Plan Review Details - Permit 12050473
Plan Review Stops For Permit 12050473
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-05-24 Cont ID  
Sent By shill Date 2012-05-24 Time 12:35 Rev Time 0.00
Received By shill Date 2012-05-24 Time 12:30 Sent To  
Notes
2012-05-24 12:36:16***PROVISO***
  
 THIS PARCEL IS LOCATED IN EXPOSURE D. REVISE RAS 117
 CALCULATIONS AND PROVIDE AT INSPECTION.
  
 STRAP/NAILING FOR MITIGATION TO BE FIELD VERIFIED AT
 INSPECTION.
  
 ISSUED AT CONTRACTOR'S RISK
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-05-16 Cont ID  
Sent By shill Date 2012-05-16 Time 11:25 Rev Time 0.00
Received By shill Date 2012-05-16 Time 11:25 Sent To  
Notes
2012-05-16 11:25:48****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. PLEASE INCLUDE THE MEAN ROOF HEIGHT AND ROOF PITCH,
 FBC R 301.2. IF DESIGN PRESSURES ARE NOT PROVIDED PER
 ASCE7-10, TABULAR VALUES WILL BE USED. NOTE THAT THIS
 PARCEL REQUIRES WIND DESIGN CRITERIA OF 170MPH EXPOSURE
 D. ***PLEASE ADVISE ENGINEER THAT THIS IS EXPOSURE D***
  
 2. PROPOSAL STATES THAT POLY FOAM WILL BE USED FOR THE
 TILE ROOF; PLEASE PROVIDE PRODUCT APPROVAL, FAC9N-3.
  
 3. ENGINEERING REQUIRED FOR ENHANCED FASTNING FOR THE
 FLAT DECK, SEE GENERAL LIMITATION #7 ON THE LAST PAGE
 OF THE MIAMIDADE NOA.
  
 4. PROVIDE SQUARE FOOT AREA OF EACH ROOF TYPE, FBC
 108.3.
  