Plan Review Details - Permit 12050341
Plan Review Stops For Permit 12050341
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-09-17 Cont ID  
Sent By jwitmer Date 2012-09-17 Time 12:03 Rev Time 0.00
Received By jwitmer Date 2012-09-17 Time 10:38 Sent To  
Notes
2012-09-17 12:03:37SEPT. 17/ 2012
 CONDITIONAL APPROVAL:
 THIS PERMIT IS BING ISSUED UNDER SPECIFIC CONDITIONS,
 LETTER SIGNED BY OWNER AND CONTRACTOR.
  
 LETTER FOR SPENDING OF FUNDS FOR ACCESSIBILITY AND
 DISPROPORTIONATE COST
 MIKE LANG GENERAL CONTRACTOR AND P E THOMAS TWOMEY
  
 SEPT. 25/ 2012
  
 BUILDING PLAN REVIEW
 PERMIT:12050341
 ADD: 1711 LONGWOOD RD
 CONT: MIKE T LANG
 TEL: (561)262-0915
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2010 CHAPTER 1 ADMINISTRATIVE CODE 105.13.
 SPECIAL PHASED PERMIT APPROVAL
  
 AFTER SUBMITTAL OF THE APPROPRIATE CONSTRUCTION
 DOCUMENTS, THE BUILDING OFFICIAL IS AUTHORIZED TO ISSUE
 A PERMIT FOR THE CONSTRUCTION OF FOUNDATIONS OR ANY
 OTHER PART OF A BUILDING OR STRUCTURE BEFORE THE
 CONSTRUCTION DOCUMENTS FOR THE WHOLE BUILDING OR
 STRUCTURE HAVE BEEN SUBMITTED. THE HOLDER OF SUCH
 PERMIT FOR THE FOUNDATION OR OTHER PARTS OF A BUILDING
 OR STRUCTURE SHALL PROCEED AT THE HOLDER'S OWN RISK
 WITH THE BUILDING OPERATION AND WITHOUT ASSURANCE THAT
 A PERMIT FOR THE ENTIRE STRUCTURE WILL BE GRANTED.
 CORRECTIONS MAY BE REQUIRED TO MEET THE REQUIREMENTS OF
 THE TECHNICAL CODES. THIS PROVISION IS ONLY FOR THE
 FLORIDA BUILDING CODE, ALL OTHER AGENCY APPROVALS
 NECESSARY FOR CONSTRUCTION MUST BE SECURED PRIOR TO
 THIS PROVISION BEING APPLIED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-05-31 Cont ID  
Sent By jwitmer Date 2012-05-31 Time 13:11 Rev Time 0.00
Received By jwitmer Date 2012-05-31 Time 09:23 Sent To  
Notes
2012-05-31 09:31:11BUILDING PLAN REVIEW
 PERMIT:12050341
 ADD: 1711 LONGWOOD RD
 CONT: MIKE T LANG
 TEL: (561)262-0915
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE COVER SHEET INDICATES THIS PROJECT WITH THE MAIN
 OCCUPANCY TYPE BEING A F1 OCCUPANCCY. TO DETERMINE IF
 THIS IS A F1 OR A F2 OCCUPANCY A DESCRIPTION OF THE
 PROCESS THAT IS TO TAKE PLACE WOULD BE HELPFULL, PLANS
 INDICATE TTHE USE OF A MACHINE SHOP WHICH WORKS WITH
 METALS, SECTION 306.3 OF THE FBC-B INDICATES THAT METAL
 PRODUCTS THE FABRICATION & ASSEMBLY OF METAL PRODUCTS.
  
 2) IF THIS PLAN IS TO BE CONSIDERED A F2 OCCUPANCY THEN
 THEN THIS REVIEW WILL NEED TO CONSIDER THIS A MIXED USE
 BUILDING SINCE THE ACCESSORY OCCUPANCIES COVERS OVER
 10% OF THE BUILDING (FLOOR) AREA. THE DESIGNER WILL
 NEED TO CONSIDER SEPERATED OR NON-SEPERATED
 OCCUPANCIES, SEE 508.3 & 508.4 ANAD TABLE 508.4 FOR
 RATING OF OCCUPANCY SEPERATION WALLS.
  
 3) IF THE DESIGNER OF RECORD DECIDES TO HAVE SEPERATED
 OCCUPANCIES WITH ASSOCIATED RATED WALLS THEN OPENING
 PROTECTIVES WILL NEED TO BE CONSIDERED FOR DOOR
 OPENINGS WITHIN THE WALL PER TABLE 715.4.
  
