Plan Review Details - Permit 12050317
Plan Review Stops For Permit 12050317
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-05-29 Cont ID  
Sent By shill Date 2012-05-29 Time 16:00 Rev Time 0.00
Received By shill Date 2012-05-29 Time 16:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-05-11 Cont ID  
Sent By shill Date 2012-05-11 Time 09:56 Rev Time 0.00
Received By shill Date 2012-05-11 Time 09:56 Sent To  
Notes
2012-05-11 10:40:17****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. PLEASE SEE WIND MAP, ASCE7-10 FIGURE 26.5-1A, FBC
 RESIDENTIAL FIGURE 301.2.4. WEST PALM BEACH LIES
 BETWEEN THE 160MPH AND 170MPH LINES. PLEASE REVISE WIND
 DESIGN CRITERIA.
  
 2. DESIGN PRESSURES WERE NOT PROVIDED AS V(ULT) OR
 V(ASD). R301.2.1.7, PLEASE SPECIFY.
  
  
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2012-05-10 Cont ID  
Sent By fmittner Date 2012-05-10 Time 13:53 Rev Time 0.00
Received By fmittner Date 2012-05-10 Time 13:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-05-29 Cont ID  
Sent By shill Date 2012-05-29 Time 16:00 Rev Time 0.00
Received By shill Date 2012-05-18 Time 11:48 Sent To  
Notes
2012-05-18 11:49:03INCOMING SENT TO S HILL DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-05-11 Cont ID  
Sent By shill Date 2012-05-11 Time 10:40 Rev Time 0.00
Received By shill Date 2012-05-10 Time 14:49 Sent To  
Notes
2012-05-10 14:49:43UNDER 5 K BUILDING