Plan Review Details - Permit 12050290
Plan Review Stops For Permit 12050290
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-09-10 Cont ID  
Sent By jgomez Date 2012-09-10 Time 11:30 Rev Time 0.00
Received By jgomez Date 2012-09-10 Time 11:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-09-07 Cont ID  
Sent By jgomez Date 2012-09-07 Time 14:57 Rev Time 0.00
Received By jgomez Date 2012-09-07 Time 14:56 Sent To  
Notes
2012-09-07 15:02:48RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW
 COMMENTS.
 2010 FBC.
  
 1- PROPOSING TO USE SINGLE PEEL AND STICK SHINGLES
 UNDERLAYMENT INSTEAD OF 2 LAYERS OF UNDERLAYMENT AS
 REQUIRED BY SEC. R905.2.2:
  
 PROVIDE LETTER ADDRESSED TO THE BUILDING OFFICIAL (DOUG
 WISE) REQUESTING APPROVAL OF THE PROPOSED APPLICATION
 UNDER THE ALTERNATIVE MATERIALS AND METHODS SEC. 104.11
 OF CITY AMENDMENTS TO THE FBC 2010.
 CLARIFY IF USING A DIRECT PEEL AND STICK APPLICATION TO
 THE WOOD DECK. NOA 11-0601.10 SUBMITTED REQUIRES BASE
 SHEET TO BE MECHANICALLY FASTENED. THEREFORE THIS NOA
 CAN'T BE USED. NEED TO PROVIDE PRODUCT APPROVAL THAT
 LISTS DIRECT DECK APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-05-10 Cont ID  
Sent By jgomez Date 2012-05-10 Time 09:35 Rev Time 0.00
Received By jgomez Date 2012-05-10 Time 09:01 Sent To  
Notes
2012-05-10 09:43:27RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS.
 2010 FBC.
  
 1- PROPOSING TO USE SINGLE PEEL AND STICK SHINGLES
 UNDERLAYMENT INSTEAD OF 2 LAYERS OF UNDERLAYMENT AS
 REQUIRED BY SEC. R905.2.2:
  
 PROVIDE LETTER ADDRESSED TO THE BUILDING OFFICIAL (DOUG
 WISE) REQUESTING APPROVAL OF THE PROPOSED APPLICATION
 UNDER THE ALTERNATIVE MATERIALS AND METHODS SEC. 104.11
 OF CITY AMENDMENTS TO THE FBC 2010.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR PEEL AND
 STICK UNDERLAYMENT DESIGNED TO BE USED FOR SHINGLES
 APPLICATION AS REQUIRED BY DCA RULE 9N-3. NOA
 08-0226.06 SUBMITTED IS FOR FLAT ROOF ASSEMBLIES NO FOR
 SHINGLES UNDERLAYMENT.
  
 3- PLEASE NOTE THAT INSTALLING PEEL AND STICK
 UNDERLAYMENT MAY VOID THE SHINGLES WARRANTY AND ROOF
 VENTILATION ISSUES MAY NEED TO BE ADDRESSED. PLEASE
 CONTACT SHINGLES MANUFACTURER AND PLYWOOD ASSOCIATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-09-10 Cont ID  
Sent By jgomez Date 2012-09-10 Time 11:29 Rev Time 0.00
Received By jgomez Date 2012-09-10 Time 11:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-05-10 Cont ID  
Sent By jgomez Date 2012-05-10 Time 09:02 Rev Time 0.00
Received By jgomez Date 2012-05-10 Time 09:01 Sent To  
Notes
***NONE***