Plan Review Details - Permit 12050508
Plan Review Stops For Permit 12050508
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-06-13 Cont ID  
Sent By jgomez Date 2012-06-13 Time 16:26 Rev Time 0.00
Received By jgomez Date 2012-06-13 Time 16:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-05-21 Cont ID  
Sent By jgomez Date 2012-05-21 Time 12:38 Rev Time 0.00
Received By jgomez Date 2012-05-21 Time 12:38 Sent To  
Notes
2012-05-21 12:50:53RESIDENTIAL (R2) SHUTTERS BUILDING REVIEW COMMENTS.
 2010 FBC.
  
 1- ACCORDION SHUTTERS NOA 07-0402.06 SUBMITTED EXPIRED
 ON APRIL 13, 2012. NEED TO PROVIDE CURRENT NOA AS
 REQUIRED BY DCA RULE 9N-3. PROVIDE 2 COPIES.
  
 2- PROVIDE COMPLETE INFORMATION ON THE STORMS SHUTTERS
 INSTALLATION SCHEDULE AS REQUIRED BY SEC. 107.2.1.3 OF
 CITY AMENDMENTS TO FBC.
 A) SPECIFY THE SHUTTER GLASS SEPARATION. SEE PRODUCT
 APPROVAL FOR REQUIRED SEPARATION.
 B) SPECIFY SPECIFIC ANCHOR TO BE USED. SEE PRODUCT
 APPROVAL. NEED TO VERIFY ANCHOR SPACING.
 C) CLEARLY IDENTIFY WHICH WALL MOUNTING DETAIL IS GOING
 TO BE USED. ACCORDION SHUTTERS DRAWINGS SUBMITTED SHOW
 5 DIFFERENT WALL MOUNTING DETAILS.
 D) CLARIFY HOW OBTAINING 3" MINIMUM EDGE DISTANCE IF
 THE SHUTTERS SPAN IS THE SAME AS THE OPENING HEIGHT TO
 BE PROTECTED. IT LOOKS LIKE THE MINIMUM EDGE DISTANCE
 IS NOT ACHIEVABLE CONSIDERING THE SIZE OF THE WALL
 HEADERS AND THE FACT THAT THE EDGE DISTANCE EXCLUDES
 THE STUCCO THICKNESS.
  
 3- PROVIDE CLEAR AND LEGIBLE ACCORDION SHUTTERS
 DRAWINGS. DRAWINGS SUBMITTED ARE INCOMPLETE. DRAWINGS
 ARE CUT IN PIECES AND ARE NOT LEGIBLE. SEC. 107.2.1
 CITY AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-06-13 Cont ID  
Sent By jgomez Date 2012-06-13 Time 16:26 Rev Time 0.00
Received By jgomez Date 2012-06-13 Time 16:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-05-21 Cont ID  
Sent By jgomez Date 2012-05-21 Time 13:09 Rev Time 0.00
Received By jgomez Date 2012-05-16 Time 11:22 Sent To  
Notes
2012-05-17 11:22:51UNDER 5 K BUILDING