CAN NOT BE EVALUATED FOR CODE COMPLIANCE
 FOR WIND, COMPONENTS AND CLADDING AND PROTECTION OF
 OPENINGS PER 2010 FBC-B 106.3.3, 1609.1.2(1).
  
 2B) THE PRODUCT APPROVALS SUBMITTED 2 INDICATE THEY ARE
 NON-IMPACT RATED, IT CAN NOT BE DETERMINED FROM THE
 PLANS IF THESE WINDOWS AND DOORS ARE INTERIOR GLAZING
 UNITS OR IF THE DESIGNER IS PLANNING TO USE NOA
 08-0528.01 SLIDING DOOR W/ BREAK-A-WAY & NOA 08-0715.14
 YKK STOREFRONT NON-IMPACT RATED AS EXTERIOR GLAZING
 UNITS. SEE 2010 FBC-B 1609.1.2(1) PROTECTION OF WINDOWS
 FOR OPENINGS FROM GRADE TO THE 30'-0" ELEVATION. IF
 STORM SHUTTERS ARE TO BE IMPLEMENTED PLEASE REVIEW :
  
 PLEASE NOTE: 104.6*/ 1609.1.4/ 1714.5 STANDARDS FOR
 WIND-BORNE DEBRIS IMPACT PROTECTION QUESTION# 13
 RECOGNIZING SUCH CONCERNS AS ABSENTEE OWNERS, OR CASES
 WHERE LONGER TIME & EFFORT IS NECESSARY TO SECURE
 SHUTTERS ON LARGE OR MULTI-STORY BUILDINGS, WHAT
 MEASURES ARE BEING RECOMMENDED OR IMPLEMENTED TO ENSURE
 THAT COMPLETE INSTALLATION OR SECURING IS DONE
 SUFFICIENTLY IN ADVANCE OF THE HURRICANE?
  
 IN MATTERS CONCERNING PUBLIC SAFETY, HEALTH, AND THE
 GENERAL WELFARE NOT SPECIFICALLY ADDRESSED IN THE CODE,
 SECTION 104.6 OF THE FLORIDA BUILDING CODE, BUILDING,
 CHAPTER 1,
 ADMINISTRATIVE CODE2004 EDITION AS AMENDED BY THE CITY
 OF WEST PALM BEACH, PROVIDES THE ABILITY FOR THE
 BUILDING OFFICIAL TO IMPLEMENT REQUIREMENTS FOR
 ENSURING STABILITY, STRENGTH, AND THE PROPER OPERATION
 OF EXISTING BUILDINGS.
  
 IN ORDER TO ASSURE THE SECURING OF SHUTTERS ON LARGE OR
 MULTI-STORY BUILDINGS, OR MULTIPLE
 ON THE SAME PROPERTY, PRE-STORM PREPARATION PLANS MUST
 BE SUBMITTED BY THE PROPERTY OWNERS OR MANAGING AGENTS
 FOR REVIEW BY THE CONSTRUCTION SERVICES DEPARTMENT. ANY
 SUCH PLAN SHALL INCLUDE, AT A MINIMUM, ON SITE LOCATION
 OF THE SHUTTERS, PARTY RESPONSIBLE FOR SECURING THE
 SHUTTERS ( SAID PARTY MUST BE LOCATED WITHIN PALM BEACH
 COUNTY), TOTAL NUMBER OF OPENINGS TO BE PROTECTED AND
 THE TOTAL TIME REQUIRED TO SECURE ALL OPENINGS.
 PROTECTION OF OPENINGS SHALL BE ACCOMPLISHED WITHIN
 TWELVE (12) HOURS OR LESS OF THE
 OFFICIAL NOTIFICATION BY THE NATIONAL WEATHER SERVICES
 OF A HURRICANE WATCH.
  
 PROVISIONS IN THE BUILDING CODES (AND THIS STANDARD)
 ARE NOT INTENDED TO PROHIBIT THE USE OF ALTERNATE
 MATERIALS AND METHODS, AND THE BUILDING OFFICIAL TO
 REVIEW AND APPROVE ANY ALTERNATE DEEMED EQUIVALENT IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE RESISTANCE,
 DURABILITY AND SAFETY PRESCRIBED BY THIS CODE. BASED
 UPON THIS CODE PROVISION, ACCEPTANCE OF ALTERNATE
 MATERIALS AND METHODS MAY BE APPROVED ON A CASE-BY-CASE
 BASIS AND SHALL REQUIRE SUFFICIENT EVIDENCE OR PROOF TO
 SUBSTANTIATE ANY CLAIM MADE REGARDING THE ALTERNATE.
  