 4) THE MANUFACTURING PROCESS OF FACTORY PROCESS IS
 UNKNOWN AT THIS TIME, A LIST OF MATERIALS THAT WILL BE
 USED IN THE MANUFACTURING PROCESS AND MSDS SHEETS WILL
 BE REQUIRED BEFORE A THROROUGH REVIEW CAN TAKE PLACE.
 PLEASE NOT THAT THE MACHINE SHOPS MAY BE CONSIDERED A
 HAZARDOUS OCCUPANCY OR POSSIBLY JUST CONTROLED AREAS
 DEPENDING ON THE AMOUNT OF FIRE OR EXPLOSIVE HAZARD IS
 ASSOCIATED WITH PROCESSING. PLEASE REVIEW COMBUSTIBLE/
 FLAMMABLE DUST , (ALUMINUM FILINGS) TABLE 414 FOOTNOTES
 A & C.
  
 5) MACHINE SHOP 2 & 3 BOTH HAVE PROBLEMS WITH EXITING,
 THE PLANS SHOW EXITING THROUGH WHAT APPEARS TO BE A
 OVERHEAD DOOR. PLEASE REVIEW FBC-B 1008.1.2 DOORS MUST
 BE SIDE SWINGING.
  
 6) SHEET A-6 INDICATES WHAT APPEARS TO BE TWO MEZZANINE
 AREAS:
  
 6A) THE PLANS INDICATE THIS BUILDING TO BE A TYPE IIA
 PLEASE REVIEW FBC-B 603.1.1 FIRE RETARDENT TREATED WOOD
 WILL BE REQUIRED.
  
 6B) 110.4.2 STORAGE & FACTORY- INDUSTRIAL OCCUPANCIES.
 IT SHALL BE THE RESPONSIBILITY OF THE OWNER, AGENT,
 PROPIETOR OR OCCUPANT OF GROUP S AND GROUP F
 OCCUPANCIES, OR ANY OCCUPANCY WHERE EXCESSIVE FLOOR
 LOADING IS LIKELY TO OCCUR, TO EMPLOY A COMPETENT
 ARCHITECT OR ENGINEER IN COMPUTING THE SAFE FLOOR LOAD
 CAPACITY. ALL SUCH COMPUTATIONS SHALL BE ACCOMPANIED BY
 AN AFFADAVIT FROM THE ARCHITECT OR ENGINEER STATING THE
 SAFE ALLOWABLE FLOOR LOADS ON EACH FLOOR IN POUNDS PER
 SQ FT.THE
 COMPUTATIONS & AFFADAVIT SHALL BE FILED AS A PERMANENT
 RECORD OF THE BLDG DEPT.
  
 6C) 110.4.3.SIGNS REQUIRED. IN EVERY BUILDING OR PART
 OF A BUILDING USED FOR STORAGE, INDUSTRIAL OR HAZARDOUS
 PURPOSES, THE SAFE FLOOR LOADS, AS REVIEWED BY THE
 BUILDING OFFICIAL ON THE PLAN, SHALL BE MARKED ON
 PLATES OF APPROVED DE SIGN WHICH SHALL BE SUPPLIED &
 SECURELY AFFIXED BY THE OWNER OF THE BUILDING IN A
 CONSPICUOUS PLACE IN EACH STORY TO WHICH THEY RELATE.
 SUCH PLATES SHALL NOT BE REMOVED OR DEFACED, & IF LOST,
 REMOVED THE OWNER OF THE BUILDING SHALL REPLACE THEM.
  
 6D) THE MEZZANINE ABOVE TTHE SHIPPING ROOM PLEASE
 PROVIDE DOCUMENTATION ON HOW THE AREA LIMITATION IN
 505.2 IS BEING MET EVEN WITH EXCEPTION # 2.
 505.2 AREA LIMITATION. THE AGGREGATE AREA OF A
 MEZZANINE OR MEZZANINES WITHIN A ROOM SHALL NOT EXCEED
 ONE-THIRD OF THE FLOOR AREA OF THAT ROOM OR SPACE IN
 WHICH THEY ARE LOCATED. THE ENCLOSED PORTION OF A ROOM
 SHALL NOT BE INCLUDED IN A DETERMINATION OF THE FLOOR
 AREA OF THE ROOM IN WHICH THE MEZZANINE IS LOCATED. IN
 DETERMINING THE ALLOWABLE MEZZANINE AREA, THE AREA OF
 THE MEZZANINE SHALL NOT BE INCLUDED IN THE FLOOR AREA
 OF THE ROOM.
 2. THE AGGREGATE AREA OF MEZZANINES IN BUILDINGS AND
 STRUCTURES OF TYPE I OR II CONSTRUCTION SHALL NOT
 EXCEED ONE-HALF OF THE FLOOR AREA OF THE ROOM IN
 BUILDINGS AND STRUCTURES EQUIPPED THROUGHOUT WITH AN
 APPROVED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH
 SECTION 903.3.1.1 AND AN APPROVED EMERGENCY VOICE/ALARM
 COMMUNICATION SYSTEM IN ACCORDANCE WITH SECTION
 907.2.12.2.
  
