Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-05-18 Cont ID  
Sent By jwitmer Date 2012-05-18 Time 14:07 Rev Time 0.00
Received By jwitmer Date 2012-05-18 Time 12:04 Sent To  
Notes
2012-05-18 13:00:27BUILDING PLAN REVIEW
 PERMIT: 12050138
 ADD: 477 S ROSEMARY # 320
 CONT: STRATICON
 TEL: (561)927-1845
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A-1 & LS-1 INDICATE THE OCCUPANCY AS A
 BUSINESS OCCUPANCY, THIS IS CORRECT FOR EDUCATIONAL
 USAGE ABOVE THE 12TH GRADE. WHERE WE DISAGREE IS HOW WE
 DETEWRMINE THE OCCUPANT LOAD. THE CODE COMMENTARY IN
 REGARDS TO FBC-B TABLE 1004.1.1 INDICATES THAT ALTHOUGH
 THIS IS CLASSIFIED AS A BUSINESS OCCUPANCY WE STILL GO
 TO TABLE 1004.1 FOR THE INTENDED USAGE. I BELIEVE THE
 OPEN LAB SHOULD BE TAKEN WITH THE SQUARE FOOTAGE FOR
 SHOPS AND VOCATIONAL TRAINING ROOMS OR (50 NET), THIS
 ROOM IS APPROX 1027 SQ FT OR AN OCCUPANT LOAD OF
 21OCCUPANTS THE OTHER AREA OF DISCREPANCY IS THE
 CLASSROOM 320H WHICH IS A CLASSROOM OR (20 NET) THE
 ROOM SIZE BEING APPROX. 800 SQ FT OR AN OCCUPANT LOAD
 OF 40.
  
 THE BREAK ROOM AND CRITIQUE LOUNGE AREAS SHOULD BE
 TAKEN AT 15 SQ FT PER OCCUPANT (NET) AND THE OFFICES AS
 100 SQ FT PER OCCUPANT.(GROSS) PER TABLE 1004.1.1. THE
 NET CALCULATION ALLOWS THE DESIGNER TO FIGURE THE
 OCCUPANT LOAD TO THE ACTUAL OCCUPIED FLOOR AREAS. THE
 AREAS USED FOR PERMANENT BUILDING COMPONENTS, SUCH AS
 WALLS, FIXED EQUIPMENT, THICKNESSES OF WALLS,
 CORRIDORS, RESTROOMS, MECHANICAL ROOMS, AND CLOSETS, IS
 NOT TO BE INCLUDED IN NET FLOOR AREA, SEE 2010 CODE
 COMMENTARY UNDER TABLE 1004.1.1.
  
 PLEASE NOTE THAT THE TOTAL OCCUPANT LOAD MAY STILL BE
 ABOVE 49 OCCUPANTS WHEN THE NET AREAS REDUCED AREAS ARE
 REMOVED FROM THE EQUATION. IF SO THE TWO REMOTE EGRESS
 OPENINGS WILL MEET THE 2010 FBC-B TABLE 1015.1 AND
 1015.2.1 DOORWAYS TO BE 1/3 THE DIAGONAL DISTANCE
 APART.
  
 2) 2010 FBC-B 712.6 FIRE WALLS, FIRE BARRIERS, FIRE
 PARTITIONS, SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY
 OTHER WALL REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY
 HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE
 ANY DECORATIVE CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: "FIRE
 AND SMOKE BARRIER - PROTECT ALL OPENINGS."
  
 3) THE PLANS INDICATE ALL EXIT DOORS SWINGING INTO THE
 CORRIDOR, PLEASE PROVIDE TYPE OF DOORS AND FIRE RATINGS
 NO DOOR SCHEDULE WAS PROVIDED. 2010 FBC-B TABLE 715.4.
  
 4) PLEASE PROVIDE CODE COMPLIANCE FOR THE FRONT ENTRY
 DOUBLE DOORS, 2010 FBC-B1008.1.9.3.(3).
  