 IN LEA OF LARGE MISSILE IMPACT RATED WINDOWS, STORM
 SHUTTERS MAY BE USED ON THE FIRST FLOOR IF: 104.6*/
 1609.1.4/ 1714.5 STANDARDS FOR WIND-BORNE DEBRIS IMPACT
 PROTECTION.
  
 2C) IF STORM SHUTTERS ARE GOING TO BE INSTALLED PLEASE
 COMPLY WITH:PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH SPECIFIC
 ANCHORS AND MOUNTING TO BE USED FOR ALL NON-IMPACT
 GLAZING. FBC 1609.1.4.
  
 FL BLD CODE 2004 SECTION 106.3.3,
 1609.1.4, 1714.5.1 & EXIST BUILD CODE 507.3.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION SCHEDULE
 SUMMARIZING & IDENTIFYING OPENING SIZES, STORY HEIGHTS,
 UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM BAR
 REINFORCING REQUIREMENTS, WALL PRESSURE ZONES, SLAT
 TYPES, ETC., SHALL BE SUBMITTED AT TIME OF PERMIT
 APPLICATION TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 COMMENT FROM 1ST REVIEW. SHEET R-A621 INDICATES THE
 WINDOW SIZES BUT NO PRODUCT APPROVALS WERE SUBMITTED
 INDICATING COMPLIANCE WITH THE 2010 EXISTING BUILDING
 CODE SECTION 606.4 REPLACEMENT OF WINDOWS. REPLACEMENT
 OF WINDOWS AND DOORS. THE REPLACEMENT OF GARAGE DOORS,
 EXTERIOR DOORS, SKYLIGHTS, OPERATIVE AND INOPERATIVE
 WINDOWS SHALL BE DESIGNED AND CONSTRUCTED TO COMPLY
 WITH CHAPTER 16 OF THE FLORIDA BUILDING CODE, BUILDING
 . 1609.1.2 PROTECTION OF OPENINGS &1609. 6.4.4.1
 COMPONENTS & CLADDING,
  
 2010 FBC 107.3.4.1* THOSE PRODUCTS THAT ARE REGULATED
 BY DCA RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO THE
 SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015
 (2) THE ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND
 REVIEWING ALL PROJECT DATA, REPORTS, SHOP DRAWINGS
 ETC..
  
 3) 2010 FBC-B 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)
 (B) WINDOWS
 (E) SHUTTERS
 (G) PRE-ENGINEERED A/C STANDS
  
 4) SEMI-COMPLIED.
  
 5) COMPLIED.
  
 6) COMPLIED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-07-05 Cont ID  
Sent By jwitmer Date 2012-07-05 Time 14:15 Rev Time 0.00
Received By jwitmer Date 2012-06-07 Time 12:19 Sent To  
Notes
2012-07-05 15:28:33BUILDING PLAN REVIEW
 PERMIT: 12050519
 ADD: 4847 FRED GLADSTONE DR
 CONT: THE WHITING TURNER CO.
 TEL: (561)###-####
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET S-2E CODES AND STANDARDS INDICATES THE WIND
 DESIGN CRITERIA TO BE ASCE 7-10 BLDG CAT LLL ON THE
 SAME SHEET THE WIND DESIGN CRITERIA INDICATES UNDER THE
 HEADING ALLOWABLE (NOMINAL) WIND DESIGN LOAD SCHEDULE
 INDICATES THE 2007 FBC NOT THE 2010 FBC. THE PRESSURES
 SHOULD REFLECT THE 2010 FBC, EXPOSURE C AND HEIGHT
 ADJUSTMENT FACTORS.
  
 2) 2010 WPB ADMINISTRATIVE CODE CHAPTER 1 FBC 107.3.4.1
 THE REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE
 CHARGE SHALL BE RESPONSIBLE FOR REVIEWING AND
 COORDINATING
 SUBMITTAL DOCUMENTS PREPARED BY OTHERS, INCLUDING
 PHASED AND DEFERRED SUBMITTAL ITEMS, FOR COMPATIBILITY
 WITH THE DESIGN OF THE BUILDING. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9N-3SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3) 2010 FBC-B 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)
 (B) WINDOWS
 (E) SHUTTERS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 4) 2010 FBC-B 420.4.2.5 EXTERIOR UNIT STANDARDS.
 420.4.2.5.1 ALL EXTERIOR WINDOW UNITS, SKYLIGHTS,
 EXTERIOR LOUVERS AND EXTERIOR DOOR UNITS INCLUDING
 VISION PANELS AND THEIR ANCHORING SYSTEMS SHALL BE
 IMPACT RESISTANT OR PROTECTED WITH AN IMPACT RESISTANT
 COVERING MEETING THE REQUIREMENTS OF THE TESTING
 APPLICATION STANDARDS (TAS) 201, 202, AND 203 OF THIS
 CODE IN ACCORDANCE WITH THE REQUIREMENTS OF SECTIONS
 1626.2 THRU 1626.4 OF THIS CODE. THE IMPACT RESISTANT
 COVERINGS MAY BE EITHER PERMANENTLY ATTACHED OR MAY BE
 REMOVABLE IF STORED ON SITE OF THE FACILITY.
 420.4.2.5.2 THE LOCATION OR APPLICATION OF EXTERIOR
 IMPACT PROTECTIVE SYSTEMS SHALL NOT PREVENT REQUIRED
 EXIT EGRESS FROM THE BUILDING.
 420.4.2.5.3 WHEN NOT BEING USED TO PROTECT THE WINDOWS,
 THE PERMANENTLY ATTACHED IMPACT RESISTANT COVERINGS
 SHALL NOT REDUCE THE PERCENTAGE OF THE CLEAR WINDOW
 OPENING BELOW THAT REQUIRED BY THIS CODE FOR THE
 PATIENT ROOM.
  
 5) MECHANICAL SHEET E-M204 DETAIL # 1 THE PLANS DO NOT
 INDICATE WHAT MATERIALS THE NEW CURB EXTENSION WILL BE
 MADE FROM NOR THE ATTACHMENT TO THE EXISTING CURB NOR
 THE
 MECHANICAL EQUIPMENT ABOVE. MECHANICAL SHEET E-M301
 ROOF EXHAUST FAN DETAIL PLEASE SEE NOTE ALL ROOF
 MOUNTED EQUIPMENT MUST ADHERE TO THE CURRENT HURRICANE
 CODES REGARDING TIE DOWN & WIND RESISTANCE.
  
 6) PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN
 CONRAD AT (561) 805-6666TO SEE IF WELDING CERTIFICATES
 WOULD BE REQUIRED OR IF A RESIDENT INSPECTOR WOULD BE
 REQUIRED
 FOR ALL INTERIOR STRUCTURAL WORK INCLUDING SHORING AND
 OR RESHORING.
  
 7) SHEET S-1E IT APPEARS THE NEW W12X30 IS MISSING A
 ATTACHMENT DETAIL TO THE NEW W16X50? ADDITIONAL
 INFORMATION IS REQUIED.
 107.2.1 WPB ADMINISTRATIVE CODE INFORMATION ON
 CONSTRUCTION DOCUMENTS. SEE PROJECT DOCS FOR LOCATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-06-01 Cont ID  
Sent By rlecky Date 2012-06-01 Time 14:36 Rev Time 0.00
Received By rlecky Date 2012-06-01 Time 07:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-06-04 Cont ID  
Sent By wjolin Date 2012-06-04 Time 14:03 Rev Time 0.00
Received By wjolin Date 2012-05-31 Time 11:32 Sent To  
Notes
2012-05-31 14:07:034847 FRED GLADSTONE DRIVE
 PERMIT #12050519
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. "NO SMOKING" SIGNS SHALL
 BE PLACE THROUGHOUT THE CONSTRUCTION AND DEMOLITION
 AREAS.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 SHEET A601: NEW FIRE-RATED STAIR DOORS SHALL HAVE A
 MINIMUM FIRE-RESISTANCE OF 1-HOUR.
  