 7) DEPENDING ON THE OUTCOME OF OCCUPANCY TYPE, THE
 BUSINESS OCCUPANCY CAN NOT HAVE EXIT SIGNS TAKING THEM
 INTO A MORE DANGEROUS OCCUPANCY PER 1014.2.NOTE
 BUSINESS TO F1, F2 OR H IS MORE HAZARDOUS.
  
 8) SHEET A-3 ACCESSIBILITY: 202.4. DISPROPORTIONATE
 COST, PLEASE SEE DOOR TO OFFICE 106 DOES NOT HAVE THE
 REQUIRED 18" ON THE LATCH SIDE OF THE DOOR404.2.4.
  
 9) GANGED BATHROOMS WITH AN ACCESSIBLE STALL NEAR ROOM
 103 & 114 DO NOT HAVE DOORS SHOWN ON THE STALLS, DOORS
 CAN NOT SWING INTO THE CLEAR FLOOR SPACE REQUIRED FOR
 FIXTURES 604.8.2.2.
  
 10) GRAB BARS FOR RESTROOMS ARE NOW MEASURED FROM THE
 TOP OF THE BAR NOT THE CENTER, RANGE BETWEEN 33 -36
 INCHES TO TOP OF BAR.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2012-09-25 Cont ID  
Sent By rlecky Date 2012-09-25 Time 15:06 Rev Time 0.00
Received By rlecky Date 2012-09-25 Time 15:06 Sent To  
Notes
2012-09-25 15:07:55PER THE BO THIS PROJECT WILL BE PROCESSED IN PHASES AND
 THE ELECTRICAL PLAN IS TO BE UPDATED WITH UNDER ANOTHER
 PHASE. RL

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2012-09-24 Cont ID  
Sent By rlecky Date 2012-09-24 Time 11:26 Rev Time 0.00
Received By rlecky Date 2012-09-21 Time 09:46 Sent To  
Notes
2012-09-24 11:26:4412050341
 1711 LONGWOOD ROAD
 NEW ELECTRIC SYSTEM
  
 SERVICE CONDUCTORS MAY NOT BE MIXED WITHIN THE SAME
 SERVICE RACEWAY (JUNCTION BOX) AS OTHER CONDUCTORS. NEC
 230.7
  
 PANEL BOARD ?PM2? REQUIRES A LARGER FEEDER. PARALLEL
 CONDUCTORS ARE LIMITED TO 1/0 AND LARGER. NEC T.
 310.16, 310.4
  
 PROVIDE GROUNDING AND BONDING SCHEMATIC FOR THE
 SEPARATELY DERIVED SYSTEMS. NEC 250.30
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-05-15 Cont ID  
Sent By rlecky Date 2012-05-15 Time 11:44 Rev Time 0.00
Received By rlecky Date 2012-05-15 Time 10:47 Sent To  
Notes
2012-05-15 11:46:0012050341
 1711 LONGWOOD RD.
 ELECTRIC ADDITION
  
