Plan Review Details - Permit 12050298
Plan Review Stops For Permit 12050298
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-06-11 Cont ID  
Sent By rmcdouga Date 2012-06-11 Time 13:53 Rev Time 0.00
Received By rmcdouga Date 2012-06-11 Time 12:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-05-31 Cont ID  
Sent By rmcdouga Date 2012-05-31 Time 11:24 Rev Time 0.00
Received By rmcdouga Date 2012-05-30 Time 16:55 Sent To  
Notes
2012-05-31 11:23:112010 FBC
  
 DENIED BY BUILDING
  
 1) THE WIND LOAD DATA ON SHEET A-1.1 IS NOT CORRECT FOR
 THE 2010 FBC. THE WIND SPEED FOR THIS PROJECT IS 170
 MPH EXPOSURE C. THE CODE NOW REFERENCES ASCE 7-10 NOT
 05. THE CODE NOW REFERENCES ACI-08 NOT THE 2005
 EDITION. PLEASE REVISE. SEE FBC R301.2.1.1 AND CHAPTER
 43
  
 2) FBC R803.2.3.1 REQUIRES THE ROOF SHEATHING TO BE
 FASTENED WITH 8D RING SHANK NAILS IN ALL ROOF ZONES
 REGARDLESS OF THE HEIGHT OF THE STRUCTURE. PLEASE
 REVISE THE NAILING SCHEDULE ON SHEET A-1.1 .
  
 3) SHOW COMPLIANCE WITH FBC R703.6.2 AND ASTM C 1063
 7.11.5 WHICH REQUIRES A FOUNDATION WEEP SCREED AT THE
 BOTTOM OF ALL FRAMED EXTERIOR STUCCO WALLS BELOW THE
 FLOOR LINE WHERE THE WALL IS SUPPORTED BY A FLOOR OR
 FOUNDATION.
  
 4) SHOW COMPLIANCE WITH FBC R703.6.3 WHICH REQUIRES A
 BOND BREAK BETWEEN THE WATER-RESISTIVE BARRIER AND THE
 EXTERIOR STUCCO.
  
 5) SHOW THAT THE UNDER-FLOOR SPACE VENTILATION REQUIRED
 BY FBC R408.1 FOR THE EXISTING CRAWL SPACE WILL NOT BE
 COMPROMISED BY THE ADDITION'S MONOLITHIC FOUNDATION.
  
 6) SUBMIT TWO COPIES OF PRODUCT APPROVALS THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD FOR THE NEW EXTERIOR WINDOWS, BARREL TILE
 ROOFING AND MODIFIED ROOFING FOR THE FLAT ROOF AS
 REQUIRED BY DCA RULE 9N-3 AND CITY AMENDMENTS
 107.3.4.1.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-06-08 Cont ID  
Sent By rlecky Date 2012-06-08 Time 12:58 Rev Time 0.00
Received By rlecky Date 2012-06-08 Time 12:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-05-30 Cont ID  
Sent By rlecky Date 2012-05-30 Time 17:10 Rev Time 0.00
Received By rlecky Date 2012-05-30 Time 16:01 Sent To  
Notes
2012-05-30 17:11:4612050298
 245 MURRAY ROAD
 ADDITION/ RENOVATION
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT
 ALREADY EXIST WITHIN THE RESIDENCE. 2010 FBC R314
 VERIFY WORKING CLEARANCES FOR AC #1 TO THE ELECTRIC
 DISCONNECT AND ACCESS PANELS. NEC 110.26
 THE NEW BATHROOMS REQUIRE A 20 AMP BRANCH CIRCUIT FOR
 RECEPTACLES OUTLETS. NEC 210.11 (C) (3)
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-05-31 Cont ID  
Sent By rmcdouga Date 2012-05-31 Time 11:24 Rev Time 0.00
Received By rmcdouga Date 2012-05-11 Time 13:57 Sent To  
Notes
2012-05-16 13:58:13DIGITAL

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2012-06-14 Cont ID  
Sent By rregueir Date 2012-06-14 Time 08:42 Rev Time 0.00
Received By rregueir Date 2012-06-14 Time 08:42 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2012-05-30 Cont ID  
Sent By rmcdouga Date 2012-05-30 Time 16:12 Rev Time 0.00
Received By rmcdouga Date 2012-05-30 Time 16:12 Sent To  
Notes
2012-05-30 16:13:18AN IMPACT FEE REVIEW BY PALM BEACH COUNTY IS REQUIRED
 BEFORE THE PERMIT IS ISSUED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-05-22 Cont ID  
Sent By rregueir Date 2012-05-22 Time 08:12 Rev Time 0.00
Received By rregueir Date 2012-05-22 Time 08:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-06-11 Cont ID  
Sent By rmcdouga Date 2012-06-11 Time 11:24 Rev Time 0.00
Received By rmcdouga Date 2012-06-11 Time 11:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-05-30 Cont ID  
Sent By rmcdouga Date 2012-05-30 Time 15:58 Rev Time 0.00
Received By rmcdouga Date 2012-05-30 Time 15:57 Sent To  
Notes
2012-05-30 16:12:102010 FBC
  
 DENIED BY PLUMBING
  
 1) THE FIXTURES THAT ARE TIED INTO THE 3" VERTICAL
 STACK ARE NOT PROPERLY VENTED. PER FBCR P3108.2.1 NOT
 MORE THAN ONE WET-VENTED FIXTURE DRAIN SHALL DISCHARGE
 UPSTREAM OF THE DRY-VENTED FIXTURE DRAIN. THERE SHOULD
 BE A VENT BETWEEN THE W.C. AND THE SHOWER OR THE SHOWER
 CAN TIE DIRECTLY INTO THE VERTICAL VENT ABOVE THE WATER
 CLOSETS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2012-06-13 Cont ID  
Sent By ajones Date 2012-06-13 Time 16:32 Rev Time 0.00
Received By ajones Date 2012-06-13 Time 16:32 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2012-06-01 Cont ID  
Sent By ajones Date 2012-06-01 Time 11:14 Rev Time 0.00
Received By ajones Date 2012-06-01 Time 11:14 Sent To  
Notes
2012-06-01 11:20:166/1/12- FAILED. PLANS NEED TO SHOW THE HEIGHT OF THE
 NEW ADDITION FROM THE MEAN HEIGHT OF THE ROOF.
 A SURVEY NEEDS TO BE PROVIDED SHOWING THE LOCATION OF
 THE ADDITION ON THE LOT.
  
 ANGELLA VANN
 561-822-1441
 [email protected]