 SHEETS FP201, FP202 & FP203: SPRINKLER ZONES DO NOT
 MATCH SMOKE COMPARTMENTS. CURRENTLY THREE DIFFERENT
 FLOW SWITCHES ALL SERVE PART OF THE SAME SMOKE
 COMPARTMENT. LOCATION OF THE SPRINKLER ALARM ACTIVATION
 AND THE ABILITY TO CONVEY THE INFORMATION TO THE STAFF
 ARE CRITICAL TO A SUCCESSFULLY COORDINATED SMOKE ZONE
 FIRE RESPONSE.
  
 SHEET E502: NO FIRE ALARM NOTIFICATION APPLIANCE
 LOCATED IN PRIVATE DINING #247 OR ACTIVITY ROOM #256.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-08-24 Cont ID  
Sent By jwitmer Date 2012-08-24 Time 12:47 Rev Time 0.00
Received By jwitmer Date 2012-07-23 Time 15:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-07-05 Cont ID  
Sent By jwitmer Date 2012-07-05 Time 15:28 Rev Time 0.00
Received By jwitmer Date 2012-05-18 Time 13:59 Sent To  
Notes
2012-05-22 13:59:25DIGITAL

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-08-24 Cont ID  
Sent By rregueir Date 2012-08-24 Time 12:13 Rev Time 0.00
Received By rregueir Date 2012-08-24 Time 12:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-07-02 Cont ID  
Sent By rregueir Date 2012-07-02 Time 16:24 Rev Time 0.00
Received By rregueir Date 2012-06-26 Time 16:52 Sent To  
Notes
2012-06-26 16:58:25REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2010
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M201, PROVIDE DRYER MANUFACTURER'S INSTALLATION
 INSTRUCTIONS TO SHOW THE PROPOSED EXHAUST INSTALLATION
 IS IN COMPLIANCE WITH THE DRYER MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. AT THIS TIME, THE PROPOSED
 BOOSTER FANS ARE NOT ACCEPTABLE FOR THIS APPLCATION.
 SEE FBC-M 507.1.
  
 2. PAGE M204, PROVIDE DETAIL FOR ATTACHMENT OF NEW
 ADAPTOR TO EXISTING CURB AND ATTACHMENT OF AHU TO THE
 ADAPTOR. INCLODE SIZE, TYPE, NUMBER, MATARIAL AND
 SPACING OF FASTENERS. THIS REQUIREMENT ALSO APPLIES TO
 ALL CONDENSERS AND FANS INSTALLED OUTDOORS. SEE FBC-M
 301.12
  
 3. PROVIDE COOLING AND HEATING OAD CALCULATIONS FOR ALL
 EXUIPMENT BEING NEWLY INSTALLED OR REPLACED PER FBC-EC
 SECTION 104.6.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected] ..
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-06-13 Cont ID  
Sent By lwagner Date 2012-06-13 Time 14:51 Rev Time 0.00
Received By lwagner Date 2012-05-31 Time 13:03 Sent To  
Notes
2012-06-13 14:46:20***PROVISO***
 FBC ACCESSIBILITY 2010 211.2 NO FEWER THAN TWO DRINKING
 FOUNTAINS SHALL BE PROVIDED. (HI/LO)

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2012-09-27 Cont ID  
Sent By rregueir Date 2012-09-27 Time 10:55 Rev Time 0.00
Received By rregueir Date 2012-09-27 Time 10:55 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2012-08-22 Cont ID  
Sent By eschneid Date 2012-08-22 Time 11:59 Rev Time 1.00
Received By eschneid Date 2012-08-22 Time 11:59 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2012-06-01 Cont ID  
Sent By eschneid Date 2012-05-30 Time 15:06 Rev Time 3.00
Received By eschneid Date 2012-05-30 Time 15:06 Sent To  
Notes
2012-06-01 15:45:05FAILED
  
 1) AN APPROVED MINOR PD AMENDMENT IS REQUIRED FOR THE
 CHANGES TO THE SITE AND LANDSCAPE PLANS AROUND THE
 EDWARDS BUILDING.
  
 2) A TREE ALTERATION PERMIT IS REQUIRED FOR THE TREES
 BEING REMOVED. THE REMOVED TREES SHALL BE REPLACED
 ELSEWHERE ON SITE.
  
 3) A SEPARATE LANDSCAPE PERMIT SHALL BE SUBMITTED PRIOR
 TO ZONING APPROVAL OF THIS PERMIT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.