 PLEASE CLARIFY THE SCOPE OF THE ELECTRIC WORK PROPOSED.
 VERIFY THE ELECTRICAL SERVICE MAINS FOR THIS BUILDING
 ARE SIX OR LESS AND GROUPED IN ONE LOCATION. CLARIFY
 THE ELECTRICAL RISER PLAN TO SHOW ALL METERS,
 GROUNDING, MAIN DISCONNECTS AND PANEL BOARDS FOR THE
 BUILDING ACCURATELY LABELED.
 NEC 230.2, 230.71, 230.72
 INDICATE THE SIZE OF THE OVERCURRENT PROTECTION FOR THE
 FEEDERS FROM THE TRANSFORMER TO THE JUNCTION BOX.
 INDICATE THE SIZE AND LOCATION OF OVERCURRENT
 PROTECTION PROPOSED FOR THE NEW PANEL BOARDS. PROVIDE
 PANEL BOARD SCHEDULES AND LABELS FOR TRANSFORMERS AND
 PANELS WHICH MATCH THE RISER PLAN. NEC 215.5
 PROVIDE A LIGHTING DENSITY CALCULATION VERIFYING
 COMPLIANCE WITH THE 2010 FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC 505.5.3
 SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE
 CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES.
 FBC505.1, 505.2
 VERIFY THE REQUIRED WORKING CLEARANCES AND DEDICATED
 WORKING SPACE HAS BEEN PROVIDED FOR THE ELECTRICAL
 EQUIPMENT AND PANEL BOARDS. NEC 110.26, 240.24, 408.17
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-09-20 Cont ID  
Sent By ddaniels Date 2012-09-20 Time 13:44 Rev Time 0.00
Received By ddaniels Date 2012-09-20 Time 13:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-05-29 Cont ID  
Sent By wjolin Date 2012-05-29 Time 12:18 Rev Time 0.00
Received By wjolin Date 2012-05-29 Time 11:20 Sent To  
Notes
2012-05-29 12:18:431711 LONGWOOD ROAD
 PERMIT #12050341
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING
 SHALL BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR
 AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL
 HAVE "NO SMOKING" SIGNS POSTED.
  
 WHERE SMOKING IS PERMITTED, SAFE RECEPTACLES FOR
 SMOKING MATERIALS SHALL BE PROVIDED.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 ENGINEERED FIRE ALARM AND FIRE SPRINKLER CONSTRUCTION
 DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT.
 AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE
 SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS
 (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS)
 FOR A SUB-PERMIT. A FIRE ALARM SYSTEM IS REQUIRED IN
 INDUSTRIAL OCCUPANCIES WITH MORE THAN 100 PERSONS PER
 SECTION 40.3.4.1.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 THE BUILDING IS FUNCTIONING AS A MULTIUSE (BUSINESS,
 INDUSTRIAL, STORAGE, ASSEMBLY, ETC.) OCCUPANCY.
 INDICATE IF THE BUILDING IS DESIGNED FOR MIXED USE
 (NON-SEPARATED) OR SEPARATED USE PER SECTION 6.1.14.2.1
 OF NFPA 101 FLORIDA EDITION 2009.
  
 PROVIDE AN ACCURATE OCCUPANT LOAD USING THE ACTUAL USE
 OF THE SPACE TO DETERMINE TOTAL OCCUPANT LOAD. FOR
 EXAMPLE THE BREAK ROOM WOULD HAVE AN ASSEMBLY USE AND
 BE FIGURED USING AN OCCUPANT LOAD FACTOR OF 15 SQ.FT.
 PER PERSON. THE INDUSTRIAL AREAS WOULD HAVE AN OCCUPANT
 LOAD FACTOR OF 100 (NOT 200) SQ.FT. PER PERSON.
  
 CLEARLY IDENTIFY ALL NEW AND EXISTING FIRE-RATED WALLS
 AND DOORS.
  
 CLASS D TYPE PORTABLE FIRE EXTINGUISHERS WILL BE NEEDED
 FOR PROTECTING COMBUSTIBLE METALS SUCH AS ALUMINUM,
 ZINC, LITHIUM, TITANIUM ETC.
  
 EMPLOYEES IN THE ENGINEERING AND BREAKROOM HAVE ONLY
 EGRESS ROUTES THROUGH A HIGHER HAZARD AREA (MACHINE
 SHOP).
  
 MACHINE SHOP #2 SHOWS AN EXIT WITH A NON-SIDE SWINGING
 DOOR.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM THE
 EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. LOCKS,
 IF PROVIDED, SHALL NOT REQUIRE THE USE OF A KEY, TOOL,
 OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE
 EGRESS SIDE.
  
 SEVERAL DOORS ARE INDICATED AS HAVING SECURITY
 HARDWARE. INDICATE IF THESE DOORS ARE DELAYED EGRESS,
 ACCESS-CONTROLLED EGRESS, ETC. INDICATE HOW THE
 LOCKS/LATCHES ARE RELEASED FROM THE EGRESS SIDE.
  
 PROVIDE ADDITIONAL INFORMATION AND DETAILS FOR THE TWO
 WOODEN MEZZANINE TYPE SPACES.
  
 EACH SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER.
  
 PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL
 BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-09-24 Cont ID  
Sent By rlecky Date 2012-09-24 Time 11:28 Rev Time 0.00
Received By rlecky Date 2012-09-13 Time 11:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-06-07 Cont ID  
Sent By shill Date 2012-06-07 Time 17:45 Rev Time 0.00
Received By shill Date 2012-05-11 Time 10:32 Sent To  
Notes
2012-05-11 10:36:17B--20

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2012-09-25 Cont ID  
Sent By rregueir Date 2012-09-25 Time 15:29 Rev Time 0.00
Received By rregueir Date 2012-09-25 Time 15:29 Sent To  
Notes
2012-09-25 15:31:01NO MECHANICAL REVIEW AT THIS TIME. SEPERATE PLANS AND
 PERMIT APPLICATION REQUIRED FOR MECHANICAL WORK
 ASSOCIATED WITH THIS PROJECT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-09-20 Cont ID  
Sent By rregueir Date 2012-09-20 Time 16:54 Rev Time 0.00
Received By rregueir Date 2012-09-20 Time 16:50 Sent To  
Notes
2012-09-20 16:54:20REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2010
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. NO VENTIALTION INFORMATION PROVIDED. PROVIDE
 VENTILATION CALCULATIONS FOR ALL NEWLY CONSTRUCTED OR
 RECONFIGURED SPACES AS WELL AS ANY SPACES WHICH
 CONSTITUTE A CHANGE OF OCCUPANCY PER FBC-M SECTION 403.
  
 2. IT IS NOT POSSIBLE TO DETERMINE WHICH DUCTWORK IS
 NEW AND WHICH DUCTWORK IS EXISTING TO REMAIL. PLEASE
 INDICATE ON PLANS WHICH DUCTWORK WILL BE NEWLY
 INSTALLED AS PART OF THE SCOPE OF THIS WORK PER FBC-B
 106.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-09-18 Cont ID  
Sent By lwagner Date 2012-09-18 Time 09:34 Rev Time 0.00
Received By lwagner Date 2012-09-17 Time 15:27 Sent To  
Notes
2012-09-17 15:57:08***PROVISO***
 REVISION REQUIRED:
  
 THE KITCHEN SINK AND SERVICE SINK ARE SHOWN CONNECTING
 TO A WET VENT. FIXTURES OTHER THAN BATHROOM FIXTURES
 ARE REQUIRED TO CONNECT DOWNSTREAM OF THE WET VENT
 SYSTEM.
 FBC 2010 PLUMBING 909.1
 IF SYSTEM IS TO BE A CIRCUIT VENT, THEN A DRY VENT WILL
 BE REQUIRED BETWEEN THE WATER CLOSETS.
 P 911.2 VENT CONNECTION.
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-05-15 Cont ID  
Sent By lwagner Date 2012-05-15 Time 09:55 Rev Time 0.00
Received By lwagner Date 2012-05-14 Time 13:19 Sent To  
Notes
2012-05-15 09:23:09FBC 2010 PLUMBING
 FBC 2010 ACCESSIBILITY
 REVIEW #1
 DENIED:
  
 1. THE NEW MENS ROOM #120 DEOE NOT HAVE A STALL
 COMPLYING WITH FBC 2010 ACCESSIBILITY 213.3.1 TOILET
 COMPARTMENTS AND 604.8.1. SEE FIGURE 604.8.1.6
  
 2. ONE URINAL WILL BE REQUIRED TO BE MOUNTED AT A MAX.
 OF 17" AFF TO RIM.- 213.3.3
  
 3. THE CENTER OF THE HC LAV ON SHEET A-8 WILL BE 1'-3"
 IF THE STALL IS THE MIN. 7'-1"
  
 4. A HI/LO DRINKING FOUNTAIN IS LISTED ON P-1 BUT NOT
 FOUND ON THE PLUMBING DRAWING.
  
 5. HOT WATER IS REQUIRED AT THE SERVICE SINK AND
 KITCHEN SINK. FBC 2010 PLUMBING 607.1
  
 6. A VENT IS REQUIRED FOR THE GRINDER PUMP PER
 MANUFACTURERS INSTRUCTIONS.
  
 7. THE KITCHEN SINK AND SERVICE SINK ARE SHOWN
 CONNECTING TO A WET VENT. FIXTURES OTHER THAN BATHROOM
 FIXTURES ARE REQUIRED TO CONNECT DOWNSTREAM OF THE WET
 VENT SYSTEM.
 FBC 2010 PLUMBING 909.1
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 1 Status N Date 2012-05-18 Cont ID  
Sent By eschnied Date 2012-05-18 Time 14:54 Rev Time 0.25
Received By eschneid Date 2012-05-17 Time 09:38 Sent To  
Notes
2012-05-18 14:55:52INTERIOR WORK ONLY, LESS THAN 50% VALUE OF STRUCTURE.