Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-05-16 Cont ID  
Sent By shill Date 2012-05-16 Time 10:16 Rev Time 0.00
Received By shill Date 2012-05-16 Time 10:16 Sent To  
Notes
2012-05-16 10:17:49170MPH EXPOSURE B
 V(ASD) DP ZONE 2 -52.5
 4' PARAPET, 20MRH
 SEE ASCE7-10 FIGURE 30.6-1, ZONE 3 TREATED AS ZONE 2
 WHEN PARAPET > 3'
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-05-15 Cont ID  
Sent By shill Date 2012-05-15 Time 16:17 Rev Time 0.00
Received By shill Date 2012-05-15 Time 16:17 Sent To  
Notes
2012-05-15 16:20:38****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
  
 1. PROVIDE THE MEAN ROOF HEIGHT AND PARAPET HEIGHT IN
 ORDER TO DETERMINE WIND DESIGN PRESSURES, FBC R 301.2.
  
  
  