| 2012-06-05 11:39:40 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS. |
| | 2010 FBC, 2010 FLORIDA RESIDENTIAL CODE. |
| | |
| | 1- INFORMATION SUBMITTED IS NOT ADEQUATE FOR PLAN |
| | REVIEW. IS MISSING ALL THE STRUCTURAL INFORMATION |
| | REQUIRED TO DETERMINE IF THE STRUCTURE MEETS THE DESIGN |
| | LOADS REQUIRED BY SEC. R301. ACCORDING TO THE |
| | INFORMATION SUBMITTED, THE STRUCTURE IS GOING TO BE |
| | INSTALLED ON PILINGS AND THE STRUCTURE IS NOT |
| | COMPLETELY ENCLOSED. PROVIDE COMPLETE ENGINEER PLANS |
| | SHOWING A COMPLETE LOAD PATH THAT MEETS ALL THE |
| | REQUIREMENTS FOR THE TRANSFER OF ALL THE LOADS FROM |
| | THEIR POINT OF ORIGIN THROUGH THE LOAD-RESISTING |
| | ELEMENTS TO THE FOUNDATION. SPECIFY TYPE AND SIZE OF |
| | ALL FRAMING MEMBERS. PLANS NEED TO BE SIGNED AND SEALED |
| | BY PROFESSIONAL ENGINEER OR ARCHITECT AS REQUIRED SEC. |
| | 107.1 CITY AMENDMENTS TO FBC. |
| | |
| | 2- PROVIDE 2 COMPLETE SETS OF PLANS SHOWING ALL THE |
| | INFORMATION REQUIRED BY SEC. R301 OF THE 2010 FLORIDA |
| | RESIDENTIAL CODE: |
| | A) ALL LIVE LOADS. |
| | C) ALL DEAD LOADS. |
| | D) ALL WIND LOADS. |
| | E) ALL ROOF LOADS. |
| | F) ALL COMPONENTS AND CLADDING WIND PRESSURES. |
| | G) BUILDING EXPOSURE AND WIND LOADS (ULTIMATE WIND LOAD |
| | AND NOMINAL WIND LOAD). |
| | H) MAKE REFERENCE TO THE 2010 FBC, WHICH IS THE CURRENT |
| | CODE. |
| | |
| | 3- PROVIDE COMPLETE FLOOR PLAN WITH COMPLETE |
| | DIMENSIONS. PROVIDE COMPLETE FLOOR FRAMING AND ROOF |
| | FRAMING PLAN SPECIFYING ALL STRUCTURAL CONNECTORS AND |
| | SPECIFYING ALL UPLIFT LOADS. PROVIDE DOOR FRAMING |
| | DETAILS. PROVIDE WALL SECTION FROM FOUNDATION THROUGH |
| | ROOF AS REQUIRED BY SEC. 107.3.5.3(5) |
| | |
| | 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) EXTERIOR DOOR AS SHOWN ON PLANS. |
| | B) 5V CRIMP AND FIBERGLASS ROOF AS SPECIFIED ON PLANS. |
| | C) ALL STRUCTURAL CONNECTORS SPECIFIED ON PLANS AND |
| | DETAILS. |
| | |
| | 5- DESIGN PROFESSIONAL OF RECORD TO REVIEW AND APPROVE |
| | IN WRITING (NOT SIGNING AND SEALING) ALL PRODUCT |
| | APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS |
| | TO FBC. |
| | |
| | 6- CLARIFY/SPECIFY HEIGHT OF FLOOR TO THE FINISH GRADE |
| | AT WORKOUT AREA TO VERIFY COMPLIANCE WITH GUARDS |
| | REQUIREMENTS OF SEC. R312. |
| | |
| | 7- PROVIDE COMPLETE INFORMATION SHOWING COMPLIANCE WITH |
| | THE PROTECTION OF WOOD AS REQUIRED BY SEC. R317. |
| | |
| | 8- PROVIDE COMPLETE INFORMATION SHOWING COMPLIANCE WITH |
| | THE PROTECTION AGAINST TERMITES AS REQUIRED BY SEC. |
| | R318. |
| | |
| | 9- VALUE DECLARED IN THE PERMIT APPLICATION IS VERY |
| | LOW. SEC. 109.3 CITY AMENDMENTS. VALUATION TO INCLUDE |
| | ALL THE LABOR, MATERIALS, LAND PREPARATION, |
| | PROFESSIONAL DESIGN FEES, OVERHEAD AND PROFIT, ETC. |
| | REVISE VALUATION AS REQUIRED. |
| | |
| | 10- SEPARATE PERMITS ARE REQUIRED FOR THE ROOFING AND |
| | ELECTRICAL WORK. OWNER/BUILDER MAY SIGN OFF ON THE |
| | PERMIT APPLICATION FOR THESE PERMITS OR SEPARATE |
| | LICENSED CONTRACTORS MAY APPLY FOR THEIR SUB-PERMITS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |