Plan Review Details - Permit 12050518
Plan Review Stops For Permit 12050518
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-08-24 Cont ID  
Sent By jwitmer Date 2012-08-24 Time 12:41 Rev Time 0.00
Received By jwitmer Date 2012-08-24 Time 12:41 Sent To  
Notes
2012-08-24 12:46:23BUILDING PROVISO:
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) 8/24/12 AS PER DISCUSSION WITH HENRY SHAWAH WITH
 WHITING-TURNER SINCE THE WIND PRESSURES ARE CODE
 COMPLIANT, THE PRODUCT APPROVALS WILL COME IN AT A
 LATER DATE, TO BE REVIEWED AS A REVISION UNDER SEPERATE
 REVIEW AND ASSOCIATED FEES.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-08-16 Cont ID  
Sent By jwitmer Date 2012-08-16 Time 14:50 Rev Time 0.00
Received By jwitmer Date 2012-08-16 Time 13:47 Sent To  
Notes
2012-08-16 13:56:00BUILDING PLAN REVIEW
 PERMIT: 12050518
 ADD: 4847 FRED GLADSTONE RESNICK PAVILION
 CONT: THE WHITING TURNER CO.
 TEL: (954)776-0800 CONTACT HENRY SHAWAH
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) 2ND REQUEST, 2A) THE PRODUCT APPROVALS SUBMITTED,
 NONE OF THE PRODUCT APPROVALS PROVIDED THE TECHNICAL
 SHEETS, AND CAN NOT BE EVALUATED FOR CODE COMPLIANCE
 FOR WIND, COMPONENTS AND CLADDING AND PROTECTION OF
 OPENINGS PER 2010 FBC-B 106.3.3, 1609.1.2(1).
  
 2B) THE PRODUCT APPROVALS SUBMITTED 2 INDICATE THEY ARE
 NON-IMPACT RATED, IT CAN NOT BE DETERMINED FROM TTHE
 PLANS IF THESE WINDOWS AND DOORS ARE INTERIOR GLAZING
 UNITS OR IF THE DESINGER IS PLANNING TO USE NOA
 08-0528.01 SLIDDING DOOR W/ BREAK-A-WAY & NOA
 08-0715.14 YKK STOREFRONT NON-IMPACT RATED AS EXTERIOR
 GLAZING UNITS. SEE 2010 FBC-B 1609.1.2(1) PROTECTION OF
 WINDOWS FOR OPENINGS FROM GRADE TO THE 30'-0"
 ELEVATION. IF STORM SHUTTERS ARE TO BE IMPLEMENTED
 PLEASE REVIEW :
  
 PLEASE NOTE: 104.6*/ 1609.1.4/ 1714.5 STANDARDS FOR
 WIND-BORNE DEBRIS IMPACT PROTECTION QUESTION# 13
 RECOGNIZING SUCH CONCERNS AS ABSENTEE OWNERS, OR CASES
 WHERE LONGER TIME & EFFORT IS NECESSARY TO SECURE
 SHUTTERS ON LARGE OR MULTI-STORY BUILDINGS, WHAT
 MEASURES ARE BEING RECOMMENDED OR IMPLEMENTED TO ENSURE
 THAT COMPLETE INSTALLATION OR SECURING IS DONE
 SUFFICIENTLY IN ADVANCE OF THE HURRICANE?
  
 IN MATTERS CONCERNING PUBLIC SAFETY, HEALTH, AND THE
 GENERAL WELFARE NOT SPECIFICALLY ADDRESSED IN THE CODE,
 SECTION 104.6 OF THE FLORIDA BUILDING CODE, BUILDING,
 CHAPTER 1,
 ADMINISTRATIVE CODE2004 EDITION AS AMENDED BY THE CITY
 OF WEST PALM BEACH, PROVIDES THE ABILITY FOR THE
 BUILDING OFFICIAL TO IMPLEMENT REQUIREMENTS FOR
 ENSURING STABILITY, STRENGTH, AND THE PROPER OPERATION
 OF EXISTING BUILDINGS.
  
 IN ORDER TO ASSURE THE SECURING OF SHUTTERS ON LARGE OR
 MULTI-STORY BUILDINGS, OR MULTIPLE
 ON THE SAME PROPERTY, PRE-STORM PREPARATION PLANS MUST
 BE SUBMITTED BY THE PROPERTY OWNERS OR MANAGING AGENTS
 FOR REVIEW BY THE CONSTRUCTION SERVICES DEPARTMENT. ANY
 SUCH PLAN SHALL INCLUDE, AT A MINIMUM, ON SITE LOCATION
 OF THE SHUTTERS, PARTY RESPONSIBLE FOR SECURING THE
 SHUTTERS ( SAID PARTY MUST BE LOCATED WITHIN PALM BEACH
 COUNTY), TOTAL NUMBER OF OPENINGS TO BE PROTECTED AND
 THE TOTAL TIME REQUIRED TO SECURE ALL OPENINGS.
 PROTECTION OF OPENINGS SHALL BE ACCOMPLISHED WITHIN
 TWELVE (12) HOURS OR LESS OF THE
 OFFICIAL NOTIFICATION BY THE NATIONAL WEATHER SERVICES
 OF A HURRICANE WATCH.
  