 5) PLEASE PROVIDE THE TYPE OF LATCHING MECHANISM TO BE
 INSTALLED ON THE EGRESS DOORS? 2010 FBC-B 1008.
  
 6) NO DETAILS OF HANDICAPPED RESTROOMS WERE SUBMITTED
 UNDER THE FIRST PLAN REVIEW. 2010 FBC-B
 106.3.5.1.1(10)*
  
 7) THERE ARE AREAS THAT DO NOT INDICATE USE OF ROOMS
 WITH BI-FOLD DOORS AND AREA WITH JUST A HEADER
 INDICATED? 106.1.2 ADITIONAL INFORMATION REQUIRED?
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-05-30 Cont ID  
Sent By rlecky Date 2012-05-30 Time 12:43 Rev Time 0.00
Received By rlecky Date 2012-05-30 Time 11:35 Sent To  
Notes
2012-05-30 12:51:4312050398
 477 S. ROSEMARY AVE #320-328
  
 VERIFY THE WORKING CLEARANCES IN THE ELECTRICAL
 EQUIPMENT ROOMS ARE ADEQUATE FOR THE NEW EQUIPMENT. NEC
 110.26
  
 INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE
 NEW SERVICE, SWITCH GEAR AND ELECTRIC PANELS. NEC
 110.9, 110.10
  
 PLANS ARE UNCLEAR AS TO WIRING METHODS PROPOSED WITHIN
 THE IT ROOM - 320B. IS IT INTENDED THAT THIS ROOM BE
 TREATED AS AN INFORMATION TECHNOLOGY EQUIPMENT ROOM
 WITH A DISCONNECTING MEANS, RAISED FLOORS AND RATED
 WALLS? NEC ARTICLE 645
  
 VERIFY THE ILLUMINATION AND BRIGHTNESS IN THE
 CLASSROOMS MEETS ENERGY CODE REQUIREMENTS. FBC 443.3.7
  
 PROVIDE A SEPARATE PERMIT AND PLANS FOR THE IT ROOM
 FIRE SUPPRESSION SYSTEM
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-06-29 Cont ID  
Sent By ddaniels Date 2012-06-29 Time 13:47 Rev Time 0.00
Received By ddaniels Date 2012-06-29 Time 13:42 Sent To  
Notes
2012-06-29 14:40:096/28/2012 PLANS REVIEWED BY FIRE ***DENIED***
 PERMIT #12050398
  
 1. DESIGN SHALL CONFORM TO THE 2010 EDITION OF THE
 FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE FLORIDA
 EDITION OF NFPA 1 AND NFPA 101.
 2. SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
 3. PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY
 TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS,
 EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF
 TRAVEL ETC.
 4. PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
  
 DERRICK L. DANIELS, BATTALION CHIEF / FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 OFFICE OF THE FIRE MARSHAL
 (561) 805-6722
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2012-06-29 Time   Rev Time 0.00
Received By rregueir Date 2012-05-15 Time 16:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-06-29 Cont ID  
Sent By rregueir Date 2012-05-30 Time 08:53 Rev Time 0.00
Received By rregueir Date 2012-05-16 Time 16:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-05-17 Cont ID  
Sent By lwagner Date 2012-05-17 Time 14:06 Rev Time 0.00
Received By lwagner Date 2012-05-17 Time 13:52 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2012-06-05 Cont ID  
Sent By eschneid Date 2012-06-05 Time 19:18 Rev Time 0.50
Received By eschneid Date 2012-06-05 Time 19:18 Sent To  
Notes
2012-06-05 19:25:12FAILED
  
 1) THE CITYPLACE DRI REQUIRES THAT MECHANICAL EQUIPMENT
 BE SCREENED. PLEASE PROVIDE DETAILS ON HOW THE NEW ROOF
 TOP CONDENSERS AT APPROXIMATELY 5 FEET IN HEIGHT WILL
 BE SCREENED FROM VIEW.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.