| Plan Review Stops For Permit 12050298 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2012-06-11 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-06-11 |
Time |
13:53 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-06-11 |
Time |
12:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2012-05-31 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-05-31 |
Time |
11:24 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-05-30 |
Time |
16:55 |
Sent To |
|
|
| Notes |
| 2012-05-31 11:23:11 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) THE WIND LOAD DATA ON SHEET A-1.1 IS NOT CORRECT FOR | | | THE 2010 FBC. THE WIND SPEED FOR THIS PROJECT IS 170 | | | MPH EXPOSURE C. THE CODE NOW REFERENCES ASCE 7-10 NOT | | | 05. THE CODE NOW REFERENCES ACI-08 NOT THE 2005 | | | EDITION. PLEASE REVISE. SEE FBC R301.2.1.1 AND CHAPTER | | | 43 | | | | | | 2) FBC R803.2.3.1 REQUIRES THE ROOF SHEATHING TO BE | | | FASTENED WITH 8D RING SHANK NAILS IN ALL ROOF ZONES | | | REGARDLESS OF THE HEIGHT OF THE STRUCTURE. PLEASE | | | REVISE THE NAILING SCHEDULE ON SHEET A-1.1 . | | | | | | 3) SHOW COMPLIANCE WITH FBC R703.6.2 AND ASTM C 1063 | | | 7.11.5 WHICH REQUIRES A FOUNDATION WEEP SCREED AT THE | | | BOTTOM OF ALL FRAMED EXTERIOR STUCCO WALLS BELOW THE | | | FLOOR LINE WHERE THE WALL IS SUPPORTED BY A FLOOR OR | | | FOUNDATION. | | | | | | 4) SHOW COMPLIANCE WITH FBC R703.6.3 WHICH REQUIRES A | | | BOND BREAK BETWEEN THE WATER-RESISTIVE BARRIER AND THE | | | EXTERIOR STUCCO. | | | | | | 5) SHOW THAT THE UNDER-FLOOR SPACE VENTILATION REQUIRED | | | BY FBC R408.1 FOR THE EXISTING CRAWL SPACE WILL NOT BE | | | COMPROMISED BY THE ADDITION'S MONOLITHIC FOUNDATION. | | | | | | 6) SUBMIT TWO COPIES OF PRODUCT APPROVALS THAT HAVE | | | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER | | | OF RECORD FOR THE NEW EXTERIOR WINDOWS, BARREL TILE | | | ROOFING AND MODIFIED ROOFING FOR THE FLAT ROOF AS | | | REQUIRED BY DCA RULE 9N-3 AND CITY AMENDMENTS | | | 107.3.4.1. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2012-06-08 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-06-08 |
Time |
12:58 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-06-08 |
Time |
12:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2012-05-30 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-05-30 |
Time |
17:10 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-05-30 |
Time |
16:01 |
Sent To |
|
|
| Notes |
| 2012-05-30 17:11:46 | 12050298 | | | 245 MURRAY ROAD | | | ADDITION/ RENOVATION | | | | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT | | | ALREADY EXIST WITHIN THE RESIDENCE. 2010 FBC R314 | | | VERIFY WORKING CLEARANCES FOR AC #1 TO THE ELECTRIC | | | DISCONNECT AND ACCESS PANELS. NEC 110.26 | | | THE NEW BATHROOMS REQUIRE A 20 AMP BRANCH CIRCUIT FOR | | | RECEPTACLES OUTLETS. NEC 210.11 (C) (3) | | | | | | ROBERT LECKY | | | ELECTRIC PLANS EXAMINER | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2012-05-31 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-05-31 |
Time |
11:24 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-05-11 |
Time |
13:57 |
Sent To |
|
|
| Notes |
| 2012-05-16 13:58:13 | DIGITAL |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
N |
Date |
2012-06-14 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2012-06-14 |
Time |
08:42 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2012-06-14 |
Time |
08:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2012-05-30 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-05-30 |
Time |
16:12 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-05-30 |
Time |
16:12 |
Sent To |
|
|
| Notes |
| 2012-05-30 16:13:18 | AN IMPACT FEE REVIEW BY PALM BEACH COUNTY IS REQUIRED | | | BEFORE THE PERMIT IS ISSUED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2012-05-22 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2012-05-22 |
Time |
08:12 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2012-05-22 |
Time |
08:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2012-06-11 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-06-11 |
Time |
11:24 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-06-11 |
Time |
11:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2012-05-30 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-05-30 |
Time |
15:58 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-05-30 |
Time |
15:57 |
Sent To |
|
|
| Notes |
| 2012-05-30 16:12:10 | 2010 FBC | | | | | | DENIED BY PLUMBING | | | | | | 1) THE FIXTURES THAT ARE TIED INTO THE 3" VERTICAL | | | STACK ARE NOT PROPERLY VENTED. PER FBCR P3108.2.1 NOT | | | MORE THAN ONE WET-VENTED FIXTURE DRAIN SHALL DISCHARGE | | | UPSTREAM OF THE DRY-VENTED FIXTURE DRAIN. THERE SHOULD | | | BE A VENT BETWEEN THE W.C. AND THE SHOWER OR THE SHOWER | | | CAN TIE DIRECTLY INTO THE VERTICAL VENT ABOVE THE WATER | | | CLOSETS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2012-06-13 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2012-06-13 |
Time |
16:32 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2012-06-13 |
Time |
16:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2012-06-01 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2012-06-01 |
Time |
11:14 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2012-06-01 |
Time |
11:14 |
Sent To |
|
|
| Notes |
| 2012-06-01 11:20:16 | 6/1/12- FAILED. PLANS NEED TO SHOW THE HEIGHT OF THE | | | NEW ADDITION FROM THE MEAN HEIGHT OF THE ROOF. | | | A SURVEY NEEDS TO BE PROVIDED SHOWING THE LOCATION OF | | | THE ADDITION ON THE LOT. | | | | | | ANGELLA VANN | | | 561-822-1441 | | | [email protected] |
|
|