 PROVISIONS IN THE BUILDING CODES (AND THIS STANDARD)
 ARE NOT INTENDED TO PROHIBIT THE USE OF ALTERNATE
 MATERIALS AND METHODS, AND THE BUILDING OFFICIAL TO
 REVIEW AND APPROVE ANY ALTERNATE DEEMED EQUIVALENT IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE RESISTANCE,
 DURABILITY AND SAFETY PRESCRIBED BY THIS CODE. BASED
 UPON THIS CODE PROVISION, ACCEPTANCE OF ALTERNATE
 MATERIALS AND METHODS MAY BE APPROVED ON A CASE-BY-CASE
 BASIS AND SHALL REQUIRE SUFFICIENT EVIDENCE OR PROOF TO
 SUBSTANTIATE ANY CLAIM MADE REGARDING THE ALTERNATE.
  
 IN LEAU OF LARGE MISSLE IMPACT RATED WINDOWS, STORM
 SHUTTERS MAY BE USED ON THE FIRST FLOOR IF: 104.6*/
 1609.1.4/ 1714.5 STANDARDS FOR WIND-BORNE DEBRIS IMPACT
 PROTECTION.
  
 2C) IF STORM SHUTTERS ARE GOING TO BE INSTALLED PLEASE
 COMPLY WITH:PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH SPECIFIC
 ANCHORS AND MOUNTING TO BE USED FOR ALL NON-IMPACT
 GLAZING. FBC 1609.1.4.
  
 FL BLD CODE 2004 SECTION 106.3.3,
 1609.1.4, 1714.5.1 & EXIST BUILD CODE 507.3.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION SCHEDULE
 SUMMARIZING & IDENTIFYING OPENING SIZES, STORY HEIGHTS,
 UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM BAR
 REINFORCING REQUIREMENTS, WALL PRESSURE ZONES, SLAT
 TYPES, ETC., SHALL BE SUBMITTED AT TIME OF PERMIT
 APPLICATION TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 COMMENT FROM 1ST REVIEW.SHEET R-A621 INDICATES THE
 WINDOW SIZES BUT NO PRODUCT APPROVALS WERE SUBMITTED
 INDICATING COMPLIANCE WITH THE 2010 EXISTING BUILDING
 CODE SECTION 606.4 REPLACEMENT OF WINDOWS. REPLACEMENT
 OF WINDOWS AND DOORS. THE REPLACEMENT OF GARAGE DOORS,
 EXTERIOR DOORS, SKYLIGHTS, OPERATIVE AND INOPERATIVE
 WINDOWS SHALL BE DESIGNED AND CONSTRUCTED TO COMPLY
 WITH CHAPTER 16 OF THE FLORIDA BUILDING CODE, BUILDING
 . 1609.1.2 PROTECTION OF OPENINGS &1609. 6.4.4.1
 COMPONENTS & CLADDING,
  
 3) 2010 FBC 107.3.4.1* THOSE PRODUCTS THAT ARE
 REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 THE SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) COMPLIED.
 5) COMPLIED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-05-31 Cont ID  
Sent By jwitmer Date 2012-05-31 Time 07:41 Rev Time 0.00
Received By jwitmer Date 2012-05-30 Time 10:37 Sent To  
Notes
2012-05-30 16:53:36BUILDING PLAN REVIEW
 PERMIT: 12050518
 ADD: 4847 FRED GLADSTONE RESNICK PAVILION
 CONT: THE WHITING TURNER CO.
 TEL: (954)776-0800 CONTACT HENRY SHAWAH
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET S-1R:
  
 1A) CODES AND STANDARDS WIND LOADS AS PER ASCE 7-10
 MISSING THE HEIGHT ADJUSTMENT FACTORS 2010 FBC-B TABLE
 1609.7(2). THIS MAY EFFECT WIND LOAD TABLE FOR ROOFS
 AND WALL WIND LOADS.
  
 1B) NOTE 2A INDICATES THE PLANS WERE DESIGNED TO FBC
 2007/09. AS OF MARCH 15/ 2012 THE STATE OF FLORIDA
 ADOPTED THE 2010 FBC PER FS 533.73.
  
 2) SHEET R-A621 INDICATES THE WINDOW SIZES BUT NO
 PRODUCT APPROVALS WERE SUBMITTED INDICATING COMPLIANCE
 WITH THE 2010 EXISTING BUILDING CODE SECTION 606.4
 REPLACEMENT OF WINDOWS. REPLACEMENT OF WINDOWS AND
 DOORS. THE REPLACEMENT OF GARAGE DOORS, EXTERIOR DOORS,
 SKYLIGHTS, OPERATIVE AND INOPERATIVE WINDOWS SHALL BE
 DESIGNED AND CONSTRUCTED TO COMPLY WITH CHAPTER 16 OF
 THE FLORIDA BUILDING CODE, BUILDING . 1609.1.2
 PROTECTION OF OPENINGS &1609. 6.4.4.1 COMPONENTS &
 CLADDING,
  
 3) 2010 FBC 107.3.4.1* THOSE PRODUCTS THAT ARE
 REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 THE SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) 2010 EXISTING BUILDING CODE LEVEL II SECTION 711.1
 ALTERATIONS SUBJECT TO THIS SHAPTER SHALL COMPLY WITH
 THE REQUIREMENTS OF THE FL BLDG CODE ENERGY
 CONSERVATION. 2010 ENERGY CODE 101.4.1 EXISTING
 BUILDINGSSHALL MEEET THE CRITERIA IN TABLE 101.4.1
 (ENERGY). RENOVATIONS FOOTNOTE "D" IS GOING TO BE THE
 TRIGGERING FACTOR SEE DEFINITIONS FOR RENOVATION AND IS
 THE RENOVATION 30% OR MORE WITHIN A YEAR PERIOD, IS
 THIS 30% OF THE ASSESSED VALUE OF THE BUILDING? IF SO
 THEN THE REQUIREMENTS OF 503, 504, 505 WOULD APPLY.
  
 5) SHEET R-A101 & R-A103 INDICATE SEMI-PRIVATE ROOMS
 ARE BEING CONVERTED TO PRIVATE ROOMS THE PLANS DO NOT
 INDICATE COMPLIANCE WITH 420.3.3 RESIDENT ROOMS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-05-31 Cont ID  
Sent By rlecky Date 2012-05-31 Time 15:31 Rev Time 0.00
Received By rlecky Date 2012-05-31 Time 14:24 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-05-31 Cont ID  
Sent By wjolin Date 2012-05-31 Time 11:31 Rev Time 0.00
Received By wjolin Date 2012-05-31 Time 08:54 Sent To  
Notes
2012-05-31 11:31:234847 FRED GLADSTONE DRIVE
 PERMIT #12050518
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 IN ADDITION TO THE FLORIDA BUILDING CODE, THE DESIGN
 SHALL CONFORM TO THE 2010 EDITION OF THE FLORIDA FIRE
 PREVENTION CODE WHICH CONTAINS THE FLORIDA 2009 EDITION
 OF NFPA 1 AND NFPA 101.
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2012-08-24 Time   Rev Time 0.00
Received By rregueir Date 2012-07-23 Time 15:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2012-06-25 Time   Rev Time 0.00
Received By rregueir Date 2012-05-18 Time 14:00 Sent To  
Notes
2012-05-22 13:27:06DIGITAL

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-08-24 Cont ID  
Sent By rregueir Date 2012-08-24 Time 09:44 Rev Time 0.00
Received By rregueir Date 2012-08-24 Time 09:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-06-25 Cont ID  
Sent By rregueir Date 2012-06-25 Time 11:36 Rev Time 0.00
Received By rregueir Date 2012-06-25 Time 11:33 Sent To  
Notes
2012-06-25 11:36:29REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2010 CODE FAMILY
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 AS OF MARCH 15, 2012, THE FLORIDA BUILDING CODE, ENERGY
 VOLUME REQUIRES COOLING AND HEATING LOAD CALCULATIONS
 FOR MECHANICAL EQUIPMENT REPLACEMENT IN EXISTING
 BUILDINGS.
 PROVIDE COOLING AND HEATING LOAD CALCULATIONS TO VERIFY
 EQUIPMENT SIZING IS IN COMPLIANCE WITH THE REQUIREMENTS
 OF THE CODE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2012-09-27 Cont ID  
Sent By rregueir Date 2012-09-27 Time 10:52 Rev Time 0.00
Received By rregueir Date 2012-09-27 Time 10:52 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2012-05-30 Cont ID  
Sent By eschneid Date 2012-05-30 Time 14:47 Rev Time 1.25
Received By eschneid Date 2012-05-30 Time 14:47 Sent To  
Notes
***NONE***