| 2012-05-16 16:42:49 | RESIDENTIAL (R3) REVISION, BUILDING REVIEW COMMENTS. |
| | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| | |
| | 1- REVISION FEES NEED TO BE PAID. |
| | |
| | 2- DCA RULE 9N-3. PLEASE PROVIDE PRODUCT APPROVAL COVER |
| | PAGE FOR: |
| | A) JELD-WEN CUSTOM CLAD CASEMENT WINDOW. ONLY THE |
| | DRAWINGS WERE SUBMITTED, BUT THERE IS NOT COVER PAGE |
| | SHOWING IF IT WAS APPROVED OR NOT. |
| | |
| | B) JELD-WEN CUSTOM COLLECTION ALUMINUM CLAD INSASH |
| | CASEMENT WINDOW. SEE COMMENT 1(A) ABOVE. |
| | |
| | C) MULLIONS NOA 10-1115.03: CLEARLY SPECIFY MULLION |
| | SIZE AND NUMBER OF MULLIONS. SINGLE MULLIONS CAN'T BE |
| | USED FOR DOOR INSTALLATION BECAUSE THE MAXIMUM MULLION |
| | SPAN FOR SINGLE MULLION IS 72". SEE DESIGN SCHEDULE ON |
| | SHEET 6 OF NOA SUBMITTED. |
| | |
| | 3- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS PRIOR |
| | TO SUBMITTAL TO THIS OFFICE. SEC. 106.3.3 OF CITY |
| | AMENDMENTS TO FBC. |
| | |
| | 4- THERE ARE 2 DIFFERENT FLOOR PLANS SUBMITTED. ONE IS |
| | COMING FROM REG ARCHITECTS AND THE OTHER ONE IS AN |
| | SKETCH. THEY DON'T MATCH. CLARIFY WHICH IS THE CORRECT |
| | ONE. |
| | |
| | 5- FOR YOUR INFORMATION ONLY: REPLACEMENT OF WINDOWS |
| | AND DOORS REQUIRE BUCK INSPECTION. MAKE SURE |
| | INSPECTIONS ARE PROPERLY SCHEDULED TO AVOID ANY DELAYS |
| | OR CONFLICTS WITH THE INSTALLATION. |
